Changes for page LX6V-4PT

Last modified by Iris on 2026/03/24 15:34

From version 4.1
edited by Iris
on 2025/10/30 10:04
Change comment: There is no comment for this version
To version 1.1
edited by Iris
on 2025/10/30 10:02
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -1,194 +1,0 @@
1 -= **Introduction** =
2 -
3 -
4 -
5 -LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
6 -
7 -LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
8 -
9 -Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.
10 -
11 -
12 -**✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.
13 -
14 -1. **Appearance and terminal description**
15 -11. **Appearance and size**
16 -
17 -
18 -
19 -[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps5.png]]
20 -
21 -① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5);
22 -
23 -⑤ DIN rail buckle.
24 -
25 -
26 -1.
27 -11. **Terminal description**
28 -
29 -The 4PT expansion module terminal are arranged as follows:
30 -
31 -
32 -|**Module model**|(% colspan="2" %)**Terminal arrangement**
33 -|LX6V-4PT| |[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps7.png]]
34 -
35 -
36 -
37 -1.
38 -11. **Installation**
39 -
40 -Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:
41 -
42 -[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml8120\wps8.png]]
43 -
44 -
45 -1.
46 -11. **Indicator**
47 -
48 -The 4PT expansion module LED is shown below:
49 -
50 -|**Indicator**|**Description**
51 -|PWR|(((
52 -Power indicator
53 -
54 -1. Lights on: The module is powered on normally
55 -1. Lights out: The module is not powered on or the module is abnormal
56 -)))
57 -|LINK|(((
58 -Communication indicator
59 -
60 -1. Lights on: Data interaction is normal
61 -1. Lights out: Data interaction is abnormal or stopped
62 -)))
63 -|L1+/L2+/L3+/L4 +|(((
64 -Channel indicator
65 -
66 -1. Lights on: Channel enable
67 -1. Lights out: Channel disable
68 -1. Slow flash: Channel not calibrated
69 -1. Fast flash: Channel abnormal (refer to status code for details)
70 -)))
71 -|L1-/L2-/L3-/L4-|N/A
72 -|I1+/I2+/I3+/I4 +|N/A
73 -
74 -
75 -
76 -
77 -1. **Parameter Specification**
78 -11. **Input Specification**
79 -
80 -|**Item**|**Description**
81 -|Input channel|4
82 -|Digital resolution|16 bit
83 -|Sensitivity|0.01℃, 0.01℉
84 -|Input terminal|Thermocouple input
85 -|Sensor type|PT100, PT1000, CU50
86 -|Accuracy (normal temperature 25℃)|Full range ± 0.2%
87 -|Accuracy (working temperature -20℃ to 55℃)|Full range ± 0. 3%
88 -|Isolation or not|I/O terminals are isolated from power supply, channels are not isolated
89 -|Overlimit disconnection detection|Support
90 -|Power consumption|< 1.1W
91 -|Power supply|Power supply via interface, DC24V±10%, 40mA
92 -
93 -
94 -
95 -1.
96 -11. **Environmental specification**
97 -11.
98 -**Software Specifications**
99 -
100 -|**Item**|(% colspan="5" %)**Specification**
101 -|Usage environment|(% colspan="5" %)No corrosive, combustible gas, no large amount of conductive dust
102 -|Environment temperature|(% colspan="5" %)(((
103 -Working temperature: 0℃ to 55℃
104 -
105 -Storage temperature: -20℃ to 70℃
106 -)))
107 -|Environment humidity|(% colspan="5" %)(((
108 -Working humidity: 10% to 90%RH (no condensation)
109 -
110 -Storage humidity: ≤ 90% RH (no condensation)
111 -)))
112 -|Installation|(% colspan="5" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
113 -|(% rowspan="6" %)Vibration resistance|(% colspan="5" %)According to JISC0040 standard
114 -|Installation|Frequency|Acceleration|Amplitude|(% rowspan="5" %)(((
115 -X, Y, Z
116 -
117 -10 times in each of three directions
118 -
119 -(80 minutes in each direction)
120 -)))
121 -|(% rowspan="2" %)DIN rail installation|10 to 57Hz|~-~-|0.035mm
122 -|57 to 150Hz|4.9m/S^^2^^|~-~-
123 -|(% rowspan="2" %)Direct installation|10 to 57Hz|~-~-|0.075mm
124 -|57 to 150Hz|9.8m/S^^2^^|~-~-
125 -|Shock resistance|(% colspan="5" %)(((
126 -Compliant with JISC0041 standard
127 -
128 -(147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)
129 -)))
130 -|EMC immunity level|(% colspan="5" %)Zone B (per IEC 61131-2)
131 -|Altitude requirements|(% colspan="5" %)≤2000m (80 kPa)
132 -|Protection level|(% colspan="5" %)IP20
133 -|Grounding|(% colspan="5" %)Not co-located with the strong current system
134 -
135 -|**Item**|**Specification**
136 -|Input PDO data volume|Maximum 24 byte
137 -|Diagnostic reporting function configuration|Support
138 -|Diagnostic detection enable configuration|Support overlimit and disconnection detection
139 -|Sensor type configuration|(((
140 -Support thermal resistor type: PT100, PT1000, CU50, default is
141 -
142 -PT100 thermal resistance
143 -)))
144 -|Filter time|0s to 100s (can be configured by software, default 5s)
145 -|Overflow detection|Support
146 -|Overlimit detection enable configuration|Support
147 -|Independent channel configuration|Support
148 -|Temperature offset enable configuration|Support
149 -|Temperature offset configuration range|-300 to +300, temperature unit
150 -|Display mode|Celsius (℃), Fahrenheit (℉)
151 -|Display sensitivity|0.01℃, 0.01℉
152 -|Sample refresh|Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
153 -|Stop mode|Output according to the maximum value, no more refresh
154 -|Disconnected or overlimit|Output according to the maximum value, no more refresh
155 -|System diagnostics|System power abnormality
156 -|Channel diagnosis|Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
157 -|Configuration diagnostics|Configuration error identification, channel parameter configuration error
158 -
159 -
160 -
161 -
162 -1.
163 -11. **Accuracy calculation**
164 -
165 -Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.
166 -
167 -|**Sensor type**|**Detection range**|**Accuracy**
168 -|PT100|(((
169 --200.0℃ to +850.0℃,
170 -
171 --328.0℉ to +1562.0℉
172 -)))|(((
173 -T < 300°C: ±0.6℃
174 -
175 -300℃ ≤ T ≤ 700℃: ±1.4℃
176 -
177 -T > 700°C: ±1.7℃
178 -)))
179 -|PT1000|(((
180 --200.0℃ to +850.0℃,
181 -
182 --328.0℉ to +1562.0℉
183 -)))|(((
184 -T < 300°C: ±0.6℃
185 -
186 -300℃ ≤ T ≤ 700℃: ±1.4℃
187 -
188 -T > 700 °C: ±1.7℃
189 -)))
190 -|CU50|(((
191 --50.0℃ to + 150.0℃,
192 -
193 --58.0℉ to +302.0℉
194 -)))|-50℃ ≤ T ≤ 150℃: ±0.3℃