Changes for page LX3V-4AD

Last modified by Devin Chen on 2024/11/27 15:04

From version 12.1
edited by Jim
on 2023/08/07 16:27
Change comment: There is no comment for this version
To version 16.1
edited by Devin Chen
on 2024/11/27 15:04
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Jim
1 +XWiki.DevinChen
Content
... ... @@ -97,7 +97,8 @@
97 97  |Off|Channel closed
98 98  |Lighting|Input analog is in the normal range
99 99  
100 -[[image:LX3V-4AD_html_5bc4b53029347d0f.png||height="309" style="float:left" width="618" class="img-thumbnail"]]
100 +(% style="text-align:center" %)
101 +[[image:LX3V-4AD_html_5bc4b53029347d0f.png||height="309" width="618" class="img-thumbnail"]]
101 101  
102 102  
103 103  Please use crimp terminals as indicated on the graph.
... ... @@ -104,16 +104,6 @@
104 104  
105 105  The tightening torque should be applied 5 to 8 Kg.cm.
106 106  
107 -= =
108 -
109 -= =
110 -
111 -= =
112 -
113 -
114 -
115 -= =
116 -
117 117  = **3 Terminal layouts** =
118 118  
119 119  (% style="text-align:center" %)
... ... @@ -337,7 +337,10 @@
337 337  |b11: Averaging error|Number of averaging samples is 4097 or more or 0 or less (default of 8 will be used)|Averaging is normal. (Between 1 and 4096)
338 338  |b12: Adjust prohibit|Prohibit-(b1, b0) of BFM #21 is set to (1, 0)|Permit-(b1, b0) of BFM #21 is set to (0,1)
339 339  
331 +(% class="box infomessage" %)
332 +(((
340 340  **✎Note: **b8, b9 and b13 to b15 are undefined.
334 +)))
341 341  
342 342  **Identification Code BFM #30**
343 343  
... ... @@ -347,11 +347,14 @@
347 347  
348 348  The user’s program in the PC can use this facility in the program to identify the special function block before commencing data transfer from and to the special function block.
349 349  
344 +(% class="box infomessage" %)
345 +(((
350 350  **✎Note: **
351 351  
352 352  * Values of BFM #0, #23 and #24 are copied to EEPROM memory of the LX3V-4AD. BFM #21 and BFM #22 are only copied when data is written to the gain/offset command buffer BFM #22. Also, BFM #20 causes writing to the EEPROM memory. The EEPROM has a life of about 10,000 cycles (changes), so do not use programs which frequently change these BFMs.
353 353  
354 354  * Because of the time needed to write to the EEPROM memory, a delay of 300 ms is required between instructions that cause a write to the EEPROM. Therefore, a delay timer should be used before writing to the EEPROM a second time.
351 +)))
355 355  
356 356  = **5 Defining gain and offset** =
357 357  
... ... @@ -391,7 +391,6 @@
391 391  1. The operational status of the LX3V-4AD is read from BFM #29 and output as bit devices at the LX3V main unit. If there are no errors in the operation of the LX3V-4AD, then the averaged data BFM’s are read.
392 392  1. In the case of this example BFM #5 and #6 are read into the LX3V main unit and stored at D0 and D1. These devices contain the averaged data for CH1 and CH2 respectively.
393 393  
394 -
395 395  **Using gain and offset in a program**
396 396  
397 397  The gain and offset of the LX3V-4AD can be adjusted using push-button switches on the input terminal of the PC. It can also be adjusted using software settings sent from the PC.
... ... @@ -423,7 +423,7 @@
423 423  
424 424  **High-speed conversion by changing A/D conversion time in a program**
425 425  
426 -[[image:/bin/download/Expansions/1%20Module/Analog/LX3V-4AD/WebHome/6.3-%E5%9B%BE%E7%89%871.png?rev=1.1||alt="6.3-图片1.png"]][[image:/bin/download/Expansions/1%20Module/Analog/LX3V-4AD/WebHome/6.3-%E5%9B%BE%E7%89%871.png?rev=1.1||alt="6.3-图片1.png"]][[image:/bin/download/Expansions/1%20Module/Analog/LX3V-4AD/WebHome/6.3-%E5%9B%BE%E7%89%871.png?rev=1.1||alt="6.3-图片1.png"]][[image:/bin/download/Expansions/1%20Module/Analog/LX3V-4AD/WebHome/6.3-%E5%9B%BE%E7%89%871.png?rev=1.1||alt="6.3-图片1.png"]]**[[image:6.3-图片1.png]]**
422 +**[[image:6.3-图片1.png]]**
427 427  )))
428 428  
429 429  Writing K10 to BFM#15 and set conversion time of all channels as 3ms.
... ... @@ -430,8 +430,6 @@
430 430  
431 431  Writing 1 to BFM#1 and set Channel 1 sample count to 1 to Channel 1 high-speed conversion.
432 432  
433 -= =
434 -
435 435  = **7 Diagnostics** =
436 436  
437 437  **Preliminary checks**