... ... @@ -3,7 +3,7 @@
3 3  (% style="text-align:center" %)
4 4  [[image:1761790581619-130.png||height="397" width="397"]]
5 5  
6 -LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
6 +LX6V-4PT (4-channal analog inputs), used for the acquisition of resistance temperature detector input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
7 7  
8 8  LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
9 9  
... ... @@ -51,10 +51,9 @@
51 51  
52 52  When using the 4PT expansion module, the wiring method of the sensor is as shown in the following diagrams:
53 53  
54 -(% style="text-align:center" %)
55 -[[image:123.wmf]]
54 +[[image:1768207221500-618.png]]
56 56  
57 -== **2.4 Indicator** ==
56 +== **2.5 Indicator** ==
58 58  
59 59  The 4PT expansion module LED is shown below:
60 60  
... ... @@ -92,12 +92,12 @@
92 92  |=Input channel|(% style="text-align:center" %)4
93 93  |=Digital resolution|(% style="text-align:center" %)16 bit
94 94  |=Sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
95 -|=Input terminal|(% style="text-align:center" %)Thermocouple input
94 +|=Input terminal|(% style="text-align:center" %)Resistance temperature detector input
96 96  |=Sensor type|(% style="text-align:center" %)PT100, PT1000, CU50
97 97  |=Accuracy (normal temperature 25℃)|(% style="text-align:center" %)Full range ± 0.2%
98 98  |=Accuracy (working temperature -20℃ to 55℃)|(% style="text-align:center" %)Full range ± 0. 3%
99 99  |=Isolation or not|(% style="text-align:center" %)I/O terminals are isolated from power supply, channels are not isolated
100 -|=Overlimit disconnection detection|(% style="text-align:center" %)Support
99 +|=Overlimit and disconnection detection|(% style="text-align:center" %)Support
101 101  |=Power consumption|(% style="text-align:center" %)< 1.1W
102 102  |=Power supply|(% style="text-align:center" %)Power supply via interface, DC24V±10%, 40mA
103 103  
... ... @@ -205,7 +205,7 @@
205 205  == **4.1 Use on LX6V/LX6S** ==
206 206  
207 207  (% style="text-align:center" %)
208 -[[image:图片8.png]]
207 +[[image:图片8.png||height="381" width="632"]]
209 209  
210 210  **(1 ) Add Module**
211 211  
... ... @@ -484,6 +484,7 @@
484 484  
485 485  |(% colspan="3" style="text-align:center" %)Current version: REV1.0
486 486  |(% style="text-align:center" %)**Version code**|(% style="text-align:center" %)**Modify content**|(% style="text-align:center" %)**Date**
487 -|(% style="text-align:center" %)REV1.0|(% style="text-align:center" %)The first release|(% style="text-align:center" %)22 October 2025
486 +|(% style="text-align:center" %)REV1.1|(% style="text-align:center" %)New wiring diagram|(% style="text-align:center" %)December 29, 2025
487 +|(% style="text-align:center" %)REV1.0|(% style="text-align:center" %)The first release|(% style="text-align:center" %)October 22, 2025
488 488  
489 489  
1768207221500-618.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Iris
Size
... ... @@ -1,0 +1,1 @@
1 +59.1 KB
Content