Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.DevinChen
1 +XWiki.Mora
Content
... ... @@ -88,7 +88,7 @@
88 88  (% class="table-bordered" style="width:1117px" %)
89 89  |=(% rowspan="2" scope="row" style="width: 253px;" %)**Item**|=(% colspan="2" style="width: 378px;" %)**Centigrade (°C)**|=(% colspan="2" style="width: 445px;" %)**Fahrenheit (°F)**
90 90  |(% colspan="4" style="width:715px" %)Both °C and °F are available by reading the appropriate buffer memory (BFM).
91 -|(% style="width:253px" %)Input signal|(% colspan="4" style="width:823px" %)Thermocouple: Type K, J, T, E, N, B, R, S (Each type can be used for each channel), 4 channels most.
91 +|(% style="width:253px" %)Input signal|(% colspan="4" style="width:823px" %)Thermocouple: Type K, J, T, E, N, B, R, S (each type can be used for each channel), 4 channels most.
92 92  |(% rowspan="8" style="width:253px" %)(((
93 93  Rated temperature range
94 94  )))|(% style="width:130px" %)Type K|(% style="width:248px" %)-100 to +1,200|(% style="width:147px" %)Type K|(% style="width:298px" %)-148 to +2,192
... ... @@ -175,7 +175,7 @@
175 175  |=(% colspan="2" %)(((
176 176  **Conversion Characteristics**
177 177  
178 -Readings given at calibration reference point 0°C/32°F (0/320) respectively. (Subject to the overall accuracy)
178 +Readings given at calibration reference point 0°C/32°F (0/320) respectively. (subject to the overall accuracy)
179 179  )))
180 180  |[[image:LX3V-4LTC_html_92edc788ec28d1cf.gif||class="img-thumbnail"]]|[[image:LX3V-4LTC_html_304483742690ee7c.gif||class="img-thumbnail"]]
181 181  
... ... @@ -389,8 +389,6 @@
389 389  )))
390 390  |(% style="width:55px" %)#76~~#80|(% style="width:12px" %)#114~~#118|(% style="width:52px" %)#152~~#156|(% style="width:65px" %)#190~~#193|(% style="width:143px" %)Reserved|(% style="width:68px" %)-|(% style="width:77px" %)-|(% style="width:104px" %)-|(% style="width:348px" %)Reserved
391 391  
392 -(% class="box infomessage" %)
393 -(((
394 394  **✎Note: **
395 395  
396 396  * 0: Retentive;
... ... @@ -397,7 +397,6 @@
397 397  * X: Non-retentive;
398 398  * R: Only read is enabled;
399 399  * R/W: Both read and write are enabled;
400 -)))
401 401  
402 402  **Details of buffer memories**
403 403  
... ... @@ -460,17 +460,6 @@
460 460  
461 461  The identification code or ID number for this Special Block is read from buffer memory BFM #30 by FROM instruction. This number for the LX3V-4LTC unit is K2130. The PLC can use this ID in program to identify the special block before commencing data transfer to and from the special block.
462 462  
463 -**Power-down retention flag BFM#42**
464 -
465 -First, configure the parameters to be saved, and then set the power-down retention flag BFM#42 to 1. This enables power-down retention for the configured parameters.
466 -
467 -The operation steps are illustrated as follows:
468 -
469 -1. Set the power-down retention register to a value of 100 (e.g., BFM#52 is set to 100).
470 -1. Set the power-down retention flag BFM#42 to 1 (data is saved at this point, and BFM#42 will automatically reset to zero upon completion).
471 -1. Change the data of the power-down retention register to 1000 (e.g., BFM#52 is set to 1000).
472 -1. Power off and then power on again. At this point, check the value of the power-down retention register, which should be 100 (e.g., BFM#52 shows a value of 100)."
473 -
474 474  **Error flag BFM #43, BFM#81, BFM#119, BFM#157 (Temperature control is stopped)**
475 475  
476 476  (((
... ... @@ -613,8 +613,6 @@
613 613  |(% style="width:88px" %)11|(% style="width:238px" %)Alarm for Upper/lower limit deviation with wait|(% style="width:608px" %)Alarms if absolute deviation (= Measured value (PV) – Set value (SV)) is less than value of alarm. However, measured value is ignored at the start of system.|(% style="width:141px" %)+Input width
614 614  )))
615 615  
616 -(% class="box infomessage" %)
617 -(((
618 618  **✎Note: **
619 619  
620 620  * Input range: it is from the lower threshold to the upper threshold of input value
... ... @@ -621,7 +621,6 @@
621 621  * Input width: Width from the lower threshold to the upper threshold of input value (Input width = Upper threshold value - Lower threshold value).
622 622  * ±Input width: it could be positive and negative.
623 623  * + Input width: it could be positive only.
624 -)))
625 625  
626 626  **Alarm dead zone setting**
627 627