Wiki source code of 11 PLC Protocol

Version 64.1 by Ben on 2022/08/29 13:46

Show last authors
1 (((
2 (% class="wikigeneratedid" id="HPLCprotocols" %)
3 **Introduction**
4 )))
5
6 This chapter contains information on configuring the communication between device and HMI.
7
8 **General Procedure**
9
10 During configuring communication in PIStudio. The following components and conditions is indeed at least.
11
12 * One PI HMI
13 * One connected controller (for example PLC)
14 * One Cable Wiring
15
16 (% style="text-align:center" %)
17 [[image:12.PLC Protocol_html_4d84fc52012aaad6.png||data-xwiki-image-style-alignment="center" height="461" width="521" class="img-thumbnail"]]
18
19 User need to select controller protocol and set communication parameters in HMI project. Please note to set same communication parameter between controller and HMI project. After finishing project, user could download HMI project into HMI and connect HMI with controller by Cable Wiring. Thena simple automation system would be established.
20
21 = **Communication Settings** =
22
23 For example, controller is WECON LX3V series PLC and HMI is PI8070. Please set communication protocol, and set communication parameters in the [Communication].
24
25 **Timeout**
26
27 The follwoing are description for the timeout settings from [Communication].
28
29 (% style="text-align:center" %)
30 [[image:Communication Timout settings.png||data-xwiki-image-style-alignment="center" class="img-thumbnail"]]
31
32 * Wait Timeout(ms): The time HMI waits for a response from the PLC.
33 * Receive Timeout(ms): The longest waiting interval between the HMI receiving two characters.
34 * Retry Count: The number of retries when there is no response in the communication between HMI and PLC.
35 * Retry Timeout(s): The PLC will not be accessed during the Retry Timeout period when there is no response in the communication between HMI and PLC.
36 * Delay Time(ms): The speed at which the HMI communicates with the device.
37 * Continuous Length: Default value 0 means the maximum length specified by each protocol. Addresses dealt by Maximum Span settings, its read length for single time, if the Continouous Length is 1, which means it will read/write the every register one by one. If the length of Maximum Span is greater than or equal to the Continuous Length, the continuous read/write will be performed in groups according to Continuous Length.
38 * Maximum Span:  Set the interval for reading PLC addresses. If there exists two same register type addresses, their interval is less than the set value of Maximum Span, then they will be integrated into a continuous address, otherwise it will be divide into two independent addresses.
39
40 **Operating Procedure**
41
42 After creating the [Quick_Start] project,select the [Project]->[Communication].
43
44 (% style="text-align:center" %)
45 [[image:12.PLC Protocol_html_39c0d342e4b1dd27.png||data-xwiki-image-style-alignment="center" height="128" width="294" class="img-thumbnail"]]
46
47 Click “Setting” to open protocol setting windows.
48
49 (% id="cke_bm_5533S" style="display:none" %) [[image:12.PLC Protocol_html_7b55815442c5544a.png||height="450" width="537"]]
50
51 Select communication protocol, users could select serial port, Ethernet port, CAN port or USB.
52
53 * Serial port:
54
55 (% style="text-align:center" %)
56 [[image:12.PLC Protocol_html_bc7e88067e699a2b.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
57
58 * Ethernet port:
59
60 (% style="text-align:center" %)
61 [[image:12.PLC Protocol_html_c3865bcb998b6ded.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
62
63 * CAN port (In COM1):
64
65 (% style="text-align:center" %)
66 [[image:12.PLC Protocol_html_61c3c5fa99a24463.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
67
68 * USB port:
69
70 (% id="cke_bm_5554S" style="display:none" %) [[image:12.PLC Protocol_html_a3105a98b48fb9b7.png||height="242" width="500"]]
71
72 About parameters for communication, PLC default communication parameters have been written to PIStudio, the user can adjust them according to the actual situation.
73
74 * Serial port:
75
76 (% style="text-align:center" %)
77 [[image:12.PLC Protocol_html_36a660d5c1a17a95.png||data-xwiki-image-style-alignment="center" height="228" width="600" class="img-thumbnail"]]
78
79 * Ethernet port
80
81 Please note, during using Ethernet port, please set HMI IP in [Project Setting], the detailed, please refer to [Project Setting] chapter.
82
83 (% style="text-align:center" %)
84 [[image:12.PLC Protocol_html_eebfc6b1337ea860.png||data-xwiki-image-style-alignment="center" height="207" width="600" class="img-thumbnail"]]
85
86 Click [OK] button to save settings and close the dialog;
87
88 = Create communication with WECON PLC =
89
90 == HMI settings ==
91
92 **Download PIStudio Software**
93
94 Please visit the link below to get the latest version PIstudio for HMI programming:
95
96 * [[Download link>>doc:PIStudio.Download.3 Software.WebHome]]
97
98 **Create a new HMI project connect with PLC**
99
100 Check the link below for the video to show you how to get started with a new project
101
102 * [[Video>>https://youtu.be/0FpmDZe_8U8]]
103
104 For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
105
106 **General**
107
108 HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
109
110 **Protocol settings**
111
112 The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
113
114 Please select the protocol, when creating a new project.
115
116 1. Select the COM port for communication;
117 1. PLC type: It means PLC brand, like WECON;
118 1. PLC model: It shows the model of PLC, such as LX3V;
119
120 (% style="text-align:center" %)
121 [[image:image-20220819093729-1.png]]
122
123 If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
124
125 (% style="text-align:center" %)
126 [[image:image-20220819093729-2.png]]
127
128
129 The steps to change the protocol for project are as follows.
130
131 1. Click [Setting] to open the [Communication device] window;
132 1. Select communication port, such as COM1;
133 1. Select Serial port for communication, such as RS422;
134 1. Select device type (device brand), such as WECON;
135 1. Select the protocol for communication, such as WECON LX3V;
136
137 (% style="text-align:center" %)
138 [[image:image-20220819093729-3.png]]
139
140 **Parameter settings**
141
142 The parameters settings are in [Communication] window, shown as following below.
143
144 1. Click [Setting] to open the [COM port setting] window;
145 1. Set the parameters such as [connection], [Baud rate] and so on;
146
147 (% style="text-align:center" %)
148 [[image:image-20220819093729-4.png||height="636" width="818"]]
149
150 (% start="3" %)
151 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
152
153 (% style="text-align:center" %)
154 [[image:image-20220819093729-5.png]]
155
156 **Set PLC address in HMI screen**
157
158 1. Place the objects to HMI screen;
159 1. Double-click the object to open the setting window;
160 1. Click “Edit” to open the address setting windows;
161 1. Connection: select the serial port in HMI;
162 1. Address type: All the PLC address types will be display in this list, such as M;
163 1. Address No.: Please input the number of this address, such as 0;
164
165 [[image:image-20220819093729-6.jpeg]]
166
167 **Communication cable**
168
169 In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
170
171 (% style="text-align:center" %)
172 [[image:image-20220819093729-7.png]]
173
174 **HMI communication PLC use Modbus **
175
176 * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
177 * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
178
179 == PLC settings ==
180
181 **Download PLC Software**
182
183 Please visit below link to get the latest version PLC Editor for HMI programming
184
185 * LX3V:[[Download link>>doc:PLC Editor.10 Hardware .Software.WebHome]]
186 * LX5V:[[Download link>>doc:PLC Editor2.Download.03 Software.WebHome]]
187
188 **Start a new PLC project**
189
190 Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
191
192 (% style="text-align:center" %)
193 [[image:image-20220819101447-3.jpeg]]
194
195
196
197 **Add a new instruction **
198
199 Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
200
201 (% style="text-align:center" %)
202 [[image:image-20220819105530-1.png]]
203
204 You could also select the ladder symbol from the menu bar directly.
205
206 [[image:image-20220819093729-11.png]]
207
208 [[image:image-20220819093729-12.png]]
209
210 **Add comment to PLC program**
211
212 (% style="text-align:center" %)
213 [[image:image-20220819105630-3.png]]
214
215 **Add the statement to PLC program**
216
217 Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
218
219 (% style="text-align:center" %)
220 [[image:image-20220819105644-4.png]]
221
222 **Compile **
223
224 You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
225
226 [[image:image-20220819093729-15.png]]
227
228 **Download setting **
229
230 Click on “Transfer Setup” to select download mode.
231
232 [[image:image-20220820150853-1.png]]**Download PLC program to PLC**
233
234 Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
235
236 [[image:image-20220819093729-17.png]]
237
238 **Upload PLC program from PLC**
239
240 Read the PLC program from PLC to computer.
241
242 [[image:image-20220819093729-18.png]]
243
244 **Device monitor**
245
246 Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
247
248 [[image:image-20220819093730-19.png]]
249
250 **Online monitor**
251
252 Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
253
254 [[image:image-20220819093730-20.png]]
255
256 **Monitor edit**
257
258 In this mode, you could edit the PLC program during PLC is running. 
259
260
261 (% style="text-align:center" %)
262 [[image:image-20220819105928-9.png||height="229" width="669"]]
263
264 = **WECON PLC** =
265
266 Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
267
268 **HMI Settings**
269
270 (% class="table-bordered" %)
271 |**Item**|**Settings**|**Note**
272 |Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
273 |Connection|RS422/RS485|
274 |Baud rate|9600|
275 |Data bit|7|
276 |Parity|EVEN|
277 |Stop bit|1|
278 |PLC station No.|1|
279
280 **Address List**
281
282 (% class="table-bordered" %)
283 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
284 |(% rowspan="6" %)Bit|X|X|Xo|0~~303237|
285 |Y|Y|Y o|0~~303237|
286 |M|M|M d|0~~99999|
287 |T|T|T d|0~~99999|
288 |C|C|C d|0~~99999|
289 |S|S|S d|0~~99999|
290 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
291 |Y|Y|Y o|0~~303237|
292 |M|M|M d|0~~99999|
293 |T|T|T d|0~~99999|
294 |C|C|C d|0~~199|
295 |D|D|D d|0~~7999|
296 |S|S|S d|0~~99999|
297 |SD|SD|SD d|8000~~9999|
298
299 **Cable Wiring**
300
301 * **RS485**
302
303 (% style="text-align:center" %)
304 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
305
306 * **RS422**
307
308 (% style="text-align:center" %)
309 [[image:12.PLC Protocol_html_5c7fca9a70da2ee8.png||data-xwiki-image-style-alignment="center" height="247" width="389" class="img-thumbnail"]]
310
311 **✎Note:**
312
313 * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
314 * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
315
316 [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
317
318
319 == **HMI and Wecon LX5V serial communication** ==
320
321 This example introduces the establishment of serial port communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
322
323 **Software configuration of PLC**
324
325 **1)PLC programming software**
326
327 [[image:image-20220810164710-1.png]]
328
329 **2)New PLC project**
330
331 Click New Project and select the PLC model.
332
333 [[image:image-20220810172412-1.png]]
334
335
336 **3)Set Serial port parameters**
337
338 Follow the steps below to configure Serial port parameters
339
340 Baud rate:115200
341
342 Data bit:8
343
344 Stop bit:1
345
346 Parity:No verification
347
348 [[image:image-20220810165759-3.png]]
349
350
351 **4)Registers list**
352
353 [[image:image-20220811102219-3.png]]
354
355
356 **HMI software configuration**
357
358 **1)HMI programming software**
359
360 [[image:image-20220810171237-4.png]]
361
362 **2)New HMI project**
363
364 Click New Project and select the HMI model.
365
366 [[image:image-20220810172010-5.png]]
367
368 **3)Set communication port parameters**
369
370 Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
371
372 Baud rate:115200
373
374 Data bit:8
375
376 Stop bit:1
377
378 Parity:No verification
379
380
381 [[image:image-20220811104012-1.png]]
382
383
384 **hardware connection**
385
386 **1)Hardware wiring diagram**
387
388 This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
389
390 [[image:image-20220811103005-4.png]]
391
392
393 [[image:image-20220811103227-7.png]]
394
395 The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
396
397 == **HMI and Wecon LX5V-N Ethernet communication** ==
398
399 (% id="cke_bm_147709S" style="display:none" %) (%%)This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V. It is introduced through three parts: PLC software configuration, HMI software configuration, and hardware wiring.
400
401
402 **Software configuration of PLC**
403
404 **1)PLC programming software**
405
406 [[image:image-20220810164710-1.png]]
407
408 **2)New PLC project**
409
410 Click New Project and select the PLC model.
411
412 [[image:image-20220811115454-1.png]]
413
414
415 **3)Set Ethernet port parameters**
416
417 Follow the steps below to configure Ethernet parameters
418
419 PLC IP address:192.168.39.200
420
421 default gateway:192.168.39.1
422
423 subnet mask:255.255.255.0
424
425 [[image:image-20220811140530-2.png]]
426
427
428 **4)Registers list**
429
430 [[image:image-20220811102219-3.png]]
431
432
433 **HMI software configuration**
434
435 **1)HMI programming software**
436
437 [[image:image-20220810171237-4.png]]
438
439 **2)New HMI project**
440
441 Click New Project and select the HMI model.
442
443 [[image:image-20220810172010-5.png]]
444
445 **3)Set communication port parameters**
446
447 Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
448
449 HMI IP address:192.168.39.201
450
451 default gateway:192.168.39.1
452
453 subnet mask:255.255.255.0
454
455 [[image:image-20220811170753-2.png]]
456
457 Next, click Communication Settings to configure the IP of the HMI communication object.
458
459 [[image:image-20220811163047-1.png]]
460
461 **hardware connection**
462
463 **1)Hardware wiring diagram**
464
465 This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
466
467 [[image:image-20220811170248-1.png]]
468
469 The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.
470
471 (% class="wikigeneratedid" %)
472 = =
473
474 = **Allen-Bradley** =
475
476 == **FreeTag Ethernet/IP (CompactLogix)** ==
477
478 Allen-Brandly CompactLogix
479
480 **HMI Settings**
481
482 (% class="table-bordered" %)
483 |**Items**|**Settings**|**Note**
484 |Protocol|Allen-Brandley FreeTag Ethernet/IP (CompactLogix)|
485 |Connection|Ethernet|
486 |Port No.|44818|
487
488 **PLC Setting**
489
490 Create new tags
491
492 (% style="text-align:center" %)
493 [[image:12.PLC Protocol_html_a748a27dcf7f1124.png||data-xwiki-image-style-alignment="center" height="411" width="700" class="img-thumbnail"]]
494
495 Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
496
497 (% style="text-align:center" %)
498 [[image:12.PLC Protocol_html_151379170bb8ff3e.png||data-xwiki-image-style-alignment="center" height="352" width="700" class="img-thumbnail"]]
499
500 Import labels, please open [Communication] window and click [Import label];
501
502 Select csv file, all tags will be displayed as belows;
503
504 (% style="text-align:center" %)
505 [[image:12.PLC Protocol_html_af192e54dee96f38.png||data-xwiki-image-style-alignment="center" height="586" width="700" class="img-thumbnail"]]
506
507 **✎Note:**
508
509 Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
510
511 (% style="text-align:center" %)
512 [[image:12.PLC Protocol_html_33df1d63ebe53726.png||data-xwiki-image-style-alignment="center" height="206" width="700" class="img-thumbnail"]]
513
514 The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
515
516 **Communication settings in HMI**
517
518 Enable HMI Ethernet in [Project Settings];
519
520 (% style="text-align:center" %)
521 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="106" width="400" class="img-thumbnail"]]
522
523 Set PLC IP in [Device IP] settings;
524
525 (% style="text-align:center" %)
526 [[image:12.PLC Protocol_html_27870d373581892e.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
527
528 **Cable Wiring**
529
530 (% style="text-align:center" %)
531 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="400" class="img-thumbnail"]]
532
533 == **MicroLogix** ==
534
535 MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
536
537 **HMI Settings**
538
539 (% class="table-bordered" %)
540 |**Item**|**Settings**|**Note**
541 |Protocol|Allen-Bradlley MicroLogix|
542 |Connection|RS232|
543 |Baud rate|19200|
544 |Data bit|8|
545 |Parity|None|
546 |Stop bit|1|
547 |PLC station No.|1|
548
549 **Address List**
550
551 (% class="table-bordered" %)
552 |**Type**|**Device registers**|**Format**|**Range**|**Note**
553 |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
554 |O|O d.d|0.0~~255.15|
555 |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
556 |S|S d.d|0.0~~255.15|
557 |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
558 |(% rowspan="9" %)Word|S|S d|0~~255|
559 |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
560 |TP|TP nnhh|0~~ffff
561 |CS|CS nnhh|0~~ffff
562 |CP|CP nnhh|0~~ffff
563 |N|N nnhh|0~~ffff
564 |C|C nnhh|0~~ffff
565 |T|T nnhh|0~~ffff
566 |R|R nnhh|0~~ffff
567
568 **Cable Wiring**
569
570 (% style="text-align:center" %)
571 [[image:12.PLC Protocol_html_58205bdf82c06d4.png||data-xwiki-image-style-alignment="center" height="307" width="500" class="img-thumbnail"]]
572
573 == **AB PLC address edit** ==
574
575 The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
576
577 * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
578 * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
579 * **Word address S:** The word address ranges from 0 to 255 (decimal).
580 * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
581
582 **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
583
584 |(% style="width:393px" %)**PLC bit address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
585 |(% style="width:393px" %)I|(% style="width:350px" %)dd.dd|(% style="width:333px" %)I 0.0 ~~ 255.15
586 |(% style="width:393px" %)O|(% style="width:350px" %)dd.dd|(% style="width:333px" %)O 0.0 ~~ 255.15
587 |(% style="width:393px" %)B|(% style="width:350px" %)fff.dd|(% style="width:333px" %)B 000.0 ~~ fff.15
588 |(% style="width:393px" %)S|(% style="width:350px" %)dd.dd|(% style="width:333px" %)S 0.0 ~~ 255.15
589 |(% style="width:393px" %)N|(% style="width:350px" %)ffff.dd|(% style="width:333px" %)N 000.0 ~~ fff.15
590 |(% style="width:393px" %)**PLC word address type**|(% style="width:350px" %)**Address format**|(% style="width:333px" %)**Address range**
591 |(% style="width:393px" %)S|(% style="width:350px" %)ddd|(% style="width:333px" %)S0 ~~ 255
592 |(% style="width:393px" %)TS|(% style="width:350px" %)ffff|(% style="width:333px" %)TS0 ~~ FFFF
593 |(% style="width:393px" %)TP|(% style="width:350px" %)ffff|(% style="width:333px" %)TP0 ~~ FFFF
594 |(% style="width:393px" %)CS|(% style="width:350px" %)ffff|(% style="width:333px" %)CS0 ~~ FFFF
595 |(% style="width:393px" %)CP|(% style="width:350px" %)ffff|(% style="width:333px" %)CP0 ~~ FFFF
596 |(% style="width:393px" %)N|(% style="width:350px" %)ffff|(% style="width:333px" %)N0 ~~ FFFF
597 |(% style="width:393px" %)F|(% style="width:350px" %)ffff|(% style="width:333px" %)F0 ~~ FFFF
598
599 = **Barcode Scanner** =
600
601 Supported: DELI 14880 barcode scanner
602
603 **HMI Setting**
604
605 (% class="table-bordered" %)
606 |**Items**|**Settings**|**Note**
607 |Protocol|Barcode Scanner|
608 |Connection|USB|
609
610 **Operating Procedures**
611
612 Select [Barcode Scanner];
613
614 (% style="text-align:center" %)
615 [[image:12.PLC Protocol_html_55a3056357320966.png||data-xwiki-image-style-alignment="center" height="266" width="600" class="img-thumbnail"]]
616
617 Set address for receiving;
618
619 Set correct length;
620
621 (% style="text-align:center" %)
622 [[image:12.PLC Protocol_html_30a4c9e9dd4db40b.png||data-xwiki-image-style-alignment="center" height="701" width="500" class="img-thumbnail"]]
623
624 **✎Note:**
625
626 * The protocol uploads the information acquired by the USB scanner to the HMI;
627 * The acquired information is displayed in string mode, so it is necessary to use [characters input/display] object;
628 * Recommended model: DELI 14880 barcode scanner;
629
630 = **Hitachi EHV Series (Ethernet)** =
631
632 Supported series: Hitachi EHV series
633
634 **HMI Settings**
635
636 (% class="table-bordered" %)
637 |**Items**|**Settings**|**Note**
638 |Protocol|Hitachi EHV series|
639 |Connection|Ethernet|
640 |Port No.|3004~~3007|
641
642 **Address List**
643
644 (% class="table-bordered" %)
645 |**Type**|**Register**|**Range**|**Format**|**Note**
646 |(% rowspan="6" %)Bit|T|0 - 2545|T DDDD|
647 |M|0 - 7FFF.f (Hex)|M HHHH.h|
648 |X|0 – FFFF.f (Hex)|X H1H2H3H4.h|(% rowspan="2" %)(((
649 H1H2H3H4 Module main number
650
651 H1: Remote number
652
653 H2: Unit number
654
655 H3: Slot number
656
657 H4: Word number of Module
658
659 H Sub number of Module
660
661 For example:X21.3
662
663 Slot number 2
664
665 Word number of module is 1
666
667 Bit number of module is 3
668
669 Remote number and unit number are 0
670 )))
671 |Y|0 – FFFF.f (Hex)|Y H1H2H3H4.h
672 |R|0 – FF.f (Hex)|R HH.h|
673 |L|0 - 73FF.f (Hex)|L HHHH.h|
674 |(% rowspan="6" %)Word|WM|0 - 7FFF (Hex)|WM HHHH|
675 |WX|0 – FFFF (Hex)|WX H1H2H3H4|(% rowspan="2" %)(((
676 H1H2H3H4 Module main number
677
678 H1: Remote number
679
680 H2: Unit number
681
682 H3: Slot number
683
684 H4: Word number of module
685
686 For example:WX21
687
688 Word number of module is 1
689
690 Slot number is 2
691
692 Remote number and unit number are 0
693 )))
694 |WY|0 – FFFF (Hex)|WY H1H2H3H4
695 |WR|0 – FFFF (Hex)|WR HHHH|
696 |WL|0 - 73FF (Hex)|WL HHHH|
697 |TC|0 - 2559|TC DDDD|
698
699 **Communication settings in HMI**
700
701 Enable HMI Ethernet in [Project Settings];
702
703 (% style="text-align:center" %)
704 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
705
706 Set PLC IP in [Device IP] settings;
707
708 (% style="text-align:center" %)
709 [[image:12.PLC Protocol_html_d825387f5bde6cdd.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
710
711 **PLC Configuration**
712
713 Connect with PLC, select[Online mode];
714
715 (% style="text-align:center" %)
716 [[image:12.PLC Protocol_html_8430dda44e5c199c.png||data-xwiki-image-style-alignment="center" height="420" width="600" class="img-thumbnail"]]
717
718 Set IP address, it is the same LAN parameters with HMI;
719
720 (% style="text-align:center" %)
721 [[image:12.PLC Protocol_html_1d8a634f64e25fc3.png||data-xwiki-image-style-alignment="center" height="252" width="347" class="img-thumbnail"]]
722
723 3) Save PLC communication parameter, and restart PLC
724
725 **PLC Monitor Mode**
726
727 Connect with PLC and choose to “online” mode
728
729 (% style="text-align:center" %)
730 [[image:12.PLC Protocol_html_cdac598e770e3b67.png||data-xwiki-image-style-alignment="center" height="193" width="553" class="img-thumbnail"]]
731
732 Open I/O monitor sheet1
733
734 (% style="text-align:center" %)
735 [[image:12.PLC Protocol_html_68eb3518e5f80892.png||data-xwiki-image-style-alignment="center" height="369" width="559" class="img-thumbnail"]]
736
737 During monitoring bit address,1 pts should be selected; during monitoring word address, 16 pts should be selected
738
739 (% style="text-align:center" %)
740 [[image:12.PLC Protocol_html_774652d8daf548d4.png||data-xwiki-image-style-alignment="center" height="118" width="102" class="img-thumbnail"]]
741
742 Enter the register address, click OK to view the value of the register.
743
744 (% style="text-align:center" %)
745 [[image:12.PLC Protocol_html_bba169c300c92051.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
746
747 (% style="text-align:center" %)
748 [[image:12.PLC Protocol_html_d3b23bb9e81921a3.png||data-xwiki-image-style-alignment="center" height="404" width="600" class="img-thumbnail"]]
749
750 **✎Note:**
751
752 * Both word registers and bit registers support even continuous read/write functions;
753 * The range of registers is based on the specific PLC type;
754
755 **Cable Wiring**
756
757 (% style="text-align:center" %)
758 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
759
760 = **IEC60870-5 104 Client** =
761
762 **HMI Setting**
763
764 (% class="table-bordered" %)
765 |**Items**|(% style="width:725px" %)**Settings**|(% style="width:309px" %)**Note**
766 |Protocol|(% style="width:725px" %)IEC60870-5 104 Client|(% style="width:309px" %)
767 |Connection|(% style="width:725px" %)Ethernet|(% style="width:309px" %)
768 |Port No.|(% style="width:725px" %)2404|(% style="width:309px" %)
769
770 **Address List**
771
772 (% class="table-bordered" %)
773 |(% style="width:460px" %)**Type**|(% style="width:461px" %)**Register**|**Range**
774 |(% rowspan="9" style="width:460px" %)Bit|(% style="width:461px" %)SPTB|0~~16777215.7
775 |(% style="width:461px" %)SCNA|0~~16777215.7
776 |(% style="width:461px" %)DPTB|0~~16777215.7
777 |(% style="width:461px" %)DCNA|0~~16777215.7
778 |(% style="width:461px" %)METF|0~~16777215.7
779 |(% style="width:461px" %)SENC|0~~16777215.7
780 |(% style="width:461px" %)SENA|0~~16777215.7
781 |(% style="width:461px" %)MENA|0~~16777215.7
782 |(% style="width:461px" %)METD|0~~16777215.7
783 |(% rowspan="11" style="width:460px" %)Word|(% style="width:461px" %)SPTB|0~~16777215
784 |(% style="width:461px" %)SCNA|0~~16777215
785 |(% style="width:461px" %)DPTB|0~~16777215
786 |(% style="width:461px" %)DCNA|0~~16777215
787 |(% style="width:461px" %)SENA|0~~16777215
788 |(% style="width:461px" %)MENA|0~~16777215
789 |(% style="width:461px" %)METD|0~~16777215
790 |(% style="width:461px" %)INRO|0~~16777215
791 |(% style="width:461px" %)TIMESYN|0~~16777215
792 |(% style="width:461px" %)TIMEZ|0~~16777215
793 |(% style="width:461px" %)NTP|0~~16777215
794 |(% rowspan="2" style="width:460px" %)Double word|(% style="width:461px" %)METF|0~~16777215
795 |(% style="width:461px" %)SENC|0~~16777215
796
797 **Address Configuration**
798
799 The address registers of the IEC60870-5-104 protocol are SPTB, SCNA, DPTB, DCNA, METF, and SENC. The protocol needs to be added with an extension tag "ASDU", which could only be added in the [Address Identification Library], other places are not editable, that is, the read address in the object or script is not editable.
800
801 (% style="text-align:center" %)
802 [[image:12.PLC Protocol_html_ba78d143bf457ead.png||data-xwiki-image-style-alignment="center" height="369" width="600" class="img-thumbnail"]]
803
804 (% style="text-align:center" %)
805 [[image:12.PLC Protocol_html_23533fd5bb81f4ab.png||data-xwiki-image-style-alignment="center" height="389" width="600" class="img-thumbnail"]]
806
807 Extended tag name
808
809 Address range for the extended tag.
810
811 **Communication Settings**
812
813 Enable HMI Ethernet in [Project Settings];
814
815 (% style="text-align:center" %)
816 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
817
818 Set PLC IP in [Device IP] settings;
819
820 (% style="text-align:center" %)
821 [[image:12.PLC Protocol_html_f848736ec68b125.png||data-xwiki-image-style-alignment="center" height="191" width="554" class="img-thumbnail"]]
822
823 **Cable Wiring**
824
825 (% style="text-align:center" %)
826 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
827
828 = **LG XGK FEnet Ethernet** =
829
830 Supported Series: LS XGT series XGK CPU with XGL-EFMT Ethernet module
831
832 **HMI Settings**
833
834 (% class="table-bordered" %)
835 |**Items**|**Settings**|**Note**
836 |Protocol|LG XGK FEnet(Ethernet)|
837 |Connection|Ethernet|
838 |Port No.|2004|
839
840 **Address List**
841
842 (% class="table-bordered" %)
843 |**Type**|**Register**|**Range**|**Format**|**Note**
844 |(% rowspan="14" %)Word|P|0~~2047|P d|
845 |M|0~~2047|M d|
846 |K|0~~2047|K d|
847 |F|0~~2047|F d|
848 |T|0~~2047|T d|
849 |C|0~~2047|C d|
850 |Z|0~~127|Z d|
851 |S|0~~127|S d|
852 |L|0~~11263|L d|
853 |N|0~~21503|N d|
854 |D|0~~32767|D d|
855 |R|0~~32767|R d|
856 |ZR|0~~65535|ZR d|
857 |UxDD|0~~6331|UxDD nndd|nn: 0~~63, dd: 0~~31
858
859 **✎Note:**
860
861 * In addition to the "UxDD" register, the others correspond to the PLC register one by one. UxDD corresponds to U in the PLC;
862 * The [UxDD] register, defined in the PLC is Ux.dd, x represents the block, and dd represents 0-31 of each block. There are 64 blocks in the PLC;
863 * All bit registers are in the form of bits in word, and the range is the same as the word register;
864
865 **Communication settings in HMI**
866
867 Enable HMI Ethernet in [Project Settings];
868
869 (% style="text-align:center" %)
870 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
871
872 Set PLC IP in [Device IP] settings;
873
874 (% style="text-align:center" %)
875 [[image:12.PLC Protocol_html_a2a19b5003ad4090.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
876
877 **Cable Wiring**
878
879 = **Mitsubishi** =
880
881 == **FX1S, 1N, 2N Series** ==
882
883 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
884
885 **HMI Settings**
886
887 (% class="table-bordered" %)
888 |**Item**|**Settings**|**Note**
889 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
890 |Connection|RS422/RS485/RS232|
891 |Baud rate|9600~~115200|
892 |Data bit|7/8|
893 |Parity|EVEN/Odd/None|
894 |Stop bit|1/2|
895 |PLC station No.|1~~255|
896
897 **Address List**
898
899 (% class="table-bordered" %)
900 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
901 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
902 |Y|Y|Y o|0~~303237|
903 |M|M|M d|0~~99999|
904 |T|T|T d|0~~99999|
905 |C|C|C d|0~~99999|
906 |S|S|S d|0~~99999|
907 |SM|SM|SM d|8000~~9999|
908 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
909 |Y|Y|Y o|0~~303237|
910 |M|M|M d|0~~99999|
911 |T|T|T d|0~~99999|
912 |C|C|C d|0~~199|
913 |D|D|D d|0~~7999|
914 |S|S|S d|0~~99999|
915 |SD|SD|SD d|8000~~9999|
916
917 **Cable Wiring**
918
919 * **RS485**
920
921 (% style="text-align:center" %)
922 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
923
924 (% style="text-align:center" %)
925 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
926
927 * **RS422**
928
929 (% style="text-align:center" %)
930 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
931
932 **✎Note:** COM3 only available in PI8000/PI9000 series.
933
934 == **FX5U Ethernet** ==
935
936 Mitsubishi FX5U series PLC
937
938 **HMI Settings**
939
940 (% class="table-bordered" %)
941 |**Items**|**Settings**|**Note**
942 |Protocol|Mitsubishi FX5U|
943 |Connection|Ethernet|
944 |Port No.|5002|Must be the same as the PLC setting
945 |PLC station No.|0|
946
947 **Address List**
948
949 (% class="table-bordered" %)
950 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
951 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
952 |Y|Y|Y o|0~~303237|
953 |M|M|M d|0~~99999|
954 |B|B|B h|0~~7FFF|
955 |F|F|F d|0~~32767|
956 |SB|SB|SB h|0~~7FFF|
957 |TS|TS|TS d|0~~1023|
958 |TC|TC|TC d|0~~1023|
959 |STS|STS|STS d|0~~1023|
960 |STC|STC|STS d|0~~1023|
961 |CS|CS|CS d|0~~1023|
962 |CC|CC|CC d|0~~1023|
963 |SM|SM|SM d|0~~9999|
964 |L|L|L d|0~~32767|
965 |S|S|S d|0~~4095|
966 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
967 |TN|TN|TN d|0~~1023|
968 |STN|STN|STN d|0~~1023|
969 |CN|CN|CN d|0~~1023|
970 |R|R|R d|0~~32767|
971 |SW|SW|SW h|0~~7FFF|
972 |Z|Z|Z d|0~~23|
973 |D|D|D d|0~~7999|
974 |SD|SD|SD d|0~~11999|
975
976 **PLC Settings (GX Works 3)**
977
978 Find the [Ethernet port] in the navigation area.
979
980 (% style="text-align:center" %)
981 [[image:12.PLC Protocol_html_8e8f85ace087346c.png||data-xwiki-image-style-alignment="center" height="593" width="300" class="img-thumbnail"]]
982
983 Select [Own Node Settings] in the [Setting Item List];
984
985 Set [IP Address], [Subnet Mask], [Default Gateway];
986
987 Click [Detailed Settings] into [Ethernet Configuration (Built-in Ethernet Port)] windows;
988
989 (% style="text-align:center" %)
990 [[image:12.PLC Protocol_html_5d98495052c8c10e.png||data-xwiki-image-style-alignment="center" height="339" width="600" class="img-thumbnail"]]
991
992 Select [SLMP Connection Module] and add into host station as below picture shows;
993
994 Set Port number as 5002 (this is necessary settings);
995
996 Click [Close with Reflecting the Setting] to save and close window;
997
998 (% style="text-align:center" %)
999 [[image:12.PLC Protocol_html_14b489fdc6c6589d.png||data-xwiki-image-style-alignment="center" height="350" width="600" class="img-thumbnail"]]
1000
1001 Click [Apply] to completed Etherenet settings;
1002
1003 Switch to the [On line data operation] interface as below, check the item and click [Execute] to download.
1004
1005 (% style="text-align:center" %)
1006 [[image:12.PLC Protocol_html_c93025a968a8a9e7.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1007
1008 **Cable Wiring**
1009
1010 (% style="text-align:center" %)
1011 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1012
1013 == **FX5U Serial Port** ==
1014
1015 Mitsubishi FX5U series PLC
1016
1017 **HMI Settings**
1018
1019 (% class="table-bordered" %)
1020 |**Item**|**Settings**|**Note**
1021 |Protocol|Mitsubishi FX5U|
1022 |Connection|RS422/RS485|
1023 |Baud rate|9600|
1024 |Data bit|7|
1025 |Parity|Odd|
1026 |Stop bit|1|
1027 |PLC station No.|1~~255|Need to be the same as PLC settings
1028
1029 **Address List**
1030
1031 (% class="table-bordered" %)
1032 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1033 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
1034 |Y|Y|Y o|0~~303237|
1035 |M|M|M d|0~~99999|
1036 |B|B|B h|0~~7FFF|
1037 |F|F|F d|0~~32767|
1038 |SB|SB|SB h|0~~7FFF|
1039 |TS|TS|TS d|0~~1023|
1040 |TC|TC|TC d|0~~1023|
1041 |STS|STS|STS d|0~~1023|
1042 |STC|STC|STS d|0~~1023|
1043 |CS|CS|CS d|0~~1023|
1044 |CC|CC|CC d|0~~1023|
1045 |SM|SM|SM d|0~~9999|
1046 |L|L|L d|0~~32767|
1047 |S|S|S d|0~~4095|
1048 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
1049 |TN|TN|TN d|0~~1023|
1050 |STN|STN|STN d|0~~1023|
1051 |CN|CN|CN d|0~~1023|
1052 |R|R|R d|0~~32767|
1053 |SW|SW|SW h|0~~7FFF|
1054 |Z|Z|Z d|0~~23|
1055 |D|D|D d|0~~7999|
1056 |SD|SD|SD d|0~~11999|
1057
1058 **PLC Settings (GX Works 3)**
1059
1060 Create a blank FX5U project
1061
1062 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
1063
1064 (% style="text-align:center" %)
1065 [[image:12.PLC Protocol_html_5c9cb13fac1e6c93.png||data-xwiki-image-style-alignment="center" height="462" width="200" class="img-thumbnail"]]
1066
1067 Select protocol in the setting item, and set parameters.
1068
1069 (% style="text-align:center" %)
1070 [[image:12.PLC Protocol_html_de942589ca070228.png||data-xwiki-image-style-alignment="center" height="324" width="600" class="img-thumbnail"]]
1071
1072 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
1073
1074 (% style="text-align:center" %)
1075 [[image:12.PLC Protocol_html_387ec7d00b5feb59.png||data-xwiki-image-style-alignment="center" height="323" width="600" class="img-thumbnail"]]
1076
1077 Click the [Apply] button to finish the setting.
1078
1079 Click download and select the items as below, then click [execute] to download the configuration to PLC.
1080
1081 (% style="text-align:center" %)
1082 [[image:12.PLC Protocol_html_cdef1c5ec8cc2105.png||data-xwiki-image-style-alignment="center" height="434" width="600" class="img-thumbnail"]]
1083
1084 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
1085
1086 Done.
1087
1088 **Cable Wiring**
1089
1090 * **RS485**
1091
1092 (% style="text-align:center" %)
1093 [[image:12.PLC Protocol_html_d4012bdeb4ce4aae.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1094
1095 (% style="text-align:center" %)
1096 [[image:12.PLC Protocol_html_4bf57ad8d44eacc4.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1097
1098 * **RS422**
1099
1100 (% style="text-align:center" %)
1101 [[image:12.PLC Protocol_html_f8a6bebc5792960d.png||data-xwiki-image-style-alignment="center" height="253" width="402" class="img-thumbnail"]]
1102
1103 **✎Note:** COM3 only available in PI8000/PI9000 series.
1104
1105 == **L02 MELSEC (Ethernet)** ==
1106
1107 Mitsubishi Q series CPU built-in Ethernet port.
1108
1109 **HMI Settings**
1110
1111 (% class="table-bordered" %)
1112 |**Items**|**Settings**|**Note**
1113 |Protocol|MIT L02 CPU MELSEC|
1114 |Connection|Ethernet|
1115 |Port No.|1025|Must be the same as the PLC setting
1116 |PLC station No.|0|Must be the same as the PLC setting
1117
1118 **Address List**
1119
1120 (% class="table-bordered" %)
1121 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1122 |Bit|X|X|X h|0~~FFFF|
1123 |Bit|Y|Y|Y h|0~~FFFF|
1124 |Bit|M|M|M d|0~~9999|
1125 |Bit|L|L|L d|0~~9999|
1126 |Bit|F|F|F d|0~~9999|
1127 |Bit|B|B|B h|0~~FFFF|
1128 |Bit|V|V|V d|0~~2047|
1129 |Bit|TC|TC|TC d|0~~9999|
1130 |Bit|SS|SS|SS d|0~~9999|
1131 |Bit|SC|SC|SC d|0~~9999|
1132 |Bit|CS|CS|CS d|0~~9999|
1133 |Bit|CC|CC|CC d|0~~9999|
1134 |Bit|SB|SB|SB h|0~~FFFF|
1135 |Bit|SM|SM|SM d|0~~2047|
1136 |Bit|STS|STS|STS d|0~~1023|
1137 |Bit|S|S|S d|0~~9999|
1138 |Bit|DX|DX|DX h|0~~FFFF|
1139 |Bit|DY|DY|DY h|0~~FFFF|
1140 |Bit|TS|TS|TS d|0~~9999|
1141 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
1142 |Word|W|W|W h|0~~FFFF|
1143 |Word|TN|TN|TN d|0~~99999|
1144 |Word|SN|SN|SN d|0~~99999|
1145 |Word|CN|CN|CN d|0~~99999|
1146 |Word|R|R|R d|0~~99999|
1147 |Word|SW|SW|SW h|0~~FFFF|
1148 |Word|Z|Z|Z d|0~~99999|
1149 |Word|ZR|ZR|ZR h|0~~FFFF|
1150 |Word|D|D|D d|0~~99999|
1151
1152 **Communication Settings**
1153
1154 Enable HMI Ethernet in [Project Settings];
1155
1156 (% id="cke_bm_7504S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1157
1158 Set PLC IP in [Device IP] settings;
1159
1160 (% style="text-align:center" %)
1161 [[image:12.PLC Protocol_html_38189fae42f6caa7.png||data-xwiki-image-style-alignment="center" height="206" width="600" class="img-thumbnail"]]
1162
1163 **PLC Settings (GX Works2 )**
1164
1165 Create a project
1166
1167 Set PLC IP, subnet mask and gateway;
1168
1169 Select [Binary Code] as communication data code;
1170
1171 (% style="text-align:center" %)
1172 [[image:12.PLC Protocol_html_776e17505f3fc6c0.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1173
1174 Set PLC port number, for example 1025
1175
1176 (% style="text-align:center" %)
1177 [[image:12.PLC Protocol_html_8d0d1a22d388f70b.png||data-xwiki-image-style-alignment="center" height="524" width="600" class="img-thumbnail"]]
1178
1179 Save settings;
1180
1181 Download project into PLC device;
1182
1183 Restart PLC device;
1184
1185 **Cable Wiring**
1186
1187 (% style="text-align:center" %)
1188 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1189
1190 == **QJ71E71 MELSEC** ==
1191
1192 Mitsubishi QJ71E71 Ethernet communication module;
1193
1194 **HMI Settings**
1195
1196 (% class="table-bordered" %)
1197 |**Items**|**Settings**|**Note**
1198 |Protocol|MIT QJ71E71 MELSEC|
1199 |Connection|Ethernet|
1200 |Port No.|1025|Must be the same as the PLC setting
1201 |PLC station No.|0|Must be the same as the PLC setting
1202
1203 **Address List**
1204
1205 (% class="table-bordered" %)
1206 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
1207 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
1208 |Y|Y|Y h|0~~1FFF|
1209 |M|M|M d|0~~99999|
1210 |L|L|L d|0~~8191|
1211 |F|F|F d|0~~2047|
1212 |B|B|B h|0~~1FFF|
1213 |V|V|V d|0~~2047|
1214 |TS|TS|TS d|0~~2047|
1215 |TC|TC|TC d|0~~2047|
1216 |SS|SS|SS d|0~~2047|
1217 |SC|SC|SC d|0~~2047|
1218 |CS|CS|CS d|0~~1023|
1219 |CC|CC|CC d|0~~1023|
1220 |SB|SB|SB h|0~~7FF|
1221 |S|S|S d|0~~8191|
1222 |DX|DX|DX h|0~~1FFF|
1223 |DY|DY|DY h|0~~1FFF|
1224 |SM|SM|SM d|8000~~9999|
1225 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
1226 |D|D|D d|0~~12287|
1227 |W|W|W h|0~~1FFF|
1228 |TN|TN|TN d|0~~2047|
1229 |SN|SN|SN d|0~~2047|
1230 |CN|CN|CN d|0~~1023|
1231 |R|R|R d|0~~32767|
1232 |SW|SW|SW h|0~~7FF|
1233 |Z|Z|Z d|0~~15|
1234 |ZR|ZR|ZR h|0~~FE7FF|
1235
1236 **HMI Communication Settings**
1237
1238 1) Enable HMI Ethernet in [Project Settings];
1239
1240 (% id="cke_bm_7537S" style="display:none" %) [[image:12.PLC Protocol_html_43b671f18153910d.png||height="107" width="405"]]
1241
1242 2) Set PLC IP in [Device IP] settings;
1243
1244 (% style="text-align:center" %)
1245 [[image:12.PLC Protocol_html_2d566cb5ffb2618c.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1246
1247 **PLC Settings(GX Works2)**
1248
1249 * Click [Ethernet/CC IE/MELSECNET];
1250 * Please select [Ethernet] as network type;
1251 * Set station I/O number according to situation (For example, 0000 means that the module is connected to PLC CPU in first order);
1252 * Select [Online] as Mode;(% id="cke_bm_8449S" style="display:none" %) [[image:12.PLC Protocol_html_acd084d845da380e.png||height="300" width="554"]]
1253 * Click [Operation setting] to set IP;
1254 * Select [Binary Code] as [Communication Data Code];(% id="cke_bm_8474S" style="display:none" %) [[image:12.PLC Protocol_html_a972e671d2bb9150.png||height="304" width="553"]]
1255 * Set protocol: TCP;
1256 * Set [unpassive] in [Open system];
1257 * Set [receive] in [Fixed buffer];
1258 * Set [procedure Exist] in [Fixed buffer communication];
1259 * Disable [Pairing open];
1260 * Set [No confirm] in [Existence confirmation];
1261 * Host station port number: 1025;
1262 * (% id="cke_bm_8547S" style="display:none" %)[[image:12.PLC Protocol_html_f2c432006cdd2f9.png||height="220" width="553"]](%%)Save settings;
1263 * Download project into PLC and restart it
1264
1265 **Cable Wiring**
1266
1267 (% style="text-align:center" %)
1268 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1269
1270 = **MODBUS** =
1271
1272 == **MODBUS RTU Master** ==
1273
1274 Supported Series: MODBUS RTU CONTROLLER
1275
1276 HMI works as MODBUS SLAVE connecting with MASTER
1277
1278 (% style="text-align:center" %)
1279 [[image:12.PLC Protocol_html_44425b313b0a6b96.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1280
1281
1282 (% style="text-align:center" %)
1283 [[image:12.PLC Protocol_html_b56b9da32c3caaa.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1284
1285
1286 (% style="text-align:center" %)
1287 [[image:12.PLC Protocol_html_67cd25458b9c72a6.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1288
1289 **HMI Settings**
1290
1291 (% class="table-bordered" %)
1292 |**Items**|**Settings**|**Note**
1293 |Protocol|MODBUS RTU Master|
1294 |Connection|RS485/RS232|
1295 |Baud rate|2400~~187500|
1296 |Data bit|8|
1297 |Parity|Even/ Odd/ None|
1298 |Stop bit|1/2|
1299 |Station No.|0~~255|
1300
1301 **Address List**
1302
1303 (% class="table-bordered" %)
1304 |**Type**|**HMI address**|**MODBUS code**|**Range**
1305 |Bit|HDX3000.0~~HDX3499.15|0|0~~7999
1306 |Word|HDW3500~~HDW7999|4|0~~4499
1307
1308 **Cable Wiring**
1309
1310 * **RS485**
1311
1312 (% style="text-align:center" %)
1313 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1314
1315 (% style="text-align:center" %)
1316 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1317
1318 * **RS232**
1319
1320 (% style="text-align:center" %)
1321 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1322
1323 **✎Note:** COM3 only available in PI8000/PI9000 series.
1324
1325 == **MODBUS RTU Slave (All function)/(All function OneBaseAddress)** ==
1326
1327 Supported Series: MODBUS RTU CONTROLLER
1328
1329 HMI works as MODBUS MASTER connecting with SLAVE.
1330
1331 The addresses in [All function] start from 0, while the addresses in [All function OneBaseAddress] start from 1 (offset 1).
1332
1333 (% style="text-align:center" %)
1334 [[image:12.PLC Protocol_html_7236139c887defad.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1335
1336
1337 (% style="text-align:center" %)
1338 [[image:12.PLC Protocol_html_de80207f2b495c17.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1339
1340
1341 (% style="text-align:center" %)
1342 [[image:12.PLC Protocol_html_4e9e8eff81c7ff8b.png||data-xwiki-image-style-alignment="center" height="462" width="600" class="img-thumbnail"]]
1343
1344 **HMI Settings**
1345
1346 (% class="table-bordered" %)
1347 |**Items**|**Settings**|**Note**
1348 |Protocol|MODBUS RTU Slave (All function)/( All function OneBaseAddress)|
1349 |Connection|RS485/RS232|
1350 |Baud rate|2400~~187500|
1351 |Data bit|8|
1352 |Parity|Even/ Odd/ None|
1353 |Stop bit|1/2|
1354 |PLC station No.|0~~255|
1355
1356 **Address List**
1357
1358 (% class="table-bordered" %)
1359 |**Type**|**Address Type**|**Function code & Description**
1360 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1361 |06 (write single register: write a binary value to a holding register)
1362 |10 (write values to multiple addresses )
1363 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1364 |06 (write single register: write a binary value to a holding register)
1365 |10 (write values to multiple addresses )
1366 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1367 |06 (write single register: write a binary value to a holding register)
1368 |10 (write values to multiple addresses )
1369 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1370 |10 (write values to multiple addresses )
1371 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1372 |05 (Force a single coil to force the on/off state of a logic coil)
1373 |0F (Write multiple bits, ie write continuously)
1374 |(% rowspan="3" %)1|02 (Read the input state)
1375 |05 (Force a single coil to force the on/off state of a logic coil)
1376 |0F (Write multiple bits)
1377 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1378 |05 (Force a single coil to force the on/off state of a logic coil)
1379 |0F (Write multiple bits)
1380 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1381 |0F (Write multiple bits)
1382
1383 **✎Note:**
1384
1385 * Modbus can also support getting bit from the word, which could access the address such as 100.1 and other formats.
1386 * The function codes sent out are the same as those that read and write words.
1387
1388 **Station number for more than one slaves**
1389
1390 If there are more than one slaves connected to HMI, please set slave station number during editing address, as below shows.
1391
1392 (% style="text-align:center" %)
1393 [[image:12.PLC Protocol_html_31f028c6d80be344.png||data-xwiki-image-style-alignment="center" height="515" width="485" class="img-thumbnail"]]
1394
1395 **Cable Wiring**
1396
1397 * **RS485**
1398
1399 (% style="text-align:center" %)
1400 [[image:12.PLC Protocol_html_68dfb6d383f0edd9.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1401
1402 (% style="text-align:center" %)
1403 [[image:12.PLC Protocol_html_cbeb90cb4faaa8bc.png||data-xwiki-image-style-alignment="center" height="244" width="394" class="img-thumbnail"]]
1404
1405 * **RS232**
1406
1407 (% style="text-align:center" %)
1408 [[image:12.PLC Protocol_html_9030ba679545793b.png||data-xwiki-image-style-alignment="center" height="241" width="387" class="img-thumbnail"]]
1409
1410 **✎Note:** COM3 only available in PI8000/PI9000 series.
1411
1412 == **MODBUS TCP Slave (All function)** ==
1413
1414 Supported series: MODBUS TCP controller
1415
1416 HMI works as MODBUS TCP MASTER connecting with TCP SLAVE
1417
1418 (% style="text-align:center" %)
1419 [[image:12.PLC Protocol_html_8877cb7f39c2b607.png||data-xwiki-image-style-alignment="center" height="571" width="544" class="img-thumbnail"]]
1420
1421 (% style="text-align:center" %)
1422 [[image:12.PLC Protocol_html_e7e1f06f127a9175.png||data-xwiki-image-style-alignment="center" height="426" width="553" class="img-thumbnail"]]
1423
1424
1425 (% style="text-align:center" %)
1426 [[image:12.PLC Protocol_html_60bbfe5de79417a6.png||data-xwiki-image-style-alignment="center" height="163" width="553" class="img-thumbnail"]]
1427
1428 **HMI Setting**
1429
1430 (% class="table-bordered" %)
1431 |**Items**|**Settings**|**Note**
1432 |Protocol|MODBUS TCP Slave (All function)|
1433 |Connection|Ethernet|
1434 |Port No.|502|
1435 |PLC station No.|1|
1436
1437 **Address List**
1438
1439 (% class="table-bordered" %)
1440 |**Type**|**Register**|**Function code & Description**
1441 |(% rowspan="11" %)Word|(% rowspan="3" %)3|04 (read input register: read current binary value in one or more input registers)
1442 |06 (write single register: write a binary value to a holding register)
1443 |10 (write values to multiple addresses )
1444 |(% rowspan="3" %)4|03 (read holding register: read current binary value in one or more holding registers)
1445 |06 (write single register: write a binary value to a holding register)
1446 |10 (write values to multiple addresses )
1447 |(% rowspan="3" %)W6|03 (read holding register: read current binary value in one or more holding registers)
1448 |06 (write single register: write a binary value to a holding register)
1449 |10 (write values to multiple addresses )
1450 |(% rowspan="2" %)W16|03 (read holding register: read current binary value in one or more holding registers)
1451 |10 (write values to multiple addresses )
1452 |(% rowspan="11" %)Bit|(% rowspan="3" %)0|01 (Read coil state)
1453 |05 (Force a single coil to force the on/off state of a logic coil)
1454 |0F (Write multiple bits, ie write continuously)
1455 |(% rowspan="3" %)1|02 (Read the input state)
1456 |05 (Force a single coil to force the on/off state of a logic coil)
1457 |0F (Write multiple bits)
1458 |(% rowspan="3" %)W5|01 (Read coil state to obtain the current state of a set of logic coils)
1459 |05 (Force a single coil to force the on/off state of a logic coil)
1460 |0F (Write multiple bits)
1461 |(% rowspan="2" %)W15|01 (Read coil state to obtain the current state of a set of logic coils)
1462 |0F (Write multiple bits)
1463
1464 **Communication Settings**
1465
1466 Enable HMI Ethernet in [Project Settings];
1467
1468 (% style="text-align:center" %)
1469 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1470
1471 Set PLC IP in [Device IP] settings;
1472
1473 (% style="text-align:center" %)
1474 [[image:12.PLC Protocol_html_4bd3cc8348adecf8.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
1475
1476 **Cable Wiring**
1477
1478 (% style="text-align:center" %)
1479 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1480
1481 = **Omron** =
1482
1483 == **EC55** ==
1484
1485 Supported device: EC55 temperature instrument
1486
1487 **HMI Settings**
1488
1489 (% class="table-bordered" %)
1490 |**Items**|**Settings**|**Note**
1491 |Protocol|Omron EC55|
1492 |Connection|RS485 (9600, 2, 7, EVEN)|
1493 |Port No.|None|
1494 |PLC station No.|0|
1495
1496 **Address List**
1497
1498 (% class="table-bordered" %)
1499 |**Type**|**Register**|**Device range**|**HMI range**|**Function**
1500 |(% rowspan="3" %)Double word|C0|0-13 (Hex)|0-19|Set read only parameter for area 0
1501 |C1|0-4D(Hex)|0-77|Set Read/Write parameter for area 0
1502 |C3|0-CD(Hex)|0-205|Set Read/Write parameter for area 1
1503 |(% rowspan="6" %)Word|80|0-13(Hex)|0-19|Set read only parameter in area 0
1504 |81|0-4D(Hex)|0-77|Set Read/Write parameter in area 0
1505 |83|0-CD(Hex)|0-205|Set Read/Write parameter in area 1
1506 |CP|-|0-6|Read controller intrinsic property
1507 |CS|-|0-2|Read controller states
1508 |CA|-|0-17|Action command
1509
1510 **Device Settings**
1511
1512 Omron E5CC PLC configuration
1513
1514 After entering the Communication Settings menu, please set the parameters to the default values for the following table. Press the cycle key of the instrument to enter the next setting.
1515
1516 (% style="text-align:center" %)
1517 [[image:12.PLC Protocol_html_3d95e093792ba98a.png||data-xwiki-image-style-alignment="center" height="229" width="550" class="img-thumbnail"]]
1518
1519 According to PLC configuration and communication port configuration information of the HMI, provide the corresponding steps and configuration screenshots. This configuration needs to communicate properly with the above PLC configuration. The project settings are as follows
1520
1521 (% style="text-align:center" %)
1522 [[image:12.PLC Protocol_html_be583aa69dd6cf4c.png||data-xwiki-image-style-alignment="center" height="242" width="550" class="img-thumbnail"]]
1523
1524 **✎Note:** The communication settings for HMI should be consistent with this setting.
1525
1526 **Cable Wiring**
1527
1528 (% style="text-align:center" %)
1529 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1530
1531 (% style="text-align:center" %)
1532 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1533
1534 **✎Note:**
1535
1536 * COM3 only available in PI8000/PI9000 series.
1537 * CA address could not support continuous writing function;
1538 * Because of CP address intrinsic property: read control intrinsic property, so please place the character input part in use. Set address with CP0 and character length 10, used to display controller type. And place a number input part, set address with CP5 (cache size). Do not place other CP type address without CP0 in screen, otherwise CP type address is invalid
1539 * When set value into read & write address, it is necessary to switch the temperature instrument meter to the corresponding interface according to the menu of the instrument where the address locates, so that the value could be written, otherwise, the value could not be written; When the communication write setting of the instrument is turned off, the writing function is invalid. Writing function could be opened by using the 00 address of the CA register, which write 01 value.
1540 * When continuous writing of a value to a read-write address, please make sure all continuous writing address could be written. Otherwise, if one of these addresses could not be written, then all continuous writing commands will fail.
1541 * Because of the mechanism problem, this protocol could not support CompoWay/F function that is read-write function of variables in protocol document.
1542 * When using double-word address, set the data format to 32 bits, otherwise the read/write function is unable.
1543 * Please set the communication delay time of 10ms in setting, to avoid that the instrument may not be able to communicate in a short time due to too fast data access and too much connection requests.
1544 * (% id="cke_bm_8690S" style="display:none" %)[[image:12.PLC Protocol_html_d428cad280fdefb3.png||height="276" width="347"]](%%)Because of the particularity of the instrument, it is necessary to write the value of the address in the menu interface corresponding to the address, and to enter the menu where the address locates, so that the value could be written.
1545
1546 == EtherNet/IP NX series ==
1547
1548 Supported series: Omron NX/NJ series
1549
1550 **HMI Setting**
1551
1552 (% class="table-bordered" %)
1553 |**Items**|**Settings**|**Note**
1554 |Protocol|Omron NX Ethernet/IP|
1555 |Connection|Ethernet|
1556 |Port No.|44818|
1557 |PLC station No.|1|
1558
1559 **Instruction**
1560
1561 1) In Sysmac Studio, please select [Publish Only] for [Network Publish] when setting address tag.
1562
1563 2) When [Do not publish] is selected for a tag, different import methods may lead to different results. When import tags by [Get Tags from Device], the tag will be eliminated. If [Import tags] is selected, the tags will be imported, but the communication will not succeed.
1564
1565 (% style="text-align:center" %)
1566 [[image:12.PLC Protocol_html_4156caf6f116c570.png||data-xwiki-image-style-alignment="center" height="277" width="600" class="img-thumbnail"]]
1567
1568 **Export labels from Sysmac Studio**
1569
1570 Launch Sysmac Studio, under Global Variables create the address labels, and thenselect [Tools] -> [Export Global Variables];
1571
1572 (% style="text-align:center" %)
1573 [[image:12.PLC Protocol_html_26f91dee66c723e9.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1574
1575 Launch PIStudio, in [Communication] Settings add Omron NX Ethernet/IP protocol;
1576
1577 Click [Label manage];
1578
1579 (% style="text-align:center" %)
1580 [[image:12.PLC Protocol_html_cd38d2d0c5187f6b.png||data-xwiki-image-style-alignment="center" height="276" width="600" class="img-thumbnail"]]
1581
1582 Click [Import labels] and then select the file exported in step 1;
1583
1584 (% style="text-align:center" %)
1585 [[image:12.PLC Protocol_html_52bd5da678bef9b4.png||data-xwiki-image-style-alignment="center" height="403" width="600" class="img-thumbnail"]]
1586
1587 The Import Status field shows the result, click [OK] to finish importing address labels;
1588
1589 (% style="text-align:center" %)
1590 [[image:12.PLC Protocol_html_7f0465a589b98912.png||data-xwiki-image-style-alignment="center" height="291" width="600" class="img-thumbnail"]]
1591
1592 **Communication Settings**
1593
1594 Enable HMI Ethernet in [Project Settings];
1595
1596 (% style="text-align:center" %)
1597 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
1598
1599 Set PLC IP in [Device IP] settings;
1600
1601 (% style="text-align:center" %)
1602 [[image:12.PLC Protocol_html_437cb087b36b5784.png||data-xwiki-image-style-alignment="center" height="330" width="600" class="img-thumbnail"]]
1603
1604
1605 (% style="text-align:center" %)
1606 [[image:12.PLC Protocol_html_60ef71528a99abf5.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
1607
1608 **Cable Wiring**
1609
1610 (% style="text-align:center" %)
1611 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
1612
1613 = **OpenCAN** =
1614
1615 OpenCan is based on CAN2.0 standard; OpenCAN protocols that could be configured autonomously to accept and send frames.
1616
1617 This protocol is only available in PI8000 series HMI.
1618
1619 **HMI Settings**
1620
1621 (% class="table-bordered" %)
1622 |**Items**|**Settings**|**Note**
1623 |Protocol|OPENCAN|
1624 |Connection|CAN port|
1625 |Baud rate|250000|
1626
1627 **CAN frame setting in HMI**
1628
1629 Click [OpenCAN setting] button in communication setting window;
1630
1631 (% style="text-align:center" %)
1632 [[image:12.PLC Protocol_html_e866b9e56e19785d.png||data-xwiki-image-style-alignment="center" height="503" width="600" class="img-thumbnail"]]
1633
1634 Click [Add] to create a new frame;
1635
1636 (% style="text-align:center" %)
1637 [[image:12.PLC Protocol_html_3a6f4e2141763c8f.png||data-xwiki-image-style-alignment="center" height="315" width="600" class="img-thumbnail"]]
1638
1639 (% class="table-bordered" %)
1640 |**No**|**Items**|**Description**
1641 |1|Add|add a frame related to register address
1642 |2|Insert|Select the position where you want to insert a frame, and click [Insert frame] to add a new frame in front of the current frame position
1643 |3|Frame manager|This list shows some of the main parameters for each frame that the user adds
1644 |4|Modify|Modify the frames in frame management
1645 |5|Copy|Copy one frame to another
1646 |6|Delete|Remove the selected frames from the list by modifying the frames in frame management. If no frames are selected in the list, the first frame is deleted.
1647 |7|Empty|All frames in the list are cleared
1648 |8|Browse|Displays configuration files in XML format in IE
1649 |9|OK|Complete the configuration of the frame and exit
1650
1651 Set CANBUS frame in setting windows
1652
1653 (% style="text-align:center" %)
1654 [[image:12.PLC Protocol_html_7c83130820321ef.png||data-xwiki-image-style-alignment="center" height="507" width="600" class="img-thumbnail"]]
1655
1656 (% class="table-bordered" %)
1657 |**No**|(% style="width:185px" %)**Items**|(% style="width:854px" %)**Description**
1658 |1|(% style="width:185px" %)ID|(% style="width:854px" %)Set the ID of a can frame in hexadecimal format;
1659 |2|(% style="width:185px" %)ID assign|(% style="width:854px" %)split the ID by PF, PS, and SA;
1660 |3|(% style="width:185px" %)Frame type|(% style="width:854px" %)Select Standard frame or Extended Frame;
1661 |4|(% style="width:185px" %)Frame format|(% style="width:854px" %)Select between data frame and remote Frame;
1662 |5|(% style="width:185px" %)Data|(% style="width:854px" %)Set the data part of CAN frame, with two Numbers representing a hexadecimal number and Spaces spaced; Maximum support of 8 bytes is defined according to CAN message;
1663 |6|(% style="width:185px" %)Use address|(% style="width:854px" %)(((
1664 Set the register address related to the CAN frame, which corresponds to the register address set on the main state one by one. The data obtained from the address is assigned continuously;
1665
1666 **Edit:** Set a bit or word address by its format;
1667
1668 **Option: **Set address options related to frame, enter “register address option” interface, specifically browse the following “register address option” interface;
1669 )))
1670 |(% rowspan="8" %)7|(% rowspan="8" style="width:185px" %)Data interactive configuration|(% style="width:854px" %)There are two interactive modes of the touch screen. One is that the touch screen actively sends frames, and the device receives and processes and feeds back. The other, on the contrary, passively receives frames from the device for processing and feedback;
1671 |(% style="width:854px" %)Send after receiving: if this item is selected, the interaction of the touch screen will act as a passive party, and the touch screen will receive the CAN frame first and send feedback. Unchecked items interact in the opposite way;
1672 |(% style="width:854px" %)Feedback mode: feedback mode includes no response, confirm response and data response;
1673 |(% style="width:854px" %)No response: the device or touch screen will not receive feedback;
1674 |(% style="width:854px" %)Confirm response: the device or the touch screen will receive feedback with confirmation, which could be used to compare the data parts. If this function is used, the 20 addresses before and after this address should not be used. All addresses of cata10-cata30 could not be used with the reply confirmation function of cata20;
1675 |(% style="width:854px" %)Data response: the device or touch screen will receive feedback with data, and the data to be separated from the feedback frame should be set to store in the register address;
1676 |(% style="width:854px" %)response ID: if the address wants to receive data on a frame with a different ID, set this, check "different from sender", and enter a different ID in the following input box. Without this setting, the screen will receive and process a frame with the same ID as the sender;
1677 |(% style="width:854px" %)Response timeout: sets whether the response frame timeout;
1678 |(% rowspan="3" %)8|(% rowspan="3" style="width:185px" %)Control address|(% style="width:854px" %)If ticked, enable sending when the value of the corresponding control bit number (address) is non-0.
1679 |(% style="width:854px" %)Control bit: CtrlBit register range 0~~255, if the control bit is ON, can instruction will run normally. Otherwise, it doesn't run;
1680 |(% style="width:854px" %)Manually send: a manually send tick indicates only one send;
1681 |9|(% style="width:185px" %)Flag configuration|(% style="width:854px" %)Communication control for each frame. Display OFF when communication is normal, and ON when communication is abnormal;
1682 |10|(% style="width:185px" %)Note|(% style="width:854px" %)Fill the text to explain the meaning of the frame;
1683 |11|(% style="width:185px" %)Data assign|(% style="width:854px" %)Preview the display in this table based on the address and the corresponding number of digits;
1684 |12|(% style="width:185px" %)Current operation display|(% style="width:854px" %)Display the description of current operation;
1685 |13|(% style="width:185px" %)Add|(% style="width:854px" %)Add a new frame;
1686 |14|(% style="width:185px" %)Save frame|(% style="width:854px" %)Save the configured frame format;
1687 |15|(% style="width:185px" %)Cancel|(% style="width:854px" %)Cancel the frame configuration;
1688
1689 Set CAN address (Read or write operation);
1690
1691 (% style="text-align:center" %)
1692 [[image:12.PLC Protocol_html_7e9f9b25eb6ae8ce.png||data-xwiki-image-style-alignment="center" height="446" width="600" class="img-thumbnail"]]
1693
1694 (% class="table-bordered" %)
1695 |**No.**|(% style="width:207px" %)**Item**|(% style="width:829px" %)**Description**
1696 |1|(% style="width:207px" %)Current address|(% style="width:829px" %)Displays the register type and register address set by the user in the data access interface
1697 |(% rowspan="3" %)2|(% rowspan="3" style="width:207px" %)Trigger|(% style="width:829px" %)Two operations, "read" and "write," are based on on-screen registers
1698 |(% style="width:829px" %)If "read" is selected, the register address is reading device data in a manner of sending frames set by the user in a loop.
1699 |(% style="width:829px" %)If "write" is selected, the screen data of the register address will be written into the device. The writing mode is that the user makes a write operation on the screen, which will trigger the sending of a frame set by the user.
1700 |(% rowspan="5" %)3|(% rowspan="3" style="width:207px" %)Data operation|(% style="width:829px" %)The read and write operations in the trigger conditions are set accordingly.
1701 |(% style="width:829px" %)If the trigger condition is a read operation, this section needs to set the position and length of the data to be obtained at the current address in the frame.
1702 |(% style="width:829px" %)If the trigger condition is a writing operation, there are two situations:(((
1703 * If the "add writing data to the frame" option is not selected, the frame set by the user will be sent directly when the user writes on the screen.
1704 * Select the "add the written data to the frame" option, and when the user writes on the screen, the program will insert the data in the frame set by the user and send the written data to the frame set by the user according to the data insertion position and length set by the user.
1705 )))
1706 |(% rowspan="2" style="width:207px" %)Position and length input format|(% style="width:829px" %)If the register type is a bit address, the decimal point is required to represent the bits in the byte. For example, 1.1 represents the first bit of the first byte of 8 bytes in the data frame, and the length is in bits, and so on.
1707 |(% style="width:829px" %)If the register type is word address, the integer only needs to represent the byte, such as 1, which represents the first byte of 8-byte data in the data frame, and the unit of length is byte, and so on.
1708 |4|(% style="width:207px" %)Add|(% style="width:829px" %)Add current configuration
1709 |5|(% style="width:207px" %)Close|(% style="width:829px" %)Close the configuration window to exit
1710
1711 **Multiple Packages Settings**
1712
1713 (% style="text-align:center" %)
1714 [[image:12.PLC Protocol_html_107e0f6b1a90afff.png||data-xwiki-image-style-alignment="center" height="341" width="600" class="img-thumbnail"]]
1715
1716 Check [Multiple packages supported] to open [Multiple package data] window, as below show.
1717
1718 Select Multiple package type
1719
1720 * Not Multiple packages
1721 * J1939 Multiple packages
1722 * Customized Multiple packages
1723
1724 Click [Edit Receive data] for [Receive] settings
1725
1726 * Start code+ Total length (J1939)
1727
1728 (% style="text-align:center" %)
1729 [[image:12.PLC Protocol_html_3c360c6b5aca51bf.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1730
1731 As set above set, J1939 command is received by the HMI, only when its length is 25 bytes, and the start code is 0x57, 0x1B;
1732
1733 * Start code + Data max length (J1939)
1734
1735 (% style="text-align:center" %)
1736 [[image:12.PLC Protocol_html_74496b2a68cfcdde.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1737
1738 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes, and the start code is 0x57, 0x1B;
1739
1740 * Data max length (J1939)
1741
1742 (% style="text-align:center" %)
1743 [[image:12.PLC Protocol_html_98cea3e7cbd8f05d.png||data-xwiki-image-style-alignment="center" height="340" width="426" class="img-thumbnail"]]
1744
1745 As set above set, J1939 command is received by the HMI, only when its length less than 50 bytes.
1746
1747 * Customized multiple package
1748
1749 (% style="text-align:center" %)
1750 [[image:12.PLC Protocol_html_4635bbe4d7999db0.png||data-xwiki-image-style-alignment="center" height="395" width="367" class="img-thumbnail"]]
1751
1752 As set above, It is received by the HMI, when the first frame starts with 0X57 0X1B, and the sum of the data lengths of multiple frames is equal to 79 bytes.
1753
1754 Click [Edit Send data] for [Send] setting
1755
1756 * J1939
1757
1758 (% style="text-align:center" %)
1759 [[image:12.PLC Protocol_html_a4769e44331ca732.png||data-xwiki-image-style-alignment="center" height="280" width="463" class="img-thumbnail"]]
1760
1761 [Data] is all data to be sent.
1762
1763 Since the frame of the J1939 frame contains the number of the data packet, so the data sent is: the first byte (number) + 7 bytes of data. If it is less than 7 bytes, it is sent in the actual number of bytes.
1764
1765 * Customized multiple package
1766
1767 (% style="text-align:center" %)
1768 [[image:12.PLC Protocol_html_78546f765d6f3deb.png||data-xwiki-image-style-alignment="center" height="280" width="463"]]
1769
1770 [Data] is all data to be sent.
1771
1772 As set above, fist frame length is 2 bytes, and others are sent with 6 bytes for every frame, if the last frame is less than 6 bytes, send according to the actual length.
1773
1774 **Cable Wiring**
1775
1776 (% style="text-align:center" %)
1777 [[image:12.PLC Protocol_html_fccede84efcbdc22.png||data-xwiki-image-style-alignment="center" height="111" width="391" class="img-thumbnail"]]
1778
1779 **✎Note:** The address interval between each frame need to be more than a word address;
1780
1781 = **SHIMADEN** =
1782
1783 == **FP23** ==
1784
1785 Supported series: SHIMADEN FP23 series
1786
1787 **HMI Setting**
1788
1789 (% class="table-bordered" %)
1790 |**Items**|**Settings**|**Note**
1791 |Protocol|SHIMADEN FP23 series|
1792 |Connection|RS485 (9600, 1, 7, EVEN)|
1793 |Port No.|None|
1794 |PLC station No.|0|
1795
1796 **Address List**
1797
1798 (% class="table-bordered" %)
1799 |**Device address**|**HMI register**|**Address range**|**Type**
1800 |0040-0043(HEX)|FP040|100064-200067|Read only
1801 |0100-010B(HEX)|FP100|100256-200267|Read only
1802 |0110-0142(HEX)|FP110|100272-200322|Read only
1803 |0182-0252(HEX)|FP182|100386-200594|Write only
1804 |0280-0281(HEX)|FP280|100640-200641|Read only
1805 |0300-030B(HEX)|FP300|100768-200779|Read and write
1806 |0380-039F(HEX)|FP380|100896-200927|Read and write
1807 |0400-04D7(HEX)|FP400|101024-201239|Read and write
1808 |0500-05B0(HEX)|FP500|101280-201456|Read and write
1809 |0600-0670(HEX)|FP600|101536-201814|Read and write
1810 |0720-0738(HEX)|FP720|101824-201848|Read and write
1811 |0800-083F(HEX)|FP800|102048-202111|Read and write
1812 |0900-0952(HEX)|FP900|102304-202386|Read and write
1813 | |Ctrl|0-2|
1814
1815 **✎Note:**
1816
1817 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1818 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in FP23;
1819 * The Ctrl register is used to store the control group number and BCC check mode.
1820
1821 **Ctrl Register Description**
1822
1823 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1824 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1825 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1826 * Ctrl3 reserved
1827
1828 **✎Note:**
1829
1830 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1831
1832 **Cable Wiring**
1833
1834 (% style="text-align:center" %)
1835 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1836
1837 (% style="text-align:center" %)
1838 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1839
1840 **✎Note:** COM3 only available in PI8000/PI9000 series.
1841
1842 == **{{id name="_Toc23422"/}}SR90** ==
1843
1844 Supported series: SHIMADEN SR90 series
1845
1846 **HMI Setting**
1847
1848 (% class="table-bordered" %)
1849 |**Items**|**Settings**|**Note**
1850 |Protocol|SHIMADEN SR90 protocol|
1851 |Connection|RS485 (1200, 1, 7, EVEN)|
1852 |Port No.|None|
1853 |PLC station No.|0|
1854
1855 **Address List**
1856
1857 (% class="table-bordered" %)
1858 |**Device address**|**HMI register**|**Address range**|**Type**
1859 |0040-0043 (HEX)|SR040|100064-100067|Read only
1860 |0100-010A(HEX)|SR0100|100256-100266|Read only
1861 |0182-018C(HEX)|SR0182|100386-100396|Write only
1862 |0300-04FE(HEX)|SR0300|100768-101278|Write/read
1863 |0500-050B(HEX)|SR0500|101280-101291|Write/read
1864 |0590-0611(HEX)|SR0590|101424-101553|Write/read
1865 |0701-0709(HEX)|SR0701|101793-101801|Write/read
1866 | |Ctrl|0-2|~-~-
1867
1868 **✎Note:**
1869
1870 * The upper 2 bits of the address of HMIs are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1871 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in SR90;
1872 * The Ctrl register is used to store the control group number and BCC check mode. See how to use it below;
1873
1874 **Ctrl Register Description**
1875
1876 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1877 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR , STX_ETX_CR LF and @_:_CR .
1878 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1879 * Ctrl3 reserved
1880
1881 **✎Note:**
1882
1883 After reloading the HMI project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1884
1885 **Cable Wiring**
1886
1887 (% style="text-align:center" %)
1888 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1889
1890 (% style="text-align:center" %)
1891 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1892
1893 **✎Note:** COM3 only available in PI8000/PI9000 series.
1894
1895 == **{{id name="_Toc22635"/}}MR13 series(standard protocol)** ==
1896
1897 Supported series: SHIMADEN MR13 series
1898
1899 **HMI Setting**
1900
1901 (% class="table-bordered" %)
1902 |**Items**|**Settings**|**Note**
1903 |Protocol|SHIMADEN standard protocol|
1904 |Connection|RS485 (1200, 1, 7, EVEN)|
1905 |Port No.|None|
1906 |PLC station No.|0|
1907
1908 **Address List**
1909
1910 (% class="table-bordered" %)
1911 |**Device address**|**HMI register**|**Address range**|**Type**
1912 |0100-010B(HEX)|MR100|100256-300267|Read only
1913 |0111-0126(HEX)|MR111|100273-300294|Read only
1914 |0184-0192(HEX)|MR184|100388-300402|Write only
1915 |0280-0282(HEX)|MR280|100640-300642|Read only
1916 |0300-030B(HEX)|MR300|100768-300779|Read/write
1917 |0314-0317(HEX)|MR314|100788-300791|Read/write
1918 |031A(HEX)|MR31A|100794-300794|Read/write
1919 |0320-0321(HEX)|MR320|100800-300801|Read/write
1920 |0400-0504(HEX)|MR400|101024-301284|Read/write
1921 |0506(HEX)|MR506|101286-301286|Read/write
1922 |0510-0514(HEX)|MR510|101296-301300|Read/write
1923 |0516-0524(HEX)|MR516|101302-301316|Read/write
1924 |0526(HEX)|MR526|101318-301318|Read/write
1925 |0580-08C3(HEX)|MR580|101408-302243|Read/write
1926 |~-~-|Ctrl|0-2|~-~-
1927
1928 **✎Note:**
1929
1930 * The upper 2 bits of the address of the HMI register are taken as the sub address, and the real address is the last four bits (for example, if the address is 100256, then 10 is the sub address as 1, and 0256 is the real address);
1931 * The address range in the table is only divided by the start and end addresses, and some of the addresses in the range have no corresponding address in MR13;
1932 * The Ctrl register is used to store the control group number and BCC check mode.
1933
1934 **Ctrl Register Description**
1935
1936 * The Ctrl register is a special register that does not communicate with the temperature controller. User needs to assign value in the screen according to the settings as in the temperature controller.
1937 * Ctrl0 indicates the setting of the control character, the valid values are 1, 2, 3 respectively, and the corresponding control group is: STX_ETX_CR, STX_ETX_CR LF and @_:_CR .
1938 * Ctrl1 indicates the BCC block check mode. The valid value range is 1-4. The corresponding check mode is: 1.ADD, 2.ADD_two's cmp, 3.XOR, 4.None;
1939 * Ctrl3 reserved
1940
1941 **✎Note:**
1942
1943 After reloading project or restarting the HMI, HMI will reset the value of ctrl0 and ctrl1 as 1, so user need to set these two values to make it the same as it in the temperature controller, then communication will be normal.
1944
1945 **Cable Wiring**
1946
1947 (% style="text-align:center" %)
1948 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
1949
1950 (% style="text-align:center" %)
1951 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
1952
1953 **✎Note:** COM3 only available in PI8000/PI9000 series.
1954
1955 = **Siemens** =
1956
1957 == **S7-200 Smart Ethernet** ==
1958
1959 Supported Series: Siemens S7-200 SMART Series Ethernet Module.
1960
1961 Website: [[http:~~/~~/www.siemens.com/entry/cc/en/>>url:http://www.siemens.com/entry/cc/en/]]
1962
1963 **HMI Setting**
1964
1965 (% class="table-bordered" %)
1966 |**Items**|**Settings**|**Note**
1967 |Protocol|Simens S7-200 Smart Ethernet|
1968 |Connection|Ethernet|
1969 |Port No.|102|
1970 |PLC station No.|2|
1971
1972 **Address List**
1973
1974 (% class="table-bordered" %)
1975 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
1976 |(% rowspan="9" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
1977 |Q|Q|Q ddddd.o|0.0~~99999.7|
1978 |V|VWbit|VWbit ddddd.o|0.0~~99999.7|
1979 |V|V|V ddddd.o|0.0~~99999.7|
1980 |M|M|M ddddd.o|0.0~~99999.7|
1981 |SM|SM|ddddd.o|0.0~~99999.7|
1982 |S|S|ddddd.o|0.0~~99999.7|Read only
1983 |T|T|ddddd|0~~99999|Timer state, read only
1984 |C|C|ddddd|0~~99999|Counter state, read only
1985 |(% rowspan="12" %)Word|I|IW|IW ddddd|0~~99999|
1986 |Q|QW|QW ddddd|0~~99999|
1987 |AI|AIW|AIW ddddd|0~~99999|
1988 |AQ|VB|VB ddddd|0~~99999|
1989 |V|VW|VW ddddd|0~~99998|(((
1990 VW0=VB (0~~1)
1991
1992 VW2=VB (2~~3)
1993
1994 Address value is a multiple of 2
1995 )))
1996 |V|VD|VD ddddd|0~~99998|(((
1997 VD0=VB (0~~3)
1998
1999 VD2=VB (4~~7)
2000
2001 Address value is a multiple of 4
2002 )))
2003 |M|MB|MB ddddd|0~~99999|
2004 |M|MW|MW ddddd|0~~99999|(((
2005 MW0=MB(0~~1)
2006
2007 MW2=MB(2~~3)
2008
2009 Address value is a multiple of 2
2010 )))
2011 |M|MD|MD ddddd|0~~99999|(((
2012 MD0=MB(0~~3)
2013
2014 MD4=MB(4~~7)
2015
2016 Address value is a multiple of 4
2017 )))
2018 |T|TW|TW ddddd|0~~99999|Value of timer
2019 |C|CW|CW ddddd|0~~99999|Value of counter
2020 |W|SW|SW ddddd|0~~99999|
2021
2022 **Communication Settings**
2023
2024 Enable HMI Ethernet in [Project Settings];
2025
2026 (% style="text-align:center" %)
2027 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2028
2029 Set PLC IP in [Device IP] settings;
2030
2031 (% style="text-align:center" %)
2032 [[image:12.PLC Protocol_html_70b0c4c2ee21b10d.png||data-xwiki-image-style-alignment="center" height="189" width="554" class="img-thumbnail"]]
2033
2034 * PLC IP Address: PLC IP
2035 * PLC pot No.: 102(fixed)
2036 * Network:TCP_Client_2N(fixed)
2037
2038 (% style="text-align:center" %)
2039 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2040
2041 * Wait timeout: depend on actual network situation (more than 1500 ms)
2042
2043 **Cable Wiring**
2044
2045 (% style="text-align:center" %)
2046 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2047
2048 == **S7-300 Ethernet** ==
2049
2050 Supported Series: Siemens S7-300 series PLC
2051
2052 **HMI Setting**
2053
2054 (% class="table-bordered" %)
2055 |**Items**|**Settings**|**Note**
2056 |Protocol|Simens S7-300 Ethernet|
2057 |Connection|Ethernet|
2058 |Port No.|102|
2059 |PLC station No.|2|Need to be same as the PLC setting
2060
2061 **Address List**
2062
2063 (% class="table-bordered" %)
2064 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2065 |(% rowspan="4" %)Bit|I|I|I ddddd.o|0.0~~99999.7|
2066 |Q|Q|Q ddddd.o|0.0~~99999.7|
2067 |M|M|M ddddd.o|0.0~~99999.7|
2068 |DB0.DB~~DB99.DB|DBxDBD|DBxDB nndddd.o|0.0~~99999999.7|(((
2069 nn: block number;
2070
2071 dddd: address;
2072 )))
2073 |(% rowspan="8" %)Word|I|IW|IW ddddd|0~~99999|
2074 |Q|QW|QW ddddd|0~~99999|
2075 |(% rowspan="3" %)M|MB|MB ddddd|0~~99999|
2076 |MW|MW ddddd|0~~99999|(((
2077 MW0=MB(0~~1)
2078
2079 MW2=MB(2~~3)
2080
2081 Address value is a multiple of 2
2082 )))
2083 |MD|MD ddddd|0~~99999|(((
2084 MD0=MB(0~~3)
2085
2086 MD4=MB(4~~7)
2087
2088 Address value is a multiple of 4
2089 )))
2090 |(% rowspan="3" %)DB0.DB~~DB99.DB|DBxDBB|DBxDBB nndddd|0~~99999999|(% rowspan="3" %)(((
2091 nn: block number;
2092
2093 dddd: address
2094 )))
2095 |DBxDBW|DBxDBW nndddd|0~~99999999
2096 |DBxDBD|DBxDBD nndddd|0~~99999999
2097
2098 **Communication Settings**
2099
2100 Enable HMI Ethernet in [Project Settings];
2101
2102 (% style="text-align:center" %)
2103 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2104
2105 Set PLC IP in [Device IP] settings;
2106
2107 (% style="text-align:center" %)
2108 [[image:12.PLC Protocol_html_910b1a0aa9e2201c.png||data-xwiki-image-style-alignment="center" height="188" width="554" class="img-thumbnail"]]
2109
2110 * PLC IP Address: PLC IP
2111 * PLC pot No.: 102(fixed)
2112 * Network:TCP_Client_2N(fixed)
2113
2114 (% style="text-align:center" %)
2115 [[image:12.PLC Protocol_html_5891afd92901b7ad.png||data-xwiki-image-style-alignment="center" height="276" width="347" class="img-thumbnail"]]
2116
2117 * Wait timeout: depend on actual network situation (more than 1500 ms)
2118
2119 **Cable Wiring**
2120
2121 (% style="text-align:center" %)
2122 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2123
2124 == **S7-1200 Ethernet** ==
2125
2126 Supported Series: Siemens S7-1200
2127
2128 **HMI Setting**
2129
2130 (% class="table-bordered" %)
2131 |**Items**|**Settings**|**Note**
2132 |Protocol|Siemens S7-1200|
2133 |Connection|Ethernet|
2134 |Port No.|102|
2135 |PLC station No.|2|
2136
2137 **Address List**
2138
2139 (% class="table-bordered" %)
2140 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2141 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2142 d:0~-~-9999
2143
2144 o:0-7
2145 )))|
2146 |Q|Q|Q d.o|(((
2147 d:0~-~-9999
2148
2149 o:0-7
2150 )))|
2151 |M|M|M d.o|(((
2152 d:0~-~-9999
2153
2154 o:0-7
2155 )))|
2156 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2157 nn:0-9999,
2158
2159 dddd:0-9999,
2160
2161 o:0-7
2162 )))|(((
2163 nn:DB No.
2164
2165 dddd:address value
2166
2167 o: digit address
2168 )))
2169 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2170 |M|MW|MW d|d:0-99999|(((
2171 MW0=MB(0~~1)
2172
2173 MW2=MB(2~~3)
2174
2175 Address value is a multiple of 2
2176 )))
2177 |M|MD|MD d|d:0-99999|(((
2178 MD0=MB(0~~3)
2179
2180 MD4=MB(4~~7)
2181
2182 Address value is a multiple of 4
2183 )))
2184 |I|IW|IW d|d:0-99999|
2185 |Q|QW|QW d|d:0-99999|
2186 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2187 nn:0-9999
2188
2189 dddd:0-9999
2190 )))|(((
2191 nn:DB No.
2192
2193 dddd:address value
2194 )))
2195 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2196 nn:0-9999
2197
2198 dddd:0-9999
2199 )))|(((
2200 nn:DB No.
2201
2202 dddd:address value
2203
2204 Address value is a multiple of 2
2205 )))
2206 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2207 nn:0-9999
2208
2209 dddd:0-9999
2210 )))|(((
2211 nn:DB No.
2212
2213 dddd:address value
2214
2215 Address value is a multiple of 4
2216 )))
2217
2218 **Communication Settings**
2219
2220 Enable HMI Ethernet in [Project Settings];
2221
2222 (% style="text-align:center" %)
2223 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-thumbnail"]]
2224
2225 Set PLC IP in [Device IP] settings;
2226
2227 (% style="text-align:center" %)
2228 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2229
2230 **✎Note:**
2231
2232 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2233 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2234
2235 **PLC Settings**
2236
2237 Add BD
2238
2239 * Please uncheck [Symbolic access only] option;
2240
2241 (% style="text-align:center" %)
2242 [[image:12.PLC Protocol_html_643144c591994418.png||data-xwiki-image-style-alignment="center" height="546" width="550" class="img-thumbnail"]]
2243
2244 Address settings, using BD2 as example.
2245
2246 * DB×DBB2xxxx, DB×DBW2xxxx, DB×DBD2xxxx for accessing data of DB2 in B1.
2247 * 2 represent DB block number
2248 * xxxx represent address
2249
2250 **Such as:**
2251
2252 * DBxDBB20000 = DB2.DBB0
2253 * DBxDBW20004 = DB2.DBW4
2254
2255 (% style="text-align:center" %)
2256 [[image:12.PLC Protocol_html_87ceaea84d552e62.png||data-xwiki-image-style-alignment="center" height="245" width="537" class="img-thumbnail"]]
2257
2258 **How to connect with S7-1200 Firmware V4.0**
2259
2260 PLC configuration
2261
2262 * Double click [device configuration] in Siemens via software
2263 * Double click [protection] to enter protection configuration screen
2264
2265 (% style="text-align:center" %)
2266 [[image:12.PLC Protocol_html_9779940d38da8e07.png||data-xwiki-image-style-alignment="center" height="426" width="341" class="img-thumbnail"]]
2267
2268 * Check [Permit access with PUT / GET communication from remote partner (PLC, HMI, OPC, ...)]
2269
2270 (% style="text-align:center" %)
2271 [[image:12.PLC Protocol_html_d2c667b02f9720b1.png||data-xwiki-image-style-alignment="center" height="296" width="554" class="img-thumbnail"]]
2272
2273 DB settings
2274
2275 * Right click [DB], select [properties]
2276 * Uncheck [optimized block access]
2277
2278 **Cable Wiring**
2279
2280 (% style="text-align:center" %)
2281 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2282
2283 == **LOGO Ethernet** ==
2284
2285 Supported Series: Siemens Logo 0BA0 series
2286
2287 **HMI Settings**
2288
2289 (% class="table-bordered" %)
2290 |**Items**|**Settings**|**Note**
2291 |Protocol|Siemens LOGO|
2292 |Connection|Ethernet|
2293 |Port No.|102|
2294 |PLC station No.|2|
2295
2296 **Address List**
2297
2298 (% class="table-bordered" %)
2299 |**Number**|**Address Type**|**Data Type**|**Range**|**DB Address**|**PLC Address**
2300 |1|RTC|Word|1-7|DB1.DBX984.0|0x001ec0
2301 |2|VB|Byte|0-1469|DB1.DBX0.0|0x000000
2302 |3|VD|Double Word|0-1466|DB1.DBX0.0|0x000000
2303 |4|VW|Word|0-1468|DB1.DBX0.0|0x000000
2304 |5|NAQ|Word|1-32|DB1.DBX1406.0|0x002bf0
2305 |6|NAI|Word|1-64|DB1.DBX1262.0|0x002770
2306 |7|AM|Word|1-64|DB1.DBX1118.0|0x0022f0
2307 |8|AQ|Word|1-16|DB1.DBX1072.0|0x002180
2308 |9|AI|Word|1-16|DB1.DBX1032.0|0x002040
2309 |10|I|Bit|1-64|DB1.DBX1024.0|0x002000
2310 |11|Q|Bit|1-64|DB1.DBX1064.0|0x002140
2311 |12|M|Bit|1-112|DB1.DBX1104.0|0x002280
2312 |13|NI|Bit|1-128|DB1.DBX1246.0|0x0026f0
2313 |14|NQ|Bit|1-128|DB1.DBX1390.0|0x002b70
2314 |15|V|Bit|0-14697|DB1.DBX0.0|0x000000
2315
2316 **PLC Settings in LOGO Software:**
2317
2318 Click [Tools]~-~-[Ethernet Connections],shown as below.
2319
2320 (% style="text-align:center" %)
2321 [[image:12.PLC Protocol_html_8b9d2322edf89519.png||data-xwiki-image-style-alignment="center" height="641" width="423" class="img-thumbnail"]]
2322
2323 Set Ethernet connection parameter. IP, Subnet Mask, shown as below.
2324
2325 (% style="text-align:center" %)
2326 [[image:12.PLC Protocol_html_6c4dd041b26cd8a1.png||data-xwiki-image-style-alignment="center" height="481" width="363" class="img-thumbnail"]]
2327
2328 **TSAP set**:The value set by local TSAP is the remote TSAP set in HMI. PLC's remote TSAP is the opposite,shown as below.
2329
2330 (% style="text-align:center" %)
2331 [[image:12.PLC Protocol_html_7af2611d3790a77d.png||data-xwiki-image-style-alignment="center" height="359" width="426" class="img-thumbnail"]]
2332
2333 **Download Project**: Click "Address book" to add the IP address to be downloaded (fi."Detect" to check whether the IP address can be detected. Then click “ok”, and the system will prompt that PLC will be "STOP" mode. Click “YES” to start download.
2334
2335 (% style="text-align:center" %)
2336 [[image:12.PLC Protocol_html_3243e4cd600595cc.png||data-xwiki-image-style-alignment="center" height="368" width="554" class="img-thumbnail"]]
2337
2338
2339 (% style="text-align:center" %)
2340 [[image:12.PLC Protocol_html_cb1d92e2cc91a8db.png||data-xwiki-image-style-alignment="center" height="320" width="553" class="img-thumbnail"]]
2341
2342
2343 **HMI Communication Settings**
2344
2345 Set PLC IP in [Device IP] settings;
2346
2347 (% style="text-align:center" %)
2348 [[image:SiemensLOGODeviceIP.png]]
2349
2350 Enable HMI Ethernet in [Project Settings];
2351
2352 (% style="text-align:center" %)
2353 [[image:12.PLC Protocol_html_95917a3d92068467.png||data-xwiki-image-style-alignment="center" height="311" width="553" class="img-thumbnail"]]
2354
2355 TSAP setting
2356
2357 * Regarding the setting of PLC TSAP, HMI provides system special address for setting, it is recommended to run in HMI script initialization, write PLC TSAP to corresponding system special register.
2358 * HSW10118 = local TSAP of HMI, this is remote TSAP of PLC.
2359 * HSW10119 = Remote TSAP of HMI, this is local TSAP of PLC.
2360
2361 **✎Note:**
2362
2363 * The data of TSAP is hexadecimal format. For example: the remote TSAP configured in the PLC is set to 20.00, then HSW10118 should be set to 0x2000, that is, HSW10118 = 8192.
2364
2365 (% style="text-align:center" %)
2366 [[image:12.PLC Protocol_html_5c6374b21f46e01e.png||data-xwiki-image-style-alignment="center" height="139" width="498" class="img-thumbnail"]]
2367
2368
2369 * AI word address and Ibit address are read-only and cannot be written on HMI.
2370 * VW address should be even number.such as VW0, VW2, VW4...
2371 * VD address it takes two VW addresses.such as VD0,VD4,VD8...
2372 * Written value of RTC cannot exceed 255.
2373
2374 **Cable Wiring**
2375
2376 (% style="text-align:center" %)
2377 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2378
2379 == **S7-XXX Ethernet** ==
2380
2381 Supported Series: Siemens S7-400, S7-1200 and S7-1500
2382
2383 **HMI Setting**
2384
2385 (% class="table-bordered" style="width:823px" %)
2386 |=**Items**|=(% style="width: 437px;" %)**Settings**|=(% style="width: 201px;" %)**Note**
2387 |Protocol|(% style="width:437px" %)Siemens S7-XXX|(% style="width:201px" %)
2388 |Connection|(% style="width:437px" %)Ethernet|(% style="width:201px" %)
2389 |Port No.|(% style="width:437px" %)102|(% style="width:201px" %)
2390 |Device No.|(% style="width:437px" %)Slot (Default 1 for S7-1500/ 2 for S7-1200/ 3 for S7-400)|(% style="width:201px" %)
2391 |HMI No.|(% style="width:437px" %)Rack (Default as 0)|(% style="width:201px" %)
2392
2393 Slot from TIA Portal is equal to Device No. of PIStudio
2394
2395 Rack from TIA Portal is equal to HMI No. of PIStudio
2396
2397 (% style="text-align:center" %)
2398 [[image:S7-XXXCommunication Settings.png]]
2399
2400 (% style="text-align:center" %)
2401 [[image:S7-XXXCommunication SettingsPIStudio.png||alt="S7-XXXCommunication SettingsPI.png"]]
2402
2403 **Address List**
2404
2405 (% class="table-bordered" %)
2406 |**Type**|**Device register**|**HMI register**|**Format**|**Range**|**Note**
2407 |(% rowspan="4" %)Bit|I|I|M d.o|(((
2408 d:0~-~-9999
2409
2410 o:0-7
2411 )))|
2412 |Q|Q|Q d.o|(((
2413 d:0~-~-9999
2414
2415 o:0-7
2416 )))|
2417 |M|M|M d.o|(((
2418 d:0~-~-9999
2419
2420 o:0-7
2421 )))|
2422 |DB0.DB-DB99.DB|DBxDB|DBxDBnndddd.o|(((
2423 nn:0-9999,
2424
2425 dddd:0-9999,
2426
2427 o:0-7
2428 )))|(((
2429 nn:DB No.
2430
2431 dddd:address value
2432
2433 o: digit address
2434 )))
2435 |(% rowspan="8" %)Word|M|MB|MB d|d:0-99999|
2436 |M|MW|MW d|d:0-99999|(((
2437 MW0=MB(0~~1)
2438
2439 MW2=MB(2~~3)
2440
2441 Address value is a multiple of 2
2442 )))
2443 |M|MD|MD d|d:0-99999|(((
2444 MD0=MB(0~~3)
2445
2446 MD4=MB(4~~7)
2447
2448 Address value is a multiple of 4
2449 )))
2450 |I|IW|IW d|d:0-99999|
2451 |Q|QW|QW d|d:0-99999|
2452 |DB0.DB-DB99.DB|DBxDBB|DBxDBBnndddd|(((
2453 nn:0-9999
2454
2455 dddd:0-9999
2456 )))|(((
2457 nn:DB No.
2458
2459 dddd:address value
2460 )))
2461 |DB0.DB-DB99.DB|DBxDBW|DBxDBWnndddd|(((
2462 nn:0-9999
2463
2464 dddd:0-9999
2465 )))|(((
2466 nn:DB No.
2467
2468 dddd:address value
2469
2470 Address value is a multiple of 2
2471 )))
2472 |DB0.DB-DB99.DB|DBxDBD|DBxDBDnndddd|(((
2473 nn:0-9999
2474
2475 dddd:0-9999
2476 )))|(((
2477 nn:DB No.
2478
2479 dddd:address value
2480
2481 Address value is a multiple of 4
2482 )))
2483
2484 **Communication Settings**
2485
2486 Enable HMI Ethernet in [Project Settings];
2487
2488 (% style="text-align:center" %)
2489 [[image:12.PLC Protocol_html_43b671f18153910d.png||data-xwiki-image-style-alignment="center" height="107" width="405" class="img-rounded img-thumbnail"]]
2490
2491 Set PLC IP in [Device IP] settings;
2492
2493 (% style="text-align:center" %)
2494 [[image:12.PLC Protocol_html_f7b3eb9abda33833.png||data-xwiki-image-style-alignment="center" height="190" width="554" class="img-thumbnail"]]
2495
2496 **✎Note:**
2497
2498 * The S7-1200 supports simultaneous connection of three devices, so the driver supports simultaneous access to PLC by three touch screens.
2499 * HMI access PLC, use S7 protocol, access PLC TSAP 02.01 (s7-1200 PROFINET interface only supports three connections, the default support), detailed reference to the system manual of S7-1200.
2500
2501 **Cable Wiring**
2502
2503 {{id name="OLE_LINK8"/}}
2504
2505 (% style="text-align:center" %)
2506 [[image:12.PLC Protocol_html_2297240b57346b2a.png||data-xwiki-image-style-alignment="center" height="170" width="401" class="img-thumbnail"]]
2507
2508 = **User Defined Protocol** =
2509
2510 If the device does not support MODBUS standard, and the protocol is not list in PIStudio, then user can define the protocol by following instruction to realize simply communication functions like sending and receiving commands.
2511
2512 **HMI Settings**
2513
2514 (% class="table-bordered" %)
2515 |**Items**|**Settings**|**Note**
2516 |Protocol|User defined protocol|
2517 |Connection|RS485/RS232|
2518 |Baud rate|2400~~187500|
2519 |Stop bits|1/ 2|
2520 |Data bits|7/ 8|
2521 |Parity|None/ Even/ ODD|
2522
2523 **Operating Procedures**
2524
2525 Select [User defined protocol];
2526
2527 Click [User defined protocol] button to open setting window as below;
2528
2529 (% style="text-align:center" %)
2530 [[image:12.PLC Protocol_html_5ca13817ac812cf0.png||data-xwiki-image-style-alignment="center" height="367" width="437" class="img-thumbnail"]]
2531
2532 Configure user defined command;
2533
2534 (% style="text-align:center" %)
2535 [[image:12.PLC Protocol_html_11441e69f21e243d.png||data-xwiki-image-style-alignment="center" height="525" width="553" class="img-thumbnail"]]
2536
2537 (% class="table-bordered" %)
2538 |**No**|**Item**|**Description**
2539 |1|Instruction edit|The required command.
2540 |2|Mode|Write to address or read from the address.
2541 |3|Format|Encode format: HEX or ASCII.
2542 |4|Other|(((
2543 **No receiving: **HMI does not respond to the receiving command.
2544
2545 **Send after receiving:** HMI responds to the receiving command.
2546 )))
2547 |5|Manually send|(((
2548 Respond once after trigger the address.
2549
2550 Address: set the trigger address.
2551 )))
2552 |6|Add|Save this setting.
2553 |7|Cancel|Cancel current settings.
2554 |(% rowspan="4" %)8|Add|Add a new command.
2555 |Edit|Edit the selected command.
2556 |Delete|Delete the selected command.
2557 |Clear|Clear all the commands.
2558 |9|Instruction list|Display all current commands.
2559 |10|Address List|Display all the addresses added.
2560 |(% rowspan="5" %)11|Import|Import the command files to the instruction list.
2561 |Export|Export current command settings to local storage.
2562 |Browse|Browse local command files.
2563 |Advanced|Combine two commands.
2564 |Exit|Complete editing and exit setting.
2565
2566 **Operating Procedures**
2567
2568 Click [Add] to create a new command, as below shows;
2569
2570 (% style="text-align:center" %)
2571 [[image:12.PLC Protocol_html_463f2cd3a8c338fc.png||data-xwiki-image-style-alignment="center" height="116" width="88" class="img-thumbnail"]]
2572
2573 Select mode, [Read] or [Write], and then select Format, there are two options [Hex] and [ASCII]. As below shows;
2574
2575 (% style="text-align:center" %)
2576 [[image:12.PLC Protocol_html_a48eba3aa30b612d.png||data-xwiki-image-style-alignment="center" height="80" width="121" class="img-thumbnail"]]
2577
2578 Other settings: [No receiving] means HMI only sends command, and it would not process the reply command which from device. [Send after receiving] means HMI will be receiving the command which from device firstly, and then sending the command to device. From example, when HMI receiving [00 FF 00] firstly and then send command, as below shows
2579
2580 (% style="text-align:center" %)
2581 [[image:12.PLC Protocol_html_b36d990e126365d.png||data-xwiki-image-style-alignment="center" height="77" width="179" class="img-thumbnail"]]
2582
2583 Check [Manually send], and then please set the address for trigging, the setting range is 1~~10, and please put Bit switch in project screen for it, and [OneCtrlBit] register is for [Manually send].
2584
2585 Instruction edit, when the data format is HEX, please use two numbers to represent one 16-bit number. ASCII format using characters to input;
2586
2587 Check settings;
2588
2589 (% style="text-align:center" %)
2590 [[image:12.PLC Protocol_html_5ac7075d9e8dad8d.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2591
2592 (% class="table-bordered" %)
2593 |**No**|**Items**|**Description**
2594 |1|Add checking|Add checking command when receiving the data.
2595 |(% rowspan="2" %)2|Back checking|Add control character in ASCII format.
2596 |Differ with send check|Set return checking.
2597 |(% rowspan="2" %)3|(% rowspan="2" %)Add control character|Start position: select the start position of the data which need to check.
2598 |Length: The data length need to be checked.
2599
2600 Object settings;
2601
2602 (% style="text-align:center" %)
2603 [[image:12.PLC Protocol_html_1e776a838316fb5.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2604
2605 (% class="table-bordered" %)
2606 |**No**|**Items**|**Description**
2607 |(% rowspan="3" %)1|(% rowspan="3" %)Object settings|Object type: bit or word address;
2608 |Address: the triggering address;
2609 |Note: description to object;
2610 |2|Byte order|The numerical display order;
2611
2612 Data length settings;
2613
2614 (% style="text-align:center" %)
2615 [[image:12.PLC Protocol_html_6959664a46b03b69.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2616
2617 (% class="table-bordered" %)
2618 |**No**|**Item**|**Description**
2619 |(% rowspan="2" %)1|(% rowspan="2" %)Return data|Position: the start position of the return data.
2620 |Length: the return data length.
2621 |(% rowspan="2" %)2|(% rowspan="2" %)Write data|Position: the start position of the write data.
2622 |Length: the write data length.
2623
2624 Instruction length settings
2625
2626 (% style="text-align:center" %)
2627 [[image:12.PLC Protocol_html_7e0d8613c5e12f7b.png||data-xwiki-image-style-alignment="center" height="185" width="554" class="img-thumbnail"]]
2628
2629 (% class="table-bordered" %)
2630 |**No**|**Item**|**Description**
2631 |1|Send length|The instruction data will only send designated data length.
2632 |2|Return length|The responds data length.
2633 |3|End code|Instruction will not be terminated until receiving [End code];
2634
2635 **Cable Wiring**
2636
2637 * **RS485**
2638
2639 (% style="text-align:center" %)
2640 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2641
2642 (% style="text-align:center" %)
2643 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2644
2645 * **RS232**
2646
2647 (% style="text-align:center" %)
2648 [[image:12.PLC Protocol_html_5de71638aab8e40d.png||data-xwiki-image-style-alignment="center" height="205" width="385" class="img-thumbnail"]]
2649
2650 **✎Note:** COM3 only available in PI8000/PI9000 series.
2651
2652 = =
2653
2654 = **Printer** =
2655
2656 == **TSPL label printer** ==
2657
2658 **Introduction**
2659
2660 TSPL label printer protocol supports following models.
2661
2662 * SPRT TL21: [[https:~~/~~/www.sprinter.com.cn/show-60-62-1.html>>https://www.sprinter.com.cn/show-60-62-1.html]]
2663 * DL-888D: [[https:~~/~~/www.deliworld.com/product/detail/7624>>https://www.deliworld.com/product/detail/7624]]
2664
2665 **Setting Step**
2666
2667 Select the protocol
2668
2669 * Create a new project, select the TSPL label printer protocol as shown below.
2670
2671 (% style="text-align:center" %)
2672 [[image:12.PLC Protocol_html_a2bec264816230db.png||data-xwiki-image-style-alignment="center" height="331" width="495" class="img-thumbnail"]]
2673
2674 Set parameters
2675
2676 * The connection between the TSPL label printer and the HMI is via the USB-A interface, no need to configure serial port parameters.
2677
2678 Printer register
2679
2680 (% class="table-bordered" %)
2681 |**Register**|**System**|**Range**|**Function**
2682 |TSPL_SP|decimal|0 - 1|Set the paper size
2683 |TSPL_PT|decimal|0 - 1999|Print text
2684 |TSPL_PQ|decimal|0 - 999|Print QR code
2685 |TSPL_PB|decimal|0 - 999|Print barcode
2686 |TSPL_PR|decimal|0 - 1|Print offset
2687 |TSPL_PN|decimal|0 - 0|Trigger printing
2688 |TSPL_PS|decimal|0 - 0|Print status
2689
2690 * Set paper size:
2691 ** TSPL_SP0: width of paper, unit: mm.
2692 ** TSPL_SP1: height of paper, unit: mm.
2693 * Print text:
2694 ** TSPL_PT can print up to 20 texts. TSPL_PT0-TSPL_PT99 is the first text; TSPL_PT100-TSPL_PT199 is the second text; … TSPL_PT1000-TSPL_PT1999 is the 20th text.
2695 ** Detailed parameter settings of each text is shown as below table. For example, first text,TSPL_PT0-TSPL_PT99.
2696
2697 (% class="table-bordered" %)
2698 |**Register**|**Function**|**Description**
2699 |TSPL_PT0|X coordinate|Unit: dot
2700 |TSPL_PT1|Ycoordinate|Unit: dot
2701 |TSPL_PT2|Rotation angle|(((
2702 0: 0 degrees
2703
2704 1: 90 degrees
2705
2706 2: 180 degrees
2707
2708 3: 270 degrees
2709 )))
2710 |TSPL_PT3|Size|Range: 0-3
2711 |TSPL_PT4 - TSPL_PT99|QR code content(text content)|Use character input device to configure
2712
2713 By analogy, we can know the text information configuration of the 2nd to 20th QR codes
2714
2715 Print QR code:
2716
2717 * TSPL_PQ can print up to 10 QR codes. TSPL_PQ0-TSPL_PQ99 is the first QR code; TSPL_PQ100-TSPL_PQ199 is the second QR code; ...., TSPL_PQ900-TSPL_PQ999 is the tenth QR code.
2718 * Specific parameter description of each item: for example, the first QR code, TSPL_PQ0-TSPL_PQ99:
2719
2720 (% class="table-bordered" %)
2721 |**Register**|**Function**|**Description**
2722 |TSPL_PQ0|X coordinate|Unit: dot
2723 |TSPL_PQ1|Ycoordinate|Unit: dot
2724 |TSPL_PQ2|Rotation angle|(((
2725 0: 0 degrees
2726
2727 1: 90 degrees
2728
2729 2: 180 degrees
2730
2731 3: 270 degrees
2732 )))
2733 |TSPL_PQ3|Size|Range: 0-5
2734 |TSPL_PQ4 - TSPL_PQ99|QR code content|Use character input device to configure
2735
2736 * By analogy, we can know the text information configuration of the 2nd to 20th QR codes.
2737
2738 Print bar code:
2739
2740 * TSPL_PB can print up to 10 barcodes. TSPL_PB0-TSPL_PB99 is the first bar code; TSPL_PB100-TSPL_PB199 is the second bar code; ..., TSPL_PB900-TSPL_PB999 is the tenth bar code.
2741 * Specific parameter description of each item: for example, the first barcode, TSPL_PB0-TSPL_PB99:
2742
2743 (% class="table-bordered" %)
2744 |**Register**|**Function**|**Description**
2745 |TSPL_PB0|X coordinate|Unit: dot
2746 |TSPL_PB1|Ycoordinate|Unit: dot
2747 |TSPL_PB2|Rotation angle|(((
2748 0: 0 degrees
2749
2750 1: 90 degrees
2751
2752 2: 180 degrees
2753
2754 3: 270 degrees
2755 )))
2756 |TSPL_PB3|height|Unit: dot
2757 |TSPL_PB4|width|Range:0-2
2758 |TSPL_PB5- TSPL_PB99|Bar code content|Use character input device to configure
2759
2760 By analogy, we can know the text information configuration of the 2nd to 20th bar codes.
2761
2762 Print offset:
2763
2764 * TSPL_PR0: X coordinate offset, unit: mm;
2765 * TSPL_PR1: Y coordinate offset, unit: mm.
2766
2767 Trigger printing:
2768
2769 * TSPL_PN0 = 1: trigger the printer to start printing.
2770
2771 Printing status:
2772
2773 * TSPL_PS0 = 1: The printing is normal.
2774 * TSPL_PS0 = 1: The printing is abnormal.
2775
2776 Print picture
2777
2778 * For the function of printing pictures, please refer to the configuration of [Printer object].
2779
2780 Conversion between dot and mm
2781
2782 * Dot is the meaning of pixels. For the conversion between dot and mm, please refer to the printer manual or consult the customer service of the corresponding printer manufacturer. For example, SPRT TL21: 8 dots / mm, that is, 1mm = 8 dot.
2783
2784 == **EpsonTM series** ==
2785
2786 **HMI Settings**
2787
2788 (% class="table-bordered" %)
2789 |**Item**|**Settings**|**Note**
2790 |Protocol|EPSON-TM-T82II/TM-XXX|
2791 |Connection|RS232|
2792 |Baud rate|9600~~115200|
2793 |Data bit|8|
2794 |Parity|None|
2795 |Stop bit|1|
2796 |PLC station No.|1|
2797
2798 Each printer protocol has default parameter. These parameters could be configured by addresses. Error parameters may cause print failure.
2799
2800 **Printer Settings**
2801
2802 (% class="table-bordered" %)
2803 |(% style="width:504px" %)**Address**|(% style="width:778px" %)**Description**|(% style="width:208px" %)**Value**
2804 |(% style="width:504px" %)HSW10603|(% style="width:778px" %)Print direction (only valid for print function)|(% style="width:208px" %)1
2805 |(% style="width:504px" %)HSW10604|(% style="width:778px" %)Dot Matrix Type|(% style="width:208px" %)1
2806 |(% style="width:504px" %)HSW10605|(% style="width:778px" %)Print width (depending on printer and paper)|(% style="width:208px" %)384
2807 |(% style="width:504px" %)HSW10606|(% style="width:778px" %)Printer instruction type|(% style="width:208px" %)1
2808 |(% style="width:504px" %)HSW10607|(% style="width:778px" %)Paper cut|(% style="width:208px" %)2
2809 |(% style="width:504px" %)HSW10608|(% style="width:778px" %)Alignment (only valid for print function)|(% style="width:208px" %)1
2810
2811 **Cable Wiring**
2812
2813 (% style="text-align:center" %)
2814 [[image:12.PLC Protocol_html_5e9a81a14106da9e.png||data-xwiki-image-style-alignment="center" height="223" width="392" class="img-thumbnail"]]
2815
2816 (% style="text-align:center" %)
2817 [[image:12.PLC Protocol_html_1897d92be6948d58.png||data-xwiki-image-style-alignment="center" height="223" width="393" class="img-thumbnail"]]
2818
2819 **✎Note:** COM3 only available in PI8000/PI9000 series.
2820
2821
2822 = **Schneider MODBUS RTU** =
2823
2824 **HMI Setting**
2825
2826 |=**Parameters**|=**Recommended**|=**Notes**
2827 |**Protocol**|(% colspan="1" %)Schneider MODBUS RTU|
2828 |Connection|RS485|
2829 |**Baud rate**|19200|
2830 |**Data bit**|8|
2831 |**Parity**|Even|
2832 |**Stop bit**|1|
2833 |**PLC station No.**|1|
2834
2835 **PLC Setting**
2836
2837 |=(% scope="row" %)**Communication mode**|Modbus RTU protocol
2838
2839 **Device Address**
2840
2841 |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo**
2842 |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only)
2843 |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils
2844 |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal)
2845 |W|MW|DDDDDD|0 ~~ 999999|Output register
2846 |DW|MD|DDDDDD|0 ~~ 999999|Output register
2847
2848 **Wiring Diagram**
2849
2850 **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector.
2851
2852 (% style="text-align:center" %)
2853 [[image:image-20220817154212-1.jpeg||height="315" width="554" class="img-thumbnail"]]