Changes for page 12 PLC Protocol OLD

Last modified by Mora Zhou on 2024/12/05 14:53

From version 104.1
edited by Ben
on 2022/08/30 09:49
Change comment: There is no comment for this version
To version 128.1
edited by Ben
on 2022/08/30 14:53
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -511,7 +511,7 @@
511 511  (% style="text-align:center" %)
512 512  [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
513 513  
514 -== **FreeTag Ethernet/IP (CompactLogix)** ==
514 +== **CompactLogix FreeTag Ethernet protocol** ==
515 515  
516 516  Allen-Brandly CompactLogix
517 517  
... ... @@ -568,7 +568,7 @@
568 568  (% style="text-align:center" %)
569 569  [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
570 570  
571 -== **AB PLC address edit** ==
571 +== **MicroLogix 1200** ** protocol** ==
572 572  
573 573  The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
574 574  
... ... @@ -1632,31 +1632,34 @@
1632 1632  **1)HMI Settings**
1633 1633  
1634 1634  |**Item**|**Settings**|**Note**
1635 -|Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
1636 -|Connection|RS422/RS485|
1635 +|Protocol|DELTA AS300 MODBUS RTU|
1636 +|Connection|RS485|
1637 1637  |Baud rate|9600|
1638 -|Data bit|7|
1639 -|Parity|EVEN|
1638 +|Data bit|8|
1639 +|Parity|NONE|
1640 1640  |Stop bit|1|
1641 1641  |PLC station No.|1|
1642 1642  
1643 1643  **2)Address List**
1644 1644  
1645 +
1645 1645  |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1646 -|(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
1647 -|Y|Y|Y o|0~~303237|
1648 -|M|M|M d|0~~99999|
1649 -|T|T|T d|0~~99999|
1650 -|C|C|C d|0~~99999|
1651 -|S|S|S d|0~~99999|
1652 -|(% rowspan="8" %)Word|X|X|Xo|0~~303237|
1653 -|Y|Y|Y o|0~~303237|
1654 -|M|M|M d|0~~99999|
1655 -|T|T|T d|0~~99999|
1656 -|C|C|C d|0~~199|
1657 -|D|D|D d|0~~7999|
1658 -|S|S|S d|0~~99999|
1659 -|SD|SD|SD d|8000~~9999|
1647 +|Bit|X|X|X d|0~~63|
1648 +|Bit|Y|Y|Y d|0~~63|
1649 +|Bit|D|D|D d|0~~29999|
1650 +|Bit|M|M|M d|0~~8191|
1651 +|Bit|SM|SM|SM d|0~~4095|
1652 +|Bit|S|S|S h|0~~2047|
1653 +|Bit|T|T|T d|0~~511|
1654 +|Bit|C|C|C d|0~~511|
1655 +|Bit|HC|HC|HC d|0~~255|
1656 +|Word|X|X|X h|0~~63|
1657 +|Word|Y|Y|Y d|0~~63|
1658 +|Word|SR|SR|SR d|0~~2047|
1659 +|Word|D|D|D d|0~~29999|
1660 +|Word|T|T|T d|0~~511|
1661 +|Word|C|C|C h|0~~511|
1662 +|Word|E|E|E d|0~~9|
1660 1660  
1661 1661  **3)Configure the communication protocol**
1662 1662  
... ... @@ -1666,238 +1666,172 @@
1666 1666  
1667 1667  **4)Cable Wiring**
1668 1668  
1669 -
1672 +Figure
1670 1670  
1671 -== **AS Ethernet Protocol** ==
1674 +[[image:image-20220830141138-1.png]]
1672 1672  
1673 -**1)HMI Settings**
1676 +Pin Definition Diagram
1674 1674  
1675 -**2)Address List**
1678 +[[image:image-20220830095131-1.png]]
1676 1676  
1677 -**3)Configure the communication protocol**
1680 +== **AS Ethernet Protocol** ==
1678 1678  
1679 -**4Cable Wiring**
1682 +**1HMI Settings**
1680 1680  
1681 -= **MODBUS** =
1682 1682  
1683 -== **MODBUS RTU Master** ==
1685 +|=**Items**|=**Settings**|=**Note**
1686 +|Protocol|DELTA AS300 MODBUS TCP|
1687 +|Connection|Ethernet|
1688 +|Port No.|502|
1689 +|Device No.|1|
1690 +|HMI No.|0|
1684 1684  
1685 -Supported Series: MODBUS RTU CONTROLLER
1692 +**2)Address List**
1686 1686  
1687 -HMI works as MODBUS SLAVE connecting with MASTER
1688 1688  
1689 -(% style="text-align:center" %)
1690 -[[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1695 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1696 +|Bit|X|X|X d|0~~63|
1697 +|Bit|Y|Y|Y d|0~~63|
1698 +|Bit|D|D|D d|0~~29999|
1699 +|Bit|M|M|M d|0~~8191|
1700 +|Bit|SM|SM|SM d|0~~4095|
1701 +|Bit|S|S|S h|0~~2047|
1702 +|Bit|T|T|T d|0~~511|
1703 +|Bit|C|C|C d|0~~511|
1704 +|Bit|HC|HC|HC d|0~~255|
1705 +|Word|X|X|X h|0~~63|
1706 +|Word|Y|Y|Y d|0~~63|
1707 +|Word|SR|SR|SR d|0~~2047|
1708 +|Word|D|D|D d|0~~29999|
1709 +|Word|T|T|T d|0~~511|
1710 +|Word|C|C|C h|0~~511|
1711 +|Word|E|E|E d|0~~9|
1691 1691  
1713 +**3)Configure the communication protocol**
1692 1692  
1693 -(% style="text-align:center" %)
1694 -[[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1715 +[[image:image-20220830140537-1.png]]
1695 1695  
1717 +[[image:image-20220830140629-2.png]]
1696 1696  
1697 -(% style="text-align:center" %)
1698 -[[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1719 +**4)Cable Wiring**
1699 1699  
1700 -**HMI Settings**
1721 +Figure
1701 1701  
1702 -(% class="table-bordered" %)
1703 -|**Items**|**Settings**|**Note**
1704 -|Protocol|MODBUS RTU Master|
1705 -|Connection|RS485/RS232|
1706 -|Baud rate|2400~~187500|
1707 -|Data bit|8|
1708 -|Parity|Even/ Odd/ None|
1709 -|Stop bit|1/2|
1710 -|Station No.|0~~255|
1723 +[[image:image-20220830094929-1.png]]
1711 1711  
1712 -**Address List**
1725 +Pin Definition Diagram
1713 1713  
1714 -(% class="table-bordered" %)
1715 -|**Type**|**HMI address**|**MODBUS code**|**Range**
1716 -|Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1717 -|Word|HDW3500~~HDW7999|4|0~~4499
1727 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1718 1718  
1719 -**Cable Wiring**
1729 += Create communication with **Omron** PLC =
1720 1720  
1721 -* **RS485**
1731 +== **CJ TCP FINS Ethemet  Protocol** ==
1722 1722  
1723 -(% style="text-align:center" %)
1724 -[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1733 +Supported device:CJ series
1725 1725  
1726 -(% style="text-align:center" %)
1727 -[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1735 +**1)HMI Settings**
1728 1728  
1729 -* **RS232**
1737 +|=**Items**|=**Settings**|=**Note**
1738 +|Protocol|OMRON CJ TCP FINS Ethemet|
1739 +|Connection|Ethernet|
1740 +|Port No.|9600|
1741 +|Device No.|0|
1742 +|HMI No.|0|(((
1743 +
1744 +)))
1730 1730  
1731 -(% style="text-align:center" %)
1732 -[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1746 +**2)Address List**
1733 1733  
1734 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1748 +|**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1749 +|Bit|CIO|CIO|CIO d|0~~99999|
1750 +|Bit|W|W|W d|0~~99999|
1751 +|Bit|D|D|D d|0~~99999|
1752 +|Bit|H|H|H d|0~~99999|
1753 +|Bit|A|A|A d|0~~99999|
1754 +|Bit|T|T|T h|0~~99999|
1755 +|Bit|CF|CF|CF d|0~~99999|
1756 +|Bit|FF|FF|FF d|0~~99999|
1757 +|Bit|C|C|C d|0~~99999|
1758 +|Bit|EM0|EM0|EM0 d|0~~99999|
1759 +|Bit|EM1|EM1|EM1 d|0~~99999|
1760 +|Bit|EM2|EM2|EM2 d|0~~99999|
1761 +|Bit|EM3|EM3|EM3 d|0~~99999|
1762 +|Bit|EM4|EM4|EM4 d|0~~99999|
1763 +|Bit|EM5|EM5|EM5 h|0~~99999|
1764 +|Bit|EM6|EM6|EM6 d|0~~99999|
1765 +|Bit|EM7|EM7|EM7 d|0~~99999|
1766 +|Bit|EM8|EM8|EM8 d|0~~99999|
1767 +|Bit|EM9|EM9|EM9 d|0~~99999|
1768 +|Bit|EMA|EMA|EMA d|0~~99999|
1769 +|Bit|EMB|EMB|EMB d|0~~99999|
1770 +|Bit|EMC|EMC|EMC d|0~~99999|
1771 +|Bit|Lamp|Lamp|Lamp d|0~~0|
1772 +|Word|CIO|CIO|CIO d|0~~99999|
1773 +|Word|W|W|W d|0~~99999|
1774 +|Word|D|D|D d|0~~99999|
1775 +|Word|H|H|H d|0~~99999|
1776 +|Word|A|A|A d|0~~99999|
1777 +|Word|T|T|T h|0~~99999|
1778 +|Word|CF|CF|CF d|0~~99999|
1779 +|Word|FF|FF|FF d|0~~99999|
1780 +|Word|C|C|C d|0~~99999|
1781 +|Word|EM0|EM0|EM0 d|0~~99999|
1782 +|Word|EM1|EM1|EM1 d|0~~99999|
1783 +|Word|EM2|EM2|EM2 d|0~~99999|
1784 +|Word|EM3|EM3|EM3 d|0~~99999|
1785 +|Word|EM4|EM4|EM4 d|0~~99999|
1786 +|Word|EM5|EM5|EM5 h|0~~99999|
1787 +|Word|EM6|EM6|EM6 d|0~~99999|
1788 +|Word|EM7|EM7|EM7 d|0~~99999|
1789 +|Word|EM8|EM8|EM8 d|0~~99999|
1790 +|Word|EM9|EM9|EM9 d|0~~99999|
1791 +|Word|EMA|EMA|EMA d|0~~99999|
1792 +|Word|EMB|EMB|EMB d|0~~99999|
1793 +|Word|EMC|EMC|EMC d|0~~99999|
1794 +|Word|IR|IR|IR d|0~~99999|
1795 +|Word|DR|DR|DR d|0~~99999|
1735 1735  
1736 -== **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1797 +**3)Configure the communication protocol**
1737 1737  
1738 -Supported Series: MODBUS RTU CONTROLLER
1799 +[[image:image-20220830143348-1.png]]
1739 1739  
1740 -HMI works as MODBUS MASTER connecting with SLAVE.
1801 +[[image:image-20220830143511-2.png]]
1741 1741  
1742 -The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1743 1743  
1744 -(% style="text-align:center" %)
1745 -[[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1746 1746  
1805 +**4)Cable Wiring**
1747 1747  
1748 -(% style="text-align:center" %)
1749 -[[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1807 +Pin Definition Diagram
1750 1750  
1809 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1751 1751  
1752 -(% style="text-align:center" %)
1753 -[[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1811 +(% class="wikigeneratedid" %)
1812 +== ==
1754 1754  
1755 -**HMI Settings**
1814 +(% class="wikigeneratedid" %)
1815 +== ==
1756 1756  
1757 -(% class="table-bordered" %)
1758 -|**Items**|**Settings**|**Note**
1759 -|Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1760 -|Connection|RS485/RS232|
1761 -|Baud rate|2400~~187500|
1762 -|Data bit|8|
1763 -|Parity|Even/ Odd/ None|
1764 -|Stop bit|1/2|
1765 -|PLC station No.|0~~255|
1817 +(% class="wikigeneratedid" %)
1818 +== ==
1766 1766  
1767 -**Address List**
1820 +(% class="wikigeneratedid" %)
1821 +== ==
1768 1768  
1769 -(% class="table-bordered" %)
1770 -|**Type**|**Address Type**|**Function code & Description**
1771 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1772 -|06 (write single register: write a binary value to a holding register)
1773 -|10 (write values to multiple addresses )
1774 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1775 -|06 (write single register: write a binary value to a holding register)
1776 -|10 (write values to multiple addresses )
1777 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1778 -|06 (write single register: write a binary value to a holding register)
1779 -|10 (write values to multiple addresses )
1780 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1781 -|10 (write values to multiple addresses )
1782 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1783 -|05 (Force a single coil to force the on/off state of a logic coil)
1784 -|0F (Write multiple bits, ie write continuously)
1785 -|(% rowspan="3" %)1|02 (Read the input state)
1786 -|05 (Force a single coil to force the on/off state of a logic coil)
1787 -|0F (Write multiple bits)
1788 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1789 -|05 (Force a single coil to force the on/off state of a logic coil)
1790 -|0F (Write multiple bits)
1791 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1792 -|0F (Write multiple bits)
1823 +(% class="wikigeneratedid" %)
1824 +== ==
1793 1793  
1794 -**✎Note:**
1826 +(% class="wikigeneratedid" %)
1827 +== ==
1795 1795  
1796 -* Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1797 -* The function codes sent out are the same as those that read and write words.
1829 +(% class="wikigeneratedid" %)
1830 +== ==
1798 1798  
1799 -**Station number for more than one slaves**
1832 +== **EC55 Protocol** ==
1800 1800  
1801 -If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1802 -
1803 -(% style="text-align:center" %)
1804 -[[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1805 -
1806 -**Cable Wiring**
1807 -
1808 -* **RS485**
1809 -
1810 -(% style="text-align:center" %)
1811 -[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1812 -
1813 -(% style="text-align:center" %)
1814 -[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1815 -
1816 -* **RS232**
1817 -
1818 -(% style="text-align:center" %)
1819 -[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1820 -
1821 -**✎Note:** COM3 only available in PI8000/PI9000 series.
1822 -
1823 -== **MODBUS TCP Slave (All function)** ==
1824 -
1825 -Supported series: MODBUS TCP controller
1826 -
1827 -HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1828 -
1829 -(% style="text-align:center" %)
1830 -[[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1831 -
1832 -(% style="text-align:center" %)
1833 -[[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1834 -
1835 -
1836 -(% style="text-align:center" %)
1837 -[[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1838 -
1839 -**HMI Setting**
1840 -
1841 -(% class="table-bordered" %)
1842 -|**Items**|**Settings**|**Note**
1843 -|Protocol|MODBUS TCP Slave (All function)|
1844 -|Connection|Ethernet|
1845 -|Port No.|502|
1846 -|PLC station No.|1|
1847 -
1848 -**Address List**
1849 -
1850 -(% class="table-bordered" %)
1851 -|**Type**|**Register**|**Function code & Description**
1852 -|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1853 -|06 (write single register: write a binary value to a holding register)
1854 -|10 (write values to multiple addresses )
1855 -|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1856 -|06 (write single register: write a binary value to a holding register)
1857 -|10 (write values to multiple addresses )
1858 -|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1859 -|06 (write single register: write a binary value to a holding register)
1860 -|10 (write values to multiple addresses )
1861 -|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1862 -|10 (write values to multiple addresses )
1863 -|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1864 -|05 (Force a single coil to force the on/off state of a logic coil)
1865 -|0F (Write multiple bits, ie write continuously)
1866 -|(% rowspan="3" %)1|02 (Read the input state)
1867 -|05 (Force a single coil to force the on/off state of a logic coil)
1868 -|0F (Write multiple bits)
1869 -|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1870 -|05 (Force a single coil to force the on/off state of a logic coil)
1871 -|0F (Write multiple bits)
1872 -|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1873 -|0F (Write multiple bits)
1874 -
1875 -**Communication Settings**
1876 -
1877 -Enable HMI Ethernet in [Project Settings];
1878 -
1879 -(% style="text-align:center" %)
1880 -[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1881 -
1882 -Set PLC IP in [Device IP] settings;
1883 -
1884 -(% style="text-align:center" %)
1885 -[[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1886 -
1887 -**Cable Wiring**
1888 -
1889 -(% style="text-align:center" %)
1890 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1891 -
1892 -= **Omron** =
1893 -
1894 -== **EC55** ==
1895 -
1896 1896  Supported device: EC55 temperature instrument
1897 1897  
1898 1898  **HMI Settings**
1899 1899  
1900 -(% class="table-bordered" %)
1901 1901  |**Items**|**Settings**|**Note**
1902 1902  |Protocol|Omron EC55|
1903 1903  |Connection|RS485 (9600, 2, 7, EVEN)|
... ... @@ -1906,7 +1906,6 @@
1906 1906  
1907 1907  **Address List**
1908 1908  
1909 -(% class="table-bordered" %)
1910 1910  |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1911 1911  |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1912 1912  |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
... ... @@ -1952,15 +1952,14 @@
1952 1952  * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1953 1953  * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1954 1954  * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1955 -* (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1891 +* [[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]]Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1956 1956  
1957 -== EtherNet/IP NX series ==
1893 +== **EtherNet/IP NX series Protocol** ==
1958 1958  
1959 1959  Supported series: Omron NX/NJ series
1960 1960  
1961 1961  **HMI Setting**
1962 1962  
1963 -(% class="table-bordered" %)
1964 1964  |**Items**|**Settings**|**Note**
1965 1965  |Protocol|Omron NX Ethernet/IP|
1966 1966  |Connection|Ethernet|
... ... @@ -2012,183 +2012,224 @@
2012 2012  (% style="text-align:center" %)
2013 2013  [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
2014 2014  
2015 -
2016 2016  (% style="text-align:center" %)
2017 2017  [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2018 2018  
2019 2019  **Cable Wiring**
2020 2020  
1955 +[[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
1956 +
1957 += **MODBUS** =
1958 +
1959 +== **MODBUS RTU Master** ==
1960 +
1961 +Supported Series: MODBUS RTU CONTROLLER
1962 +
1963 +HMI works as MODBUS SLAVE connecting with MASTER
1964 +
2021 2021  (% style="text-align:center" %)
2022 -[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1966 +[[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2023 2023  
2024 -= **OpenCAN** =
2025 2025  
2026 -OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1969 +(% style="text-align:center" %)
1970 +[[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2027 2027  
2028 -This protocol is only available in PI8000 series HMI.
2029 2029  
1973 +(% style="text-align:center" %)
1974 +[[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1975 +
2030 2030  **HMI Settings**
2031 2031  
2032 2032  (% class="table-bordered" %)
2033 2033  |**Items**|**Settings**|**Note**
2034 -|Protocol|OPENCAN|
2035 -|Connection|CAN port|
2036 -|Baud rate|250000|
1980 +|Protocol|MODBUS RTU Master|
1981 +|Connection|RS485/RS232|
1982 +|Baud rate|2400~~187500|
1983 +|Data bit|8|
1984 +|Parity|Even/ Odd/ None|
1985 +|Stop bit|1/2|
1986 +|Station No.|0~~255|
2037 2037  
2038 -**CAN frame setting in HMI**
1988 +**Address List**
2039 2039  
2040 -Click [OpenCAN setting] button in communication setting window;
1990 +(% class="table-bordered" %)
1991 +|**Type**|**HMI address**|**MODBUS code**|**Range**
1992 +|Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1993 +|Word|HDW3500~~HDW7999|4|0~~4499
2041 2041  
2042 -(% style="text-align:center" %)
2043 -[[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1995 +**Cable Wiring**
2044 2044  
2045 -Click [Add] to create a new frame;
1997 +* **RS485**
2046 2046  
2047 2047  (% style="text-align:center" %)
2048 -[[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
2000 +[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2049 2049  
2050 -(% class="table-bordered" %)
2051 -|**No**|**Items**|**Description**
2052 -|1|Add|add a frame related to register address
2053 -|2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
2054 -|3|Frame manager|This list shows some of the main parameters for each frame that the user adds
2055 -|4|Modify|Modify the frames in frame management
2056 -|5|Copy|Copy one frame to another
2057 -|6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
2058 -|7|Empty|All frames in the list are cleared
2059 -|8|Browse|Displays configuration files in XML format in IE
2060 -|9|OK|Complete the configuration of the frame and exit
2002 +(% style="text-align:center" %)
2003 +[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2061 2061  
2062 -Set CANBUS frame in setting windows
2005 +* **RS232**
2063 2063  
2064 2064  (% style="text-align:center" %)
2065 -[[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
2008 +[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2066 2066  
2067 -(% class="table-bordered" %)
2068 -|**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
2069 -|1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
2070 -|2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
2071 -|3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
2072 -|4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
2073 -|5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
2074 -|6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
2075 -Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
2010 +**✎Note:** COM3 only available in PI8000/PI9000 series.
2076 2076  
2077 -**Edit:** Set a bit or word address by its format;
2012 +== **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
2078 2078  
2079 -**Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
2080 -)))
2081 -|(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
2082 -|(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
2083 -|(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
2084 -|(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
2085 -|(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
2086 -|(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
2087 -|(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
2088 -|(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
2089 -|(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
2090 -|(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
2091 -|(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
2092 -|9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
2093 -|10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
2094 -|11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
2095 -|12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
2096 -|13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
2097 -|14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
2098 -|15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
2014 +Supported Series: MODBUS RTU CONTROLLER
2099 2099  
2100 -Set CAN address (Read or write operation);
2016 +HMI works as MODBUS MASTER connecting with SLAVE.
2101 2101  
2018 +The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
2019 +
2102 2102  (% style="text-align:center" %)
2103 -[[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
2021 +[[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2104 2104  
2105 -(% class="table-bordered" %)
2106 -|**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
2107 -|1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
2108 -|(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
2109 -|(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
2110 -|(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
2111 -|(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
2112 -|(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
2113 -|(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
2114 -* If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
2115 -* Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
2116 -)))
2117 -|(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
2118 -|(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
2119 -|4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
2120 -|5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
2121 2121  
2122 -**Multiple Packages Settings**
2024 +(% style="text-align:center" %)
2025 +[[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2123 2123  
2027 +
2124 2124  (% style="text-align:center" %)
2125 -[[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
2029 +[[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
2126 2126  
2127 -Check [Multiple packages supported] to open [Multiple package data] window, as below show.
2031 +**HMI Settings**
2128 2128  
2129 -Select Multiple package type
2033 +(% class="table-bordered" %)
2034 +|**Items**|**Settings**|**Note**
2035 +|Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
2036 +|Connection|RS485/RS232|
2037 +|Baud rate|2400~~187500|
2038 +|Data bit|8|
2039 +|Parity|Even/ Odd/ None|
2040 +|Stop bit|1/2|
2041 +|PLC station No.|0~~255|
2130 2130  
2131 -* Not Multiple packages
2132 -* J1939 Multiple packages
2133 -* Customized Multiple packages
2043 +**Address List**
2134 2134  
2135 -Click [Edit Receive data] for [Receive] settings
2045 +(% class="table-bordered" %)
2046 +|**Type**|**Address Type**|**Function code & Description**
2047 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2048 +|06 (write single register: write a binary value to a holding register)
2049 +|10 (write values to multiple addresses )
2050 +|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2051 +|06 (write single register: write a binary value to a holding register)
2052 +|10 (write values to multiple addresses )
2053 +|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2054 +|06 (write single register: write a binary value to a holding register)
2055 +|10 (write values to multiple addresses )
2056 +|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2057 +|10 (write values to multiple addresses )
2058 +|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2059 +|05 (Force a single coil to force the on/off state of a logic coil)
2060 +|0F (Write multiple bits, ie write continuously)
2061 +|(% rowspan="3" %)1|02 (Read the input state)
2062 +|05 (Force a single coil to force the on/off state of a logic coil)
2063 +|0F (Write multiple bits)
2064 +|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2065 +|05 (Force a single coil to force the on/off state of a logic coil)
2066 +|0F (Write multiple bits)
2067 +|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2068 +|0F (Write multiple bits)
2136 2136  
2137 -* Start code+ Total length (J1939)
2070 +**✎Note:**
2138 2138  
2139 -(% style="text-align:center" %)
2140 -[[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2072 +* Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
2073 +* The function codes sent out are the same as those that read and write words.
2141 2141  
2142 -As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
2075 +**Station number for more than one slaves**
2143 2143  
2144 -* Start code + Data max length (J1939)
2077 +If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
2145 2145  
2146 2146  (% style="text-align:center" %)
2147 -[[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2080 +[[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
2148 2148  
2149 -As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
2082 +**Cable Wiring**
2150 2150  
2151 -* Data max length (J1939)
2084 +* **RS485**
2152 2152  
2153 2153  (% style="text-align:center" %)
2154 -[[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
2087 +[[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2155 2155  
2156 -As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
2089 +(% style="text-align:center" %)
2090 +[[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
2157 2157  
2158 -* Customized multiple package
2092 +* **RS232**
2159 2159  
2160 2160  (% style="text-align:center" %)
2161 -[[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
2095 +[[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
2162 2162  
2163 -As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
2097 +**✎Note:** COM3 only available in PI8000/PI9000 series.
2164 2164  
2165 -Click [Edit Send data] for [Send] setting
2099 +== **MODBUS TCP Slave (All function)** ==
2166 2166  
2167 -* J1939
2101 +Supported series: MODBUS TCP controller
2168 2168  
2103 +HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
2104 +
2169 2169  (% style="text-align:center" %)
2170 -[[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
2106 +[[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
2171 2171  
2172 -[Data] is all data to be sent.
2108 +(% style="text-align:center" %)
2109 +[[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
2173 2173  
2174 -Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
2175 2175  
2176 -* Customized multiple package
2112 +(% style="text-align:center" %)
2113 +[[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
2177 2177  
2115 +**HMI Setting**
2116 +
2117 +(% class="table-bordered" %)
2118 +|**Items**|**Settings**|**Note**
2119 +|Protocol|MODBUS TCP Slave (All function)|
2120 +|Connection|Ethernet|
2121 +|Port No.|502|
2122 +|PLC station No.|1|
2123 +
2124 +**Address List**
2125 +
2126 +(% class="table-bordered" %)
2127 +|**Type**|**Register**|**Function code & Description**
2128 +|(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
2129 +|06 (write single register: write a binary value to a holding register)
2130 +|10 (write values to multiple addresses )
2131 +|(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
2132 +|06 (write single register: write a binary value to a holding register)
2133 +|10 (write values to multiple addresses )
2134 +|(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
2135 +|06 (write single register: write a binary value to a holding register)
2136 +|10 (write values to multiple addresses )
2137 +|(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
2138 +|10 (write values to multiple addresses )
2139 +|(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
2140 +|05 (Force a single coil to force the on/off state of a logic coil)
2141 +|0F (Write multiple bits, ie write continuously)
2142 +|(% rowspan="3" %)1|02 (Read the input state)
2143 +|05 (Force a single coil to force the on/off state of a logic coil)
2144 +|0F (Write multiple bits)
2145 +|(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
2146 +|05 (Force a single coil to force the on/off state of a logic coil)
2147 +|0F (Write multiple bits)
2148 +|(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
2149 +|0F (Write multiple bits)
2150 +
2151 +**Communication Settings**
2152 +
2153 +Enable HMI Ethernet in [Project Settings];
2154 +
2178 2178  (% style="text-align:center" %)
2179 -[[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
2156 +[[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2180 2180  
2181 -[Data] is all data to be sent.
2158 +Set PLC IP in [Device IP] settings;
2182 2182  
2183 -As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
2160 +(% style="text-align:center" %)
2161 +[[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2184 2184  
2185 2185  **Cable Wiring**
2186 2186  
2187 2187  (% style="text-align:center" %)
2188 -[[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
2166 +[[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2189 2189  
2190 -**✎Note:** The address interval between each frame need to be more than a word address;
2191 -
2192 2192  = **SHIMADEN** =
2193 2193  
2194 2194  == **FP23** ==
... ... @@ -2988,3 +2988,168 @@
2988 2988  **Cable Wiring**
2989 2989  
2990 2990  [[image:https://docs.we-con.com.cn/bin/download/PIStudio/12.PLC%20protocols/WebHome/12.PLC%20Protocol_html_2297240b57346b2a.png?width=401&height=170&rev=1.1||alt="12.可编程逻辑控制器Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
2967 +
2968 +
2969 += **OpenCAN** =
2970 +
2971 +OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
2972 +
2973 +This protocol is only available in PI8000 series HMI.
2974 +
2975 +**HMI Settings**
2976 +
2977 +|**Items**|**Settings**|**Note**
2978 +|Protocol|OPENCAN|
2979 +|Connection|CAN port|
2980 +|Baud rate|250000|
2981 +
2982 +**CAN frame setting in HMI**
2983 +
2984 +Click [OpenCAN setting] button in communication setting window;
2985 +
2986 +(% style="text-align:center" %)
2987 +[[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
2988 +
2989 +Click [Add] to create a new frame;
2990 +
2991 +(% style="text-align:center" %)
2992 +[[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
2993 +
2994 +|**No**|**Items**|**Description**
2995 +|1|Add|add a frame related to register address
2996 +|2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
2997 +|3|Frame manager|This list shows some of the main parameters for each frame that the user adds
2998 +|4|Modify|Modify the frames in frame management
2999 +|5|Copy|Copy one frame to another
3000 +|6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
3001 +|7|Empty|All frames in the list are cleared
3002 +|8|Browse|Displays configuration files in XML format in IE
3003 +|9|OK|Complete the configuration of the frame and exit
3004 +
3005 +Set CANBUS frame in setting windows
3006 +
3007 +(% style="text-align:center" %)
3008 +[[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
3009 +
3010 +|**No**|**Items**|**Description**
3011 +|1|ID|Set the ID of a can frame in hexadecimal format;
3012 +|2|ID assign|split the ID by PF, PS, and SA;
3013 +|3|Frame type|Select Standard frame or Extended Frame;
3014 +|4|Frame format|Select between data frame and remote Frame;
3015 +|5|Data|Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
3016 +|6|Use address|(((
3017 +Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
3018 +
3019 +**Edit:** Set a bit or word address by its format;
3020 +
3021 +**Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
3022 +)))
3023 +|(% rowspan="8" %)7|(% rowspan="8" %)Data interactive configuration|There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
3024 +|Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
3025 +|Feedback mode: feedback mode includes no response, confirm response and data response;
3026 +|No response: the device or touch screen will not receive feedback;
3027 +|Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
3028 +|Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
3029 +|response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
3030 +|Response timeout: sets whether the response frame timeout;
3031 +|(% rowspan="3" %)8|(% rowspan="3" %)Control address|If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
3032 +|Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
3033 +|Manually send: a manually send tick indicates only one send;
3034 +|9|Flag configuration|Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
3035 +|10|Note|Fill the text to explain the meaning of the frame;
3036 +|11|Data assign|Preview the display in this table based on the address and the corresponding number of digits;
3037 +|12|Current operation display|Display the description of current operation;
3038 +|13|Add|Add a new frame;
3039 +|14|Save frame|Save the configured frame format;
3040 +|15|Cancel|Cancel the frame configuration;
3041 +
3042 +Set CAN address (Read or write operation);
3043 +
3044 +(% style="text-align:center" %)
3045 +[[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
3046 +
3047 +|**No.**|**Item**|**Description**
3048 +|1|Current address|Displays the register type and register address set by the user in the data access interface
3049 +|(% rowspan="3" %)2|(% rowspan="3" %)Trigger|Two operations, "read" and "write," are based on on-screen registers
3050 +|If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
3051 +|If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
3052 +|(% rowspan="5" %)3|(% rowspan="3" %)Data operation|The read and write operations in the trigger conditions are set accordingly.
3053 +|If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
3054 +|If the trigger condition is a writing operation, there are two situations:(((
3055 +* If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
3056 +* Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
3057 +)))
3058 +|(% rowspan="2" %)Position and length input format|If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
3059 +|If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
3060 +|4|Add|Add current configuration
3061 +|5|Close|Close the configuration window to exit
3062 +
3063 +**Multiple Packages Settings**
3064 +
3065 +(% style="text-align:center" %)
3066 +[[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
3067 +
3068 +Check [Multiple packages supported] to open [Multiple package data] window, as below show.
3069 +
3070 +Select Multiple package type
3071 +
3072 +* Not Multiple packages
3073 +* J1939 Multiple packages
3074 +* Customized Multiple packages
3075 +
3076 +Click [Edit Receive data] for [Receive] settings
3077 +
3078 +* Start code+ Total length (J1939)
3079 +
3080 +(% style="text-align:center" %)
3081 +[[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3082 +
3083 +As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
3084 +
3085 +* Start code + Data max length (J1939)
3086 +
3087 +(% style="text-align:center" %)
3088 +[[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3089 +
3090 +As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
3091 +
3092 +* Data max length (J1939)
3093 +
3094 +(% style="text-align:center" %)
3095 +[[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
3096 +
3097 +As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
3098 +
3099 +* Customized multiple package
3100 +
3101 +(% style="text-align:center" %)
3102 +[[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
3103 +
3104 +As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
3105 +
3106 +Click [Edit Send data] for [Send] setting
3107 +
3108 +* J1939
3109 +
3110 +(% style="text-align:center" %)
3111 +[[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
3112 +
3113 +[Data] is all data to be sent.
3114 +
3115 +Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
3116 +
3117 +* Customized multiple package
3118 +
3119 +(% style="text-align:center" %)
3120 +[[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
3121 +
3122 +[Data] is all data to be sent.
3123 +
3124 +As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
3125 +
3126 +**Cable Wiring**
3127 +
3128 +(% style="text-align:center" %)
3129 +[[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
3130 +
3131 +**✎Note:** The address interval between each frame need to be more than a word address;
image-20220830094929-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +90.4 KB
Content
image-20220830095131-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +25.7 KB
Content
image-20220830140537-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +35.2 KB
Content
image-20220830140629-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +48.4 KB
Content
image-20220830141138-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +82.9 KB
Content
image-20220830143348-1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +35.9 KB
Content
image-20220830143511-2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Ben
Size
... ... @@ -1,0 +1,1 @@
1 +46.3 KB
Content