... ... @@ -3,7 +3,7 @@
3 3  (% style="text-align:center" %)
4 4  [[image:1761790581619-130.png||height="397" width="397"]]
5 5  
6 -LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
6 +LX6V-4PT (4-channal analog inputs), used for the acquisition of resistance temperature detector input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
7 7  
8 8  LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
9 9  
... ... @@ -47,8 +47,14 @@
47 47  (% style="text-align:center" %)
48 48  [[image:图片7.png||height="303" width="577"]]
49 49  
50 -== **2.4 Indicator** ==
50 +== **2.4** **Wiring instruction diagram** ==
51 51  
52 +When using the 4PT expansion module, the wiring method of the sensor is as shown in the following diagrams:
53 +
54 +[[image:1768207221500-618.png]]
55 +
56 +== **2.5 Indicator** ==
57 +
52 52  The 4PT expansion module LED is shown below:
53 53  
54 54  (% style="margin-left:auto; margin-right:auto" %)
... ... @@ -85,12 +85,12 @@
85 85  |=Input channel|(% style="text-align:center" %)4
86 86  |=Digital resolution|(% style="text-align:center" %)16 bit
87 87  |=Sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
88 -|=Input terminal|(% style="text-align:center" %)Thermocouple input
94 +|=Input terminal|(% style="text-align:center" %)Resistance temperature detector input
89 89  |=Sensor type|(% style="text-align:center" %)PT100, PT1000, CU50
90 90  |=Accuracy (normal temperature 25℃)|(% style="text-align:center" %)Full range ± 0.2%
91 91  |=Accuracy (working temperature -20℃ to 55℃)|(% style="text-align:center" %)Full range ± 0. 3%
92 92  |=Isolation or not|(% style="text-align:center" %)I/O terminals are isolated from power supply, channels are not isolated
93 -|=Overlimit disconnection detection|(% style="text-align:center" %)Support
99 +|=Overlimit and disconnection detection|(% style="text-align:center" %)Support
94 94  |=Power consumption|(% style="text-align:center" %)< 1.1W
95 95  |=Power supply|(% style="text-align:center" %)Power supply via interface, DC24V±10%, 40mA
96 96  
... ... @@ -198,7 +198,7 @@
198 198  == **4.1 Use on LX6V/LX6S** ==
199 199  
200 200  (% style="text-align:center" %)
201 -[[image:图片8.png]]
207 +[[image:图片8.png||height="381" width="632"]]
202 202  
203 203  **(1 ) Add Module**
204 204  
... ... @@ -477,6 +477,7 @@
477 477  
478 478  |(% colspan="3" style="text-align:center" %)Current version: REV1.0
479 479  |(% style="text-align:center" %)**Version code**|(% style="text-align:center" %)**Modify content**|(% style="text-align:center" %)**Date**
480 -|(% style="text-align:center" %)REV1.0|(% style="text-align:center" %)The first release|(% style="text-align:center" %)22 October 2025
486 +|(% style="text-align:center" %)REV1.1|(% style="text-align:center" %)New wiring diagram|(% style="text-align:center" %)December 29, 2025
487 +|(% style="text-align:center" %)REV1.0|(% style="text-align:center" %)The first release|(% style="text-align:center" %)October 22, 2025
481 481  
482 482  
123.wmf
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +81.9 KB
Content
1768207221500-618.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +59.1 KB
Content