1 += **1 Introduction** =
2 +
3 +(% style="text-align:center" %)
4 +[[image:1761790581619-130.png||height="397" width="397"]]
5 +
6 +LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
7 +
8 +LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
9 +
10 +Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.
11 +
12 +**✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.
13 +
14 += **2 Appearance and terminal description** =
15 +
16 +== **2.1 ​​​​​Appearance and size** ==
17 +
18 +(% style="text-align:center" %)
19 +[[image:1761790728530-525.png]]
20 +
21 +① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5); ⑤ DIN rail buckle.
22 +
23 +== **2.2 Terminal description** ==
24 +
25 +The 4PT expansion module terminal are arranged as follows:
26 +
27 +(% style="margin-left:auto; margin-right:auto" %)
28 +|=(((
29 +**Module model**
30 +)))|=(% colspan="2" rowspan="1" %)(((
31 +**Terminal arrangement**
32 +)))
33 +|=(((
34 +LX6V-4PT
35 +)))|(((
36 +(% style="text-align:center" %)
37 +[[image:1761790846633-145.png]]
38 +)))|(((
39 +(% style="text-align:center" %)
40 +[[image:1761790839326-892.png]]
41 +)))
42 +
43 +== **2.3** **Installation** ==
44 +
45 +Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:
46 +
47 +
48 +(% style="text-align:center" %)
49 +[[image:1761790902574-569.png||height="377" width="719"]]
50 +
51 +== **2.4 Indicator** ==
52 +
53 +The 4PT expansion module LED is shown below:
54 +
55 +(% style="margin-left:auto; margin-right:auto" %)
56 +|=**Indicator**|=**Description**
57 +|=PWR|(((
58 +Power indicator
59 +
60 +1. Lights on: The module is powered on normally
61 +1. Lights out: The module is not powered on or the module is abnormal
62 +)))
63 +|=LINK|(((
64 +Communication indicator
65 +
66 +1. Lights on: Data interaction is normal
67 +1. Lights out: Data interaction is abnormal or stopped
68 +)))
69 +|=L1+/L2+/L3+/L4 +|(((
70 +Channel indicator
71 +
72 +1. Lights on: Channel enable
73 +1. Lights out: Channel disable
74 +1. Slow flash: Channel not calibrated
75 +1. Fast flash: Channel abnormal (refer to status code for details)
76 +)))
77 +|=L1-/L2-/L3-/L4-|(% style="text-align:center" %)N/A
78 +|=I1+/I2+/I3+/I4 +|(% style="text-align:center" %)N/A
79 +
80 +== **3 Parameter Specification** ==
81 +
82 +=== **3.1 Input Specification** ===
83 +
84 +(% style="margin-left:auto; margin-right:auto" %)
85 +|=**Item**|=**Description**
86 +|=Input channel|(% style="text-align:center" %)4
87 +|=Digital resolution|(% style="text-align:center" %)16 bit
88 +|=Sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
89 +|=Input terminal|(% style="text-align:center" %)Thermocouple input
90 +|=Sensor type|(% style="text-align:center" %)PT100, PT1000, CU50
91 +|=Accuracy (normal temperature 25℃)|(% style="text-align:center" %)Full range ± 0.2%
92 +|=Accuracy (working temperature -20℃ to 55℃)|(% style="text-align:center" %)Full range ± 0. 3%
93 +|=Isolation or not|(% style="text-align:center" %)I/O terminals are isolated from power supply, channels are not isolated
94 +|=Overlimit disconnection detection|(% style="text-align:center" %)Support
95 +|=Power consumption|(% style="text-align:center" %)< 1.1W
96 +|=Power supply|(% style="text-align:center" %)Power supply via interface, DC24V±10%, 40mA
97 +
98 +== **3.2 Environmental specification** ==
99 +
100 +(% style="margin-left:auto; margin-right:auto" %)
101 +|=**Item**|=(% colspan="5" %)**Specification**
102 +|=Usage environment|(% colspan="5" style="text-align:center" %)No corrosive, combustible gas, no large amount of conductive dust
103 +|=Environment temperature|(% colspan="5" style="text-align:center" %)(((
104 +Working temperature: 0℃ to 55℃
105 +
106 +Storage temperature: -20℃ to 70℃
107 +)))
108 +|=(% style="text-align: center;" %)Environment humidity|(% colspan="5" style="text-align:center" %)(((
109 +Working humidity: 10% to 90%RH (no condensation)
110 +
111 +Storage humidity: ≤ 90% RH (no condensation)
112 +)))
113 +|=Installation|(% colspan="5" style="text-align:center" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
114 +|=(% rowspan="6" %)Vibration resistance|(% colspan="5" style="text-align:center" %)According to JISC0040 standard
115 +|=Installation|(% style="text-align:center" %)Frequency|(% style="text-align:center" %)Acceleration|(% style="text-align:center" %)Amplitude|(% rowspan="5" %)(((
116 +X, Y, Z
117 +
118 +10 times in each of three directions
119 +
120 +(80 minutes in each direction)
121 +)))
122 +|=(% rowspan="2" %)DIN rail installation|(% style="text-align:center" %)10 to 57Hz|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0.035mm
123 +|=(% style="text-align: center;" %)57 to 150Hz|(% style="text-align:center" %)4.9m/S^^2^^|(% style="text-align:center" %)~-~-
124 +|=(% rowspan="2" %)Direct installation|(% style="text-align:center" %)10 to 57Hz|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0.075mm
125 +|=(% style="text-align: center;" %)57 to 150Hz|(% style="text-align:center" %)9.8m/S^^2^^|(% style="text-align:center" %)~-~-
126 +|=Shock resistance|(% colspan="5" %)(((
127 +Compliant with JISC0041 standard
128 +
129 +(147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)
130 +)))
131 +|=EMC immunity level|(% colspan="5" style="text-align:center" %)Zone B (per IEC 61131-2)
132 +|=Altitude requirements|(% colspan="5" style="text-align:center" %)≤2000m (80 kPa)
133 +|=Protection level|(% colspan="5" style="text-align:center" %)IP20
134 +|=Grounding|(% colspan="5" style="text-align:center" %)Not co-located with the strong current system
135 +
136 +== **3.3 Software Specifications** ==
137 +
138 +|(% style="text-align:center" %)**Item**|(% style="text-align:center" %)**Specification**
139 +|(% style="text-align:center" %)Input PDO data volume|(% style="text-align:center" %)Maximum 24 byte
140 +|(% style="text-align:center" %)Diagnostic reporting function configuration|(% style="text-align:center" %)Support
141 +|(% style="text-align:center" %)Diagnostic detection enable configuration|(% style="text-align:center" %)Support overlimit and disconnection detection
142 +|(% style="text-align:center" %)Sensor type configuration|(% style="text-align:center" %)(((
143 +Support thermal resistor type: PT100, PT1000, CU50, default is
144 +
145 +PT100 thermal resistance
146 +)))
147 +|(% style="text-align:center" %)Filter time|(% style="text-align:center" %)0s to 100s (can be configured by software, default 5s)
148 +|(% style="text-align:center" %)Overflow detection|(% style="text-align:center" %)Support
149 +|(% style="text-align:center" %)Overlimit detection enable configuration|(% style="text-align:center" %)Support
150 +|(% style="text-align:center" %)Independent channel configuration|(% style="text-align:center" %)Support
151 +|(% style="text-align:center" %)Temperature offset enable configuration|(% style="text-align:center" %)Support
152 +|(% style="text-align:center" %)Temperature offset configuration range|(% style="text-align:center" %)-300 to +300, temperature unit
153 +|(% style="text-align:center" %)Display mode|(% style="text-align:center" %)Celsius (℃), Fahrenheit (℉)
154 +|(% style="text-align:center" %)Display sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
155 +|(% style="text-align:center" %)Sample refresh|(% style="text-align:center" %)Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
156 +|(% style="text-align:center" %)Stop mode|(% style="text-align:center" %)Output according to the maximum value, no more refresh
157 +|(% style="text-align:center" %)Disconnected or overlimit|(% style="text-align:center" %)Output according to the maximum value, no more refresh
158 +|(% style="text-align:center" %)System diagnostics|(% style="text-align:center" %)System power abnormality
159 +|(% style="text-align:center" %)Channel diagnosis|(% style="text-align:center" %)Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
160 +|(% style="text-align:center" %)Configuration diagnostics|(% style="text-align:center" %)Configuration error identification, channel parameter configuration error
161 +
162 +== **3.4 Accuracy calculation** ==
163 +
164 +Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.
165 +
166 +|(% style="text-align:center" %)**Sensor type**|(% style="text-align:center" %)**Detection range**|(% style="text-align:center" %)**Accuracy**
167 +|(% style="text-align:center" %)PT100|(% style="text-align:center" %)(((
168 +-200.0℃ to +850.0℃,
169 +
170 +-328.0℉ to +1562.0℉
171 +)))|(% style="text-align:center" %)(((
172 +T < 300°C: ±0.6℃
173 +
174 +300℃ ≤ T ≤ 700℃: ±1.4℃
175 +
176 +T > 700°C: ±1.7℃
177 +)))
178 +|(% style="text-align:center" %)PT1000|(% style="text-align:center" %)(((
179 +-200.0℃ to +850.0℃,
180 +
181 +-328.0℉ to +1562.0℉
182 +)))|(% style="text-align:center" %)(((
183 +T < 300°C: ±0.6℃
184 +
185 +300℃ ≤ T ≤ 700℃: ±1.4℃
186 +
187 +T > 700 °C: ±1.7℃
188 +)))
189 +|(% style="text-align:center" %)CU50|(% style="text-align:center" %)(((
190 +-50.0℃ to + 150.0℃,
191 +
192 +-58.0℉ to +302.0℉
193 +)))|(% style="text-align:center" %)-50℃ ≤ T ≤ 150℃: ±0.3℃
194 +
195 += **4 Usage** =
196 +
197 +This module is suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler. The two usage methods are as follow.
198 +
199 +== **4.1 Use on LX6V/LX6S** ==
200 +
201 +(% style="text-align:center" %)
202 +[[image:1761791554402-822.png||height="324" width="537"]]
203 +
204 +**(1 ) Add Module**
205 +
206 +Steps:
207 +
208 +① Double-click the expansion module configuration to open the configuration interface;
209 +
210 +② In the module list, select LX6V-4PT and double-click to add a module;
211 +
212 +③ Double-click the module in the current machine slot to open the parameter configuration interface;
213 +
214 +(% style="text-align:center" %)
215 +[[image:图片1.png]]
216 +
217 +**(2) Configuration module**
218 +
219 +**~ 1) General configuration**
220 +
221 +(% style="text-align:center" %)
222 +[[image:1761790435591-998.jpeg]]
223 +
224 +① Temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;
225 +
226 +② Power frequency suppression: It can eliminate or reduce electromagnetic interference from the power system frequency (50Hz or 60Hz) on electronic equipment, especially signal acquisition systems. The power frequency suppression can be set to the module according to the actual application scenario.
227 +
228 +**~ 2) Channel configuration**
229 +
230 +(% style="text-align:center" %)
231 +[[image:1761790435593-675.jpeg]]
232 +
233 +① Enable channels: It can be set whether to enable the current expansion module channel;
234 +
235 +② Sensor type: Set the sensor type connected to the module channel, the default sensor type is PT100, there are three sensor types supported by the PT module, which are: PT100, PT1000, CU50;
236 +
237 +③ Filtering time: The supported filtering time is 0 to 100s, it is used to reduce fluctuations in channel temperature data. The default filtering time is 5s. Please choose the appropriate filtering time according to the requirements of actual application scenarios for channel output data;
238 +
239 +④ Enable overlimit detection: Channel temperature data overlimit judgment switch, when overlimit detection is enabled, the upper and lower limits of temperature can be set. When the temperature output by the channel is greater than the upper limit of temperature or less than the lower limit of temperature, the state of this channel will output a channel overlimit warning;
240 +
241 +⑤ Enable temperature offset: Channel temperature data offset enable switch. When temperature offset is enabled, the output temperature data of the channel will be offset;
242 +
243 +**~ 3) I/O mapping**
244 +
245 +By default, channels are mapped to R device according to the number of current module channels. The figure below maps modules CH1 ~~ CH12 to R0 ~~ R11 device. The data type of temperature value of channel is REAL. If want to display the temperature value of channel 1, the temperature value can be viewed after assigning a variable using the DEMOV instruction.
246 +
247 +(% style="text-align:center" %)
248 +[[image:1761790435595-524.jpeg||height="638" width="806"]]
249 +
250 +Supported status codes:
251 +
252 +* 0x00: Channel normal;
253 +* 0x40: Channel disconnection;
254 +* 0x41: Channel overflow;
255 +* 0x42: Channel overrun;
256 +
257 +**(3) Download configuration**
258 +
259 +After the module configuration is completed and the program is compiled correctly, the project can be downloaded (at present, it is not supported to download the extension module configuration separately). Before downloading, make sure that the connected expansion module model and configuration model are in the same order. Otherwise, the PLC will report an error and stop running.
260 +
261 +
262 +
263 +== **4.2 Used on LX6V-EM□-ECAT coupler** ==
264 +
265 +(% style="text-align:center" %)
266 +[[image:1761791932607-101.png]]
267 +
268 +
269 +**(1) First  add EtherCAT device**
270 +
271 +According to steps ① to ④ in the figure below, right-click EtherCAT, and click [New]->[Import] to import the ESI device description file of the device;
272 +
273 +[[image:1761790435601-438.jpeg]]
274 +
275 +After the import is completed, select the coupler according to the module model and location connected to PLC. (the figure below takes LX6V-EMB-ECAT as an example);
276 +
277 +[[image:1761790435610-644.jpeg]]
278 +
279 +**(2) Configuration module**
280 +
281 +Right-click the currently added coupler to add the expansion module mounted to the current coupler.
282 +
283 +[[image:1761790435616-427.jpeg]]
284 +
285 +**✎Note: **When the configuration module is inconsistent with the actual mounted module, an error will be reported that the OP cannot be successful.
286 +
287 +**(3) Start configuration**
288 +
289 +[[image:1761790435644-648.jpeg]]
290 +
291 +
292 +[[image:1761790435655-470.jpeg]]
293 +
294 +
295 +① PT module temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;
296 +
297 +0: Degree Celsius (℃);
298 +
299 +Others: Degree Fahrenheit (℉)
300 +
301 +② PT module power frequency support: Set the power frequency suppression of the module to suppress 50Hz or suppress 60Hz, and the default suppression is 50Hz;
302 +
303 +0: Suppress 50 Hz;
304 +
305 +Others: Suppress 60 Hz;
306 +
307 +③ reserve: Reserve
308 +
309 +④ CHx sensor type: Set the type of sensor external to the channel;
310 +
311 +Supported sensor types:
312 +
313 +0: Disable
314 +
315 +1: PT100;
316 +
317 +3: PT1000
318 +
319 +4: CU50;
320 +
321 +⑤ CHx filter time: Used to specify the filtering time of the current channel. The supported filtering time is 0 to 100s, it is used to reduce the fluctuation of channel temperature data. The default filtering time is 5s;
322 +
323 +⑥ CHx over limit detection: Overlimit detection enable configuration, 0: Overlimit detection detection is not enabled, others: Enable overlimit detection
324 +
325 +⑦ CHx temperature upper limit: The upper limit value of the channel overlimit detection temperature;
326 +
327 +⑧ CHx temperature lower limit: The lower limit value of the channel overlimit detection temperature;
328 +
329 +⑨ CHx temperature offset: The offset of channel data, supported offset range:-300 to +300;
330 +
331 +**I/O mapping**
332 +
333 +The temperature and state of the module can be mapped to variables/device. For example, the following figure maps the temperature values of the CH0 to CH3 channels to the D0 to D7 device, and the status codes of the CH0 to CH3 channels to the D8 to D11 device.
334 +
335 +[[image:1761790435666-763.jpeg]]
336 +
337 +Click save configuration and download the configuration to PLC.
338 +
339 += **5 Object dictionary** =
340 +
341 +|(% style="text-align:center; width:77px" %)(((
342 +**Index**
343 +
344 +**(16#)**
345 +)))|(% style="text-align:center; width:142px" %)(((
346 +**Sub-index**
347 +
348 +**(16#)**
349 +)))|(% style="text-align:center; width:288px" %)**Description**|(% style="text-align:center" %)(((
350 +**Data**
351 +
352 +**Type**
353 +)))|(% style="text-align:center" %)**Range**|(% style="text-align:center" %)**Read-write support**|(% style="text-align:center" %)**Unit**|(% style="text-align:center" %)**Default**|(% style="text-align:center" %)**Name**
354 +|(% rowspan="5" style="text-align:center; width:77px" %)8000|(% style="text-align:center; width:142px" %)01|(% style="width:288px" %)(((
355 +PT module temperature unit
356 +
357 +0: Degree Celsius (℃)
358 +
359 +Others: Degrees Fahrenheit (℉)
360 +)))|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)PT module temperature unit
361 +|(% style="text-align:center; width:142px" %)02|(% style="width:288px" %)(((
362 +PT module power frequency suppression
363 +
364 +0: Suppress 50 Hz
365 +
366 +Others: Suppress 60Hz
367 +)))|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)PT module power frequency suppression
368 +|(% style="text-align:center; width:142px" %)03|(% style="width:288px" %)Reserve parameter 0|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 0
369 +|(% style="text-align:center; width:142px" %)04|(% style="width:288px" %)Reserve Parameter 1|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 1
370 +|(% style="text-align:center; width:142px" %)05|(% style="width:288px" %)Reserve parameter 2|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 2
371 +|(% rowspan="4" style="text-align:center; width:77px" %)8001|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
372 +Sensor type
373 +
374 +0: Disable
375 +
376 +1: PT100
377 +
378 +3: PT1000
379 +
380 +4: CU50
381 +
382 +Others: Not supported
383 +)))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 4|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)1|(% style="text-align:center" %)CH0 sensor type
384 +|(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 sensor type
385 +|(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 sensor type
386 +|(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 sensor type
387 +|(% rowspan="4" style="text-align:center; width:77px" %)8002|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
388 +PT module channel filtering time: 0 to 100s
389 +
390 +Others: 100s
391 +)))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 255|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)s|(% rowspan="4" style="text-align:center" %)5|(% style="text-align:center" %)CH0 filter time
392 +|(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 filter time
393 +|(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 filter time
394 +|(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 filter time
395 +|(% rowspan="4" style="text-align:center; width:77px" %)8003|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
396 +Overlimit detection enable
397 +
398 +0: Disable
399 +
400 +Others: Enable
401 +)))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 255|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)0|(% style="text-align:center" %)CH0 overlimit detection
402 +|(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 overlimit detection
403 +|(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 overlimit detection
404 +|(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 overlimit detection
405 +|(% rowspan="4" style="text-align:center; width:77px" %)8004|(% style="text-align:center; width:142px" %)01|(% rowspan="8" style="width:288px" %)(((
406 +Temperature unit: 0.1℃/0.1℉
407 +
408 +The upper and lower limits of sensors are different for each model
409 +)))|(% rowspan="4" style="text-align:center" %)INT32|(% rowspan="4" style="text-align:center" %)-32768 to 40000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)32767|(% style="text-align:center" %)CH0 temperature upper limit
410 +|(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature upper limit
411 +|(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 temperature upper limit
412 +|(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature upper limit
413 +|(% rowspan="4" style="text-align:center; width:77px" %)8005|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="text-align:center" %)INT32|(% rowspan="4" style="text-align:center" %)-32768 to 40000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)-32768|(% style="text-align:center" %)CH0 temperature lower limit
414 +|(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature lower limit
415 +|(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH1 temperature lower limit
416 +|(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature lower limit
417 +|(% rowspan="4" style="text-align:center; width:77px" %)8006|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
418 +Offset temperature value (0.1℃/0.1 ℉)
419 +
420 +0: No offset
421 +
422 +
423 +)))|(% rowspan="4" style="text-align:center" %)INT16|(% rowspan="4" style="text-align:center" %)-3000 to 3000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)0|(% style="text-align:center" %)CH0 temperature offset
424 +|(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature offset
425 +|(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 temperature offset
426 +|(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature offset
427 +|(% rowspan="3" style="text-align:center; width:77px" %)A000|(% style="text-align:center; width:142px" %)00|(% style="width:288px" %)Module status information|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Module status
428 +|(% style="text-align:center; width:142px" %)01|(% style="width:288px" %)Version code|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Version
429 +|(% style="text-align:center; width:142px" %)02|(% style="width:288px" %)Error status|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Run status
430 +|(% rowspan="4" style="text-align:center; width:77px" %)6000|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
431 +PT CH0 to CH3 channel current temperature value (℃/℉)
432 +
433 +
434 +)))|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH0 temperature
435 +|(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH1 temperature
436 +|(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH2 temperature
437 +|(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH3 temperature
438 +|(% rowspan="4" style="text-align:center; width:77px" %)6001|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
439 +PT CH0 to CH3 status code
440 +
441 +0, no error
442 +
443 +0xFF, sensor not supported
444 +
445 +0x10, configuration error: Temperature overlimit configuration
446 +
447 +0x11, configuration error: The upper limit of the overlimit configuration is less than the lower limit
448 +
449 +0x12, configuration error: Temperature offset configuration temperature overlimit
450 +
451 +0x13, configuration error: NTC B value overlimit
452 +
453 +0x40, channel disconnection error
454 +
455 +0x41, channel temperature overflow
456 +
457 +0x42, channel temperature overlimit
458 +)))|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH0 status
459 +|(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH1 status
460 +|(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH2 status
461 +|(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH3 status
462 +
463 += **6 Error code** =
464 +
465 +|(% style="text-align:center" %)**Error code**|(% style="text-align:center; width:354px" %)**Description**|(% style="text-align:center; width:153px" %)**Action**|(% style="text-align:center; width:366px" %)**Solution**|(% style="text-align:center; width:161px" %)**Detect time**
466 +|(% style="text-align:center" %)7080|(% style="width:354px" %)Expansion module and checksum error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect whether there is external interference between the expansion module and the PLC.|(% style="text-align:center; width:161px" %)Instruction running
467 +|(% style="text-align:center" %)7081|(% style="width:354px" %)Expansion module communication message error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect whether there is external interference between the expansion module and the PLC.|(% style="text-align:center; width:161px" %)Instruction running
468 +|(% style="text-align:center" %)7083|(% style="width:354px" %)Expansion module access error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect the link between the expansion module and the host|(% style="text-align:center; width:161px" %)Instruction running
469 +|(% style="text-align:center" %)7084|(% style="width:354px" %)The number of expansion modules configured does not match the actual number|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Check whether the configuration is correct.|(% style="text-align:center; width:161px" %)Instruction running
470 +|(% style="text-align:center" %)7110|(% style="width:354px" %)Extension module configuration error|(% style="text-align:center; width:153px" %)Stop running|(% style="width:366px" %)Check that the extension module is configured correctly|(% style="text-align:center; width:161px" %)Instruction running
471 +
472 += **7 Version record** =
473 +
474 +|(% colspan="3" style="text-align:center" %)Current version: REV1.0
475 +|(% style="text-align:center" %)**Version code**|(% style="text-align:center" %)**Modify content**|(% style="text-align:center" %)**Date**
476 +|(% style="text-align:center" %)REV1.0|(% style="text-align:center" %)The first release|(% style="text-align:center" %)22 October 2025
477 +
478 +
1761790435458-276.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +2.5 MB
Content
1761790435527-310.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +2.5 MB
Content
1761790435581-926.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +500.0 KB
Content
1761790435591-998.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +26.3 KB
Content
1761790435593-675.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +68.8 KB
Content
1761790435595-524.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +56.7 KB
Content
1761790435597-964.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +147.2 KB
Content
1761790435601-438.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +545.2 KB
Content
1761790435610-644.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +93.1 KB
Content
1761790435616-427.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +706.6 KB
Content
1761790435644-648.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +630.2 KB
Content
1761790435655-470.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +678.3 KB
Content
1761790435666-763.jpeg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +153.3 KB
Content
1761790581619-130.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +565.4 KB
Content
1761790728530-525.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +47.3 KB
Content
1761790839326-892.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +126.8 KB
Content
1761790846633-145.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +169.4 KB
Content
1761790902574-569.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +581.1 KB
Content
1761791554402-822.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +491.0 KB
Content
1761791932607-101.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +601.9 KB
Content
1761792561604-505.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +977.1 KB
Content
1761792587489-425.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +977.1 KB
Content
1761792704532-635.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +299.8 KB
Content
1761792792216-675.jpeg
Author
... ... @@ -1,0 +1,1 @@