Changes for page LX6V-4PT

Last modified by Iris on 2026/03/24 15:34

From version 1.1
edited by Iris
on 2025/10/30 10:02
Change comment: There is no comment for this version
To version 4.1
edited by Iris
on 2025/10/30 10:04
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,0 +1,194 @@
1 += **Introduction** =
2 +
3 +
4 +
5 +LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
6 +
7 +LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
8 +
9 +Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.
10 +
11 +
12 +**✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.
13 +
14 +1. **Appearance and terminal description**
15 +11. **Appearance and size**
16 +
17 +
18 +
19 +[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps5.png]]
20 +
21 +① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5);
22 +
23 +⑤ DIN rail buckle.
24 +
25 +
26 +1.
27 +11. **Terminal description**
28 +
29 +The 4PT expansion module terminal are arranged as follows:
30 +
31 +
32 +|**Module model**|(% colspan="2" %)**Terminal arrangement**
33 +|LX6V-4PT| |[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps7.png]]
34 +
35 +
36 +
37 +1.
38 +11. **Installation**
39 +
40 +Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:
41 +
42 +[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps8.png]]
43 +
44 +
45 +1.
46 +11. **Indicator**
47 +
48 +The 4PT expansion module LED is shown below:
49 +
50 +|**Indicator**|**Description**
51 +|PWR|(((
52 +Power indicator
53 +
54 +1. Lights on: The module is powered on normally
55 +1. Lights out: The module is not powered on or the module is abnormal
56 +)))
57 +|LINK|(((
58 +Communication indicator
59 +
60 +1. Lights on: Data interaction is normal
61 +1. Lights out: Data interaction is abnormal or stopped
62 +)))
63 +|L1+/L2+/L3+/L4 +|(((
64 +Channel indicator
65 +
66 +1. Lights on: Channel enable
67 +1. Lights out: Channel disable
68 +1. Slow flash: Channel not calibrated
69 +1. Fast flash: Channel abnormal (refer to status code for details)
70 +)))
71 +|L1-/L2-/L3-/L4-|N/A
72 +|I1+/I2+/I3+/I4 +|N/A
73 +
74 +
75 +
76 +
77 +1. **Parameter Specification**
78 +11. **Input Specification**
79 +
80 +|**Item**|**Description**
81 +|Input channel|4
82 +|Digital resolution|16 bit
83 +|Sensitivity|0.01℃, 0.01℉
84 +|Input terminal|Thermocouple input
85 +|Sensor type|PT100, PT1000, CU50
86 +|Accuracy (normal temperature 25℃)|Full range ± 0.2%
87 +|Accuracy (working temperature -20℃ to 55℃)|Full range ± 0. 3%
88 +|Isolation or not|I/O terminals are isolated from power supply, channels are not isolated
89 +|Overlimit disconnection detection|Support
90 +|Power consumption|< 1.1W
91 +|Power supply|Power supply via interface, DC24V±10%, 40mA
92 +
93 +
94 +
95 +1.
96 +11. **Environmental specification**
97 +11.
98 +**Software Specifications**
99 +
100 +|**Item**|(% colspan="5" %)**Specification**
101 +|Usage environment|(% colspan="5" %)No corrosive, combustible gas, no large amount of conductive dust
102 +|Environment temperature|(% colspan="5" %)(((
103 +Working temperature: 0℃ to 55℃
104 +
105 +Storage temperature: -20℃ to 70℃
106 +)))
107 +|Environment humidity|(% colspan="5" %)(((
108 +Working humidity: 10% to 90%RH (no condensation)
109 +
110 +Storage humidity: ≤ 90% RH (no condensation)
111 +)))
112 +|Installation|(% colspan="5" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
113 +|(% rowspan="6" %)Vibration resistance|(% colspan="5" %)According to JISC0040 standard
114 +|Installation|Frequency|Acceleration|Amplitude|(% rowspan="5" %)(((
115 +X, Y, Z
116 +
117 +10 times in each of three directions
118 +
119 +(80 minutes in each direction)
120 +)))
121 +|(% rowspan="2" %)DIN rail installation|10 to 57Hz|~-~-|0.035mm
122 +|57 to 150Hz|4.9m/S^^2^^|~-~-
123 +|(% rowspan="2" %)Direct installation|10 to 57Hz|~-~-|0.075mm
124 +|57 to 150Hz|9.8m/S^^2^^|~-~-
125 +|Shock resistance|(% colspan="5" %)(((
126 +Compliant with JISC0041 standard
127 +
128 +(147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)
129 +)))
130 +|EMC immunity level|(% colspan="5" %)Zone B (per IEC 61131-2)
131 +|Altitude requirements|(% colspan="5" %)≤2000m (80 kPa)
132 +|Protection level|(% colspan="5" %)IP20
133 +|Grounding|(% colspan="5" %)Not co-located with the strong current system
134 +
135 +|**Item**|**Specification**
136 +|Input PDO data volume|Maximum 24 byte
137 +|Diagnostic reporting function configuration|Support
138 +|Diagnostic detection enable configuration|Support overlimit and disconnection detection
139 +|Sensor type configuration|(((
140 +Support thermal resistor type: PT100, PT1000, CU50, default is
141 +
142 +PT100 thermal resistance
143 +)))
144 +|Filter time|0s to 100s (can be configured by software, default 5s)
145 +|Overflow detection|Support
146 +|Overlimit detection enable configuration|Support
147 +|Independent channel configuration|Support
148 +|Temperature offset enable configuration|Support
149 +|Temperature offset configuration range|-300 to +300, temperature unit
150 +|Display mode|Celsius (℃), Fahrenheit (℉)
151 +|Display sensitivity|0.01℃, 0.01℉
152 +|Sample refresh|Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
153 +|Stop mode|Output according to the maximum value, no more refresh
154 +|Disconnected or overlimit|Output according to the maximum value, no more refresh
155 +|System diagnostics|System power abnormality
156 +|Channel diagnosis|Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
157 +|Configuration diagnostics|Configuration error identification, channel parameter configuration error
158 +
159 +
160 +
161 +
162 +1.
163 +11. **Accuracy calculation**
164 +
165 +Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.
166 +
167 +|**Sensor type**|**Detection range**|**Accuracy**
168 +|PT100|(((
169 +-200.0℃ to +850.0℃,
170 +
171 +-328.0℉ to +1562.0℉
172 +)))|(((
173 +T < 300°C: ±0.6℃
174 +
175 +300℃ ≤ T ≤ 700℃: ±1.4℃
176 +
177 +T > 700°C: ±1.7℃
178 +)))
179 +|PT1000|(((
180 +-200.0℃ to +850.0℃,
181 +
182 +-328.0℉ to +1562.0℉
183 +)))|(((
184 +T < 300°C: ±0.6℃
185 +
186 +300℃ ≤ T ≤ 700℃: ±1.4℃
187 +
188 +T > 700 °C: ±1.7℃
189 +)))
190 +|CU50|(((
191 +-50.0℃ to + 150.0℃,
192 +
193 +-58.0℉ to +302.0℉
194 +)))|-50℃ ≤ T ≤ 150℃: ±0.3℃