Wiki source code of LX6V-4PT

Version 12.1 by Iris on 2026/01/12 16:39

Hide last authors
Iris 6.1 1 = **1 Introduction** =
Iris 2.1 2
Iris 6.1 3 (% style="text-align:center" %)
Iris 7.1 4 [[image:1761790581619-130.png||height="397" width="397"]]
Iris 2.1 5
6 LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
7
8 LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
9
10 Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.
11
12 **✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.
13
Iris 6.1 14 = **2 Appearance and terminal description** =
Iris 2.1 15
Iris 6.1 16 == **2.1 ​​​​​Appearance and size** ==
Iris 2.1 17
Iris 6.1 18 (% style="text-align:center" %)
19 [[image:1761790728530-525.png]]
Iris 2.1 20
Iris 6.1 21 ① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5); ⑤ DIN rail buckle.
Iris 2.1 22
Iris 6.1 23 == **2.2 Terminal description** ==
Iris 2.1 24
25 The 4PT expansion module terminal are arranged as follows:
26
Iris 6.1 27 (% style="margin-left:auto; margin-right:auto" %)
28 |=(((
29 **Module model**
30 )))|=(% colspan="2" rowspan="1" %)(((
31 **Terminal arrangement**
32 )))
33 |=(((
34 LX6V-4PT
35 )))|(((
36 (% style="text-align:center" %)
37 [[image:1761790846633-145.png]]
38 )))|(((
39 (% style="text-align:center" %)
40 [[image:1761790839326-892.png]]
41 )))
Iris 2.1 42
Iris 6.1 43 == **2.3** **Installation** ==
Iris 2.1 44
45 Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:
46
Iris 6.1 47 (% style="text-align:center" %)
Iris 9.1 48 [[image:图片7.png||height="303" width="577"]]
Iris 2.1 49
Iris 12.1 50 == **2.4** **Wiring instruction diagram** ==
51
52 When using the 4PT expansion module, the wiring method of the sensor is as shown in the following diagrams:
53
54 (% style="text-align:center" %)
55 [[image:123.wmf]]
56
Iris 6.1 57 == **2.4 Indicator** ==
Iris 2.1 58
59 The 4PT expansion module LED is shown below:
60
Iris 6.1 61 (% style="margin-left:auto; margin-right:auto" %)
62 |=**Indicator**|=**Description**
63 |=PWR|(((
Iris 2.1 64 Power indicator
65
66 1. Lights on: The module is powered on normally
67 1. Lights out: The module is not powered on or the module is abnormal
68 )))
Iris 6.1 69 |=LINK|(((
Iris 2.1 70 Communication indicator
71
72 1. Lights on: Data interaction is normal
73 1. Lights out: Data interaction is abnormal or stopped
74 )))
Iris 6.1 75 |=L1+/L2+/L3+/L4 +|(((
Iris 2.1 76 Channel indicator
77
78 1. Lights on: Channel enable
79 1. Lights out: Channel disable
80 1. Slow flash: Channel not calibrated
81 1. Fast flash: Channel abnormal (refer to status code for details)
82 )))
Iris 6.1 83 |=L1-/L2-/L3-/L4-|(% style="text-align:center" %)N/A
84 |=I1+/I2+/I3+/I4 +|(% style="text-align:center" %)N/A
Iris 2.1 85
Iris 11.1 86 = **3 Parameter Specification** =
Iris 2.1 87
Iris 10.1 88 == **3.1 Input Specification** ==
Iris 2.1 89
Iris 6.1 90 (% style="margin-left:auto; margin-right:auto" %)
91 |=**Item**|=**Description**
92 |=Input channel|(% style="text-align:center" %)4
93 |=Digital resolution|(% style="text-align:center" %)16 bit
94 |=Sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
95 |=Input terminal|(% style="text-align:center" %)Thermocouple input
96 |=Sensor type|(% style="text-align:center" %)PT100, PT1000, CU50
97 |=Accuracy (normal temperature 25℃)|(% style="text-align:center" %)Full range ± 0.2%
98 |=Accuracy (working temperature -20℃ to 55℃)|(% style="text-align:center" %)Full range ± 0. 3%
99 |=Isolation or not|(% style="text-align:center" %)I/O terminals are isolated from power supply, channels are not isolated
100 |=Overlimit disconnection detection|(% style="text-align:center" %)Support
101 |=Power consumption|(% style="text-align:center" %)< 1.1W
102 |=Power supply|(% style="text-align:center" %)Power supply via interface, DC24V±10%, 40mA
Iris 2.1 103
Iris 6.1 104 == **3.2 Environmental specification** ==
Iris 2.1 105
Iris 6.1 106 (% style="margin-left:auto; margin-right:auto" %)
107 |=**Item**|=(% colspan="5" %)**Specification**
108 |=Usage environment|(% colspan="5" style="text-align:center" %)No corrosive, combustible gas, no large amount of conductive dust
109 |=Environment temperature|(% colspan="5" style="text-align:center" %)(((
Iris 2.1 110 Working temperature: 0℃ to 55℃
111
112 Storage temperature: -20℃ to 70℃
113 )))
Iris 6.1 114 |=(% style="text-align: center;" %)Environment humidity|(% colspan="5" style="text-align:center" %)(((
Iris 2.1 115 Working humidity: 10% to 90%RH (no condensation)
116
117 Storage humidity: ≤ 90% RH (no condensation)
118 )))
Iris 6.1 119 |=Installation|(% colspan="5" style="text-align:center" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
120 |=(% rowspan="6" %)Vibration resistance|(% colspan="5" style="text-align:center" %)According to JISC0040 standard
121 |=Installation|(% style="text-align:center" %)Frequency|(% style="text-align:center" %)Acceleration|(% style="text-align:center" %)Amplitude|(% rowspan="5" %)(((
Iris 2.1 122 X, Y, Z
123
124 10 times in each of three directions
125
126 (80 minutes in each direction)
127 )))
Iris 6.1 128 |=(% rowspan="2" %)DIN rail installation|(% style="text-align:center" %)10 to 57Hz|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0.035mm
129 |=(% style="text-align: center;" %)57 to 150Hz|(% style="text-align:center" %)4.9m/S^^2^^|(% style="text-align:center" %)~-~-
130 |=(% rowspan="2" %)Direct installation|(% style="text-align:center" %)10 to 57Hz|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0.075mm
131 |=(% style="text-align: center;" %)57 to 150Hz|(% style="text-align:center" %)9.8m/S^^2^^|(% style="text-align:center" %)~-~-
132 |=Shock resistance|(% colspan="5" %)(((
Iris 2.1 133 Compliant with JISC0041 standard
134
135 (147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)
136 )))
Iris 6.1 137 |=EMC immunity level|(% colspan="5" style="text-align:center" %)Zone B (per IEC 61131-2)
138 |=Altitude requirements|(% colspan="5" style="text-align:center" %)≤2000m (80 kPa)
139 |=Protection level|(% colspan="5" style="text-align:center" %)IP20
140 |=Grounding|(% colspan="5" style="text-align:center" %)Not co-located with the strong current system
Iris 2.1 141
Iris 6.1 142 == **3.3 Software Specifications** ==
143
144 |(% style="text-align:center" %)**Item**|(% style="text-align:center" %)**Specification**
145 |(% style="text-align:center" %)Input PDO data volume|(% style="text-align:center" %)Maximum 24 byte
146 |(% style="text-align:center" %)Diagnostic reporting function configuration|(% style="text-align:center" %)Support
147 |(% style="text-align:center" %)Diagnostic detection enable configuration|(% style="text-align:center" %)Support overlimit and disconnection detection
148 |(% style="text-align:center" %)Sensor type configuration|(% style="text-align:center" %)(((
Iris 2.1 149 Support thermal resistor type: PT100, PT1000, CU50, default is
150
151 PT100 thermal resistance
152 )))
Iris 6.1 153 |(% style="text-align:center" %)Filter time|(% style="text-align:center" %)0s to 100s (can be configured by software, default 5s)
154 |(% style="text-align:center" %)Overflow detection|(% style="text-align:center" %)Support
155 |(% style="text-align:center" %)Overlimit detection enable configuration|(% style="text-align:center" %)Support
156 |(% style="text-align:center" %)Independent channel configuration|(% style="text-align:center" %)Support
157 |(% style="text-align:center" %)Temperature offset enable configuration|(% style="text-align:center" %)Support
158 |(% style="text-align:center" %)Temperature offset configuration range|(% style="text-align:center" %)-300 to +300, temperature unit
159 |(% style="text-align:center" %)Display mode|(% style="text-align:center" %)Celsius (℃), Fahrenheit (℉)
160 |(% style="text-align:center" %)Display sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
161 |(% style="text-align:center" %)Sample refresh|(% style="text-align:center" %)Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
162 |(% style="text-align:center" %)Stop mode|(% style="text-align:center" %)Output according to the maximum value, no more refresh
163 |(% style="text-align:center" %)Disconnected or overlimit|(% style="text-align:center" %)Output according to the maximum value, no more refresh
164 |(% style="text-align:center" %)System diagnostics|(% style="text-align:center" %)System power abnormality
165 |(% style="text-align:center" %)Channel diagnosis|(% style="text-align:center" %)Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
166 |(% style="text-align:center" %)Configuration diagnostics|(% style="text-align:center" %)Configuration error identification, channel parameter configuration error
Iris 2.1 167
Iris 8.1 168 == **3.4 Accuracy calculation** ==
Iris 2.1 169
170 Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.
171
Iris 6.1 172 |(% style="text-align:center" %)**Sensor type**|(% style="text-align:center" %)**Detection range**|(% style="text-align:center" %)**Accuracy**
173 |(% style="text-align:center" %)PT100|(% style="text-align:center" %)(((
Iris 2.1 174 -200.0℃ to +850.0℃,
175
176 -328.0℉ to +1562.0℉
Iris 6.1 177 )))|(% style="text-align:center" %)(((
Iris 2.1 178 T < 300°C: ±0.6℃
179
180 300℃ ≤ T ≤ 700℃: ±1.4℃
181
182 T > 700°C: ±1.7℃
183 )))
Iris 6.1 184 |(% style="text-align:center" %)PT1000|(% style="text-align:center" %)(((
Iris 2.1 185 -200.0℃ to +850.0℃,
186
187 -328.0℉ to +1562.0℉
Iris 6.1 188 )))|(% style="text-align:center" %)(((
Iris 2.1 189 T < 300°C: ±0.6℃
190
191 300℃ ≤ T ≤ 700℃: ±1.4℃
192
193 T > 700 °C: ±1.7℃
194 )))
Iris 6.1 195 |(% style="text-align:center" %)CU50|(% style="text-align:center" %)(((
Iris 2.1 196 -50.0℃ to + 150.0℃,
197
198 -58.0℉ to +302.0℉
Iris 6.1 199 )))|(% style="text-align:center" %)-50℃ ≤ T ≤ 150℃: ±0.3℃
Iris 5.1 200
Iris 6.1 201 = **4 Usage** =
Iris 5.1 202
Iris 6.1 203 This module is suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler. The two usage methods are as follow.
Iris 5.1 204
Iris 8.1 205 == **4.1 Use on LX6V/LX6S** ==
Iris 5.1 206
Iris 6.1 207 (% style="text-align:center" %)
Iris 9.1 208 [[image:图片8.png]]
Iris 5.1 209
Iris 6.1 210 **(1 ) Add Module**
Iris 5.1 211
212 Steps:
213
214 ① Double-click the expansion module configuration to open the configuration interface;
215
216 ② In the module list, select LX6V-4PT and double-click to add a module;
217
218 ③ Double-click the module in the current machine slot to open the parameter configuration interface;
219
Iris 6.1 220 (% style="text-align:center" %)
Iris 8.1 221 [[image:图片1.png]]
Iris 5.1 222
Iris 6.1 223 **(2) Configuration module**
Iris 5.1 224
Iris 6.1 225 **~ 1) General configuration**
Iris 5.1 226
Iris 8.1 227 (% style="text-align:center" %)
Iris 5.1 228 [[image:1761790435591-998.jpeg]]
229
230 ① Temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;
231
232 ② Power frequency suppression: It can eliminate or reduce electromagnetic interference from the power system frequency (50Hz or 60Hz) on electronic equipment, especially signal acquisition systems. The power frequency suppression can be set to the module according to the actual application scenario.
233
Iris 6.1 234 **~ 2) Channel configuration**
Iris 5.1 235
Iris 8.1 236 (% style="text-align:center" %)
Iris 5.1 237 [[image:1761790435593-675.jpeg]]
238
239 ① Enable channels: It can be set whether to enable the current expansion module channel;
240
241 ② Sensor type: Set the sensor type connected to the module channel, the default sensor type is PT100, there are three sensor types supported by the PT module, which are: PT100, PT1000, CU50;
242
243 ③ Filtering time: The supported filtering time is 0 to 100s, it is used to reduce fluctuations in channel temperature data. The default filtering time is 5s. Please choose the appropriate filtering time according to the requirements of actual application scenarios for channel output data;
244
245 ④ Enable overlimit detection: Channel temperature data overlimit judgment switch, when overlimit detection is enabled, the upper and lower limits of temperature can be set. When the temperature output by the channel is greater than the upper limit of temperature or less than the lower limit of temperature, the state of this channel will output a channel overlimit warning;
246
247 ⑤ Enable temperature offset: Channel temperature data offset enable switch. When temperature offset is enabled, the output temperature data of the channel will be offset;
248
Iris 6.1 249 **~ 3) I/O mapping**
Iris 5.1 250
251 By default, channels are mapped to R device according to the number of current module channels. The figure below maps modules CH1 ~~ CH12 to R0 ~~ R11 device. The data type of temperature value of channel is REAL. If want to display the temperature value of channel 1, the temperature value can be viewed after assigning a variable using the DEMOV instruction.
252
Iris 8.1 253 (% style="text-align:center" %)
254 [[image:1761790435595-524.jpeg||height="638" width="806"]]
Iris 5.1 255
256 Supported status codes:
257
Iris 6.1 258 * 0x00: Channel normal;
259 * 0x40: Channel disconnection;
260 * 0x41: Channel overflow;
261 * 0x42: Channel overrun;
Iris 5.1 262
Iris 6.1 263 **(3) Download configuration**
Iris 5.1 264
265 After the module configuration is completed and the program is compiled correctly, the project can be downloaded (at present, it is not supported to download the extension module configuration separately). Before downloading, make sure that the connected expansion module model and configuration model are in the same order. Otherwise, the PLC will report an error and stop running.
266
Iris 9.1 267 (% style="text-align:center" %)
268 [[image:图片2.png]]
Iris 5.1 269
Iris 8.1 270 == **4.2 Used on LX6V-EM□-ECAT coupler** ==
271
Iris 6.1 272 (% style="text-align:center" %)
273 [[image:1761791932607-101.png]]
Iris 5.1 274
Iris 6.1 275 **(1) First  add EtherCAT device**
Iris 5.1 276
277 According to steps ① to ④ in the figure below, right-click EtherCAT, and click [New]->[Import] to import the ESI device description file of the device;
278
Iris 9.1 279 (% style="text-align:center" %)
280 [[image:图片3.png]]
Iris 5.1 281
282 After the import is completed, select the coupler according to the module model and location connected to PLC. (the figure below takes LX6V-EMB-ECAT as an example);
283
Iris 9.1 284 (% style="text-align:center" %)
Iris 5.1 285 [[image:1761790435610-644.jpeg]]
286
Iris 6.1 287 **(2) Configuration module**
Iris 5.1 288
289 Right-click the currently added coupler to add the expansion module mounted to the current coupler.
290
Iris 9.1 291 (% style="text-align:center" %)
292 [[image:图片4.png]]
Iris 5.1 293
294 **✎Note: **When the configuration module is inconsistent with the actual mounted module, an error will be reported that the OP cannot be successful.
295
Iris 6.1 296 **(3) Start configuration**
Iris 5.1 297
Iris 9.1 298 (% style="text-align:center" %)
299 [[image:图片5.png||alt="1761790435644-648.jpeg"]]
Iris 5.1 300
301
Iris 9.1 302 (% style="text-align:center" %)
303 [[image:图片6.png]]
Iris 5.1 304
305 ① PT module temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;
306
307 0: Degree Celsius (℃);
308
309 Others: Degree Fahrenheit (℉)
310
311 ② PT module power frequency support: Set the power frequency suppression of the module to suppress 50Hz or suppress 60Hz, and the default suppression is 50Hz;
312
313 0: Suppress 50 Hz;
314
315 Others: Suppress 60 Hz;
316
317 ③ reserve: Reserve
318
319 ④ CHx sensor type: Set the type of sensor external to the channel;
320
321 Supported sensor types:
322
323 0: Disable
324
325 1: PT100;
326
327 3: PT1000
328
329 4: CU50;
330
331 ⑤ CHx filter time: Used to specify the filtering time of the current channel. The supported filtering time is 0 to 100s, it is used to reduce the fluctuation of channel temperature data. The default filtering time is 5s;
332
333 ⑥ CHx over limit detection: Overlimit detection enable configuration, 0: Overlimit detection detection is not enabled, others: Enable overlimit detection
334
335 ⑦ CHx temperature upper limit: The upper limit value of the channel overlimit detection temperature;
336
337 ⑧ CHx temperature lower limit: The lower limit value of the channel overlimit detection temperature;
338
339 ⑨ CHx temperature offset: The offset of channel data, supported offset range:-300 to +300;
340
341 **I/O mapping**
342
343 The temperature and state of the module can be mapped to variables/device. For example, the following figure maps the temperature values of the CH0 to CH3 channels to the D0 to D7 device, and the status codes of the CH0 to CH3 channels to the D8 to D11 device.
344
Iris 9.1 345 (% style="text-align:center" %)
Iris 5.1 346 [[image:1761790435666-763.jpeg]]
347
348 Click save configuration and download the configuration to PLC.
349
Iris 6.1 350 = **5 Object dictionary** =
Iris 5.1 351
Iris 6.1 352 |(% style="text-align:center; width:77px" %)(((
Iris 5.1 353 **Index**
354
355 **(16#)**
Iris 6.1 356 )))|(% style="text-align:center; width:142px" %)(((
Iris 5.1 357 **Sub-index**
358
359 **(16#)**
Iris 6.1 360 )))|(% style="text-align:center; width:288px" %)**Description**|(% style="text-align:center" %)(((
Iris 5.1 361 **Data**
362
363 **Type**
Iris 6.1 364 )))|(% style="text-align:center" %)**Range**|(% style="text-align:center" %)**Read-write support**|(% style="text-align:center" %)**Unit**|(% style="text-align:center" %)**Default**|(% style="text-align:center" %)**Name**
365 |(% rowspan="5" style="text-align:center; width:77px" %)8000|(% style="text-align:center; width:142px" %)01|(% style="width:288px" %)(((
Iris 5.1 366 PT module temperature unit
367
368 0: Degree Celsius (℃)
369
370 Others: Degrees Fahrenheit (℉)
Iris 6.1 371 )))|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)PT module temperature unit
372 |(% style="text-align:center; width:142px" %)02|(% style="width:288px" %)(((
Iris 5.1 373 PT module power frequency suppression
374
375 0: Suppress 50 Hz
376
377 Others: Suppress 60Hz
Iris 6.1 378 )))|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)PT module power frequency suppression
379 |(% style="text-align:center; width:142px" %)03|(% style="width:288px" %)Reserve parameter 0|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 0
380 |(% style="text-align:center; width:142px" %)04|(% style="width:288px" %)Reserve Parameter 1|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 1
381 |(% style="text-align:center; width:142px" %)05|(% style="width:288px" %)Reserve parameter 2|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 2
382 |(% rowspan="4" style="text-align:center; width:77px" %)8001|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 383 Sensor type
384
385 0: Disable
386
387 1: PT100
388
389 3: PT1000
390
391 4: CU50
392
393 Others: Not supported
Iris 6.1 394 )))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 4|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)1|(% style="text-align:center" %)CH0 sensor type
395 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 sensor type
396 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 sensor type
397 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 sensor type
398 |(% rowspan="4" style="text-align:center; width:77px" %)8002|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 399 PT module channel filtering time: 0 to 100s
400
401 Others: 100s
Iris 6.1 402 )))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 255|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)s|(% rowspan="4" style="text-align:center" %)5|(% style="text-align:center" %)CH0 filter time
403 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 filter time
404 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 filter time
405 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 filter time
406 |(% rowspan="4" style="text-align:center; width:77px" %)8003|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 407 Overlimit detection enable
408
409 0: Disable
410
411 Others: Enable
Iris 6.1 412 )))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 255|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)0|(% style="text-align:center" %)CH0 overlimit detection
413 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 overlimit detection
414 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 overlimit detection
415 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 overlimit detection
416 |(% rowspan="4" style="text-align:center; width:77px" %)8004|(% style="text-align:center; width:142px" %)01|(% rowspan="8" style="width:288px" %)(((
Iris 5.1 417 Temperature unit: 0.1℃/0.1℉
418
419 The upper and lower limits of sensors are different for each model
Iris 6.1 420 )))|(% rowspan="4" style="text-align:center" %)INT32|(% rowspan="4" style="text-align:center" %)-32768 to 40000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)32767|(% style="text-align:center" %)CH0 temperature upper limit
421 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature upper limit
422 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 temperature upper limit
423 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature upper limit
424 |(% rowspan="4" style="text-align:center; width:77px" %)8005|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="text-align:center" %)INT32|(% rowspan="4" style="text-align:center" %)-32768 to 40000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)-32768|(% style="text-align:center" %)CH0 temperature lower limit
425 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature lower limit
426 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH1 temperature lower limit
427 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature lower limit
428 |(% rowspan="4" style="text-align:center; width:77px" %)8006|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 429 Offset temperature value (0.1℃/0.1 ℉)
430
431 0: No offset
432
433
Iris 6.1 434 )))|(% rowspan="4" style="text-align:center" %)INT16|(% rowspan="4" style="text-align:center" %)-3000 to 3000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)0|(% style="text-align:center" %)CH0 temperature offset
435 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature offset
436 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 temperature offset
437 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature offset
438 |(% rowspan="3" style="text-align:center; width:77px" %)A000|(% style="text-align:center; width:142px" %)00|(% style="width:288px" %)Module status information|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Module status
439 |(% style="text-align:center; width:142px" %)01|(% style="width:288px" %)Version code|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Version
440 |(% style="text-align:center; width:142px" %)02|(% style="width:288px" %)Error status|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Run status
441 |(% rowspan="4" style="text-align:center; width:77px" %)6000|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 442 PT CH0 to CH3 channel current temperature value (℃/℉)
443
444
Iris 6.1 445 )))|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH0 temperature
446 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH1 temperature
447 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH2 temperature
448 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH3 temperature
449 |(% rowspan="4" style="text-align:center; width:77px" %)6001|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 450 PT CH0 to CH3 status code
451
452 0, no error
453
454 0xFF, sensor not supported
455
456 0x10, configuration error: Temperature overlimit configuration
457
458 0x11, configuration error: The upper limit of the overlimit configuration is less than the lower limit
459
460 0x12, configuration error: Temperature offset configuration temperature overlimit
461
462 0x13, configuration error: NTC B value overlimit
463
464 0x40, channel disconnection error
465
466 0x41, channel temperature overflow
467
468 0x42, channel temperature overlimit
Iris 6.1 469 )))|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH0 status
470 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH1 status
471 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH2 status
472 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH3 status
Iris 5.1 473
Iris 6.1 474 = **6 Error code** =
Iris 5.1 475
Iris 6.1 476 |(% style="text-align:center" %)**Error code**|(% style="text-align:center; width:354px" %)**Description**|(% style="text-align:center; width:153px" %)**Action**|(% style="text-align:center; width:366px" %)**Solution**|(% style="text-align:center; width:161px" %)**Detect time**
477 |(% style="text-align:center" %)7080|(% style="width:354px" %)Expansion module and checksum error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect whether there is external interference between the expansion module and the PLC.|(% style="text-align:center; width:161px" %)Instruction running
478 |(% style="text-align:center" %)7081|(% style="width:354px" %)Expansion module communication message error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect whether there is external interference between the expansion module and the PLC.|(% style="text-align:center; width:161px" %)Instruction running
479 |(% style="text-align:center" %)7083|(% style="width:354px" %)Expansion module access error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect the link between the expansion module and the host|(% style="text-align:center; width:161px" %)Instruction running
480 |(% style="text-align:center" %)7084|(% style="width:354px" %)The number of expansion modules configured does not match the actual number|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Check whether the configuration is correct.|(% style="text-align:center; width:161px" %)Instruction running
481 |(% style="text-align:center" %)7110|(% style="width:354px" %)Extension module configuration error|(% style="text-align:center; width:153px" %)Stop running|(% style="width:366px" %)Check that the extension module is configured correctly|(% style="text-align:center; width:161px" %)Instruction running
Iris 5.1 482
Iris 6.1 483 = **7 Version record** =
Iris 5.1 484
Iris 6.1 485 |(% colspan="3" style="text-align:center" %)Current version: REV1.0
486 |(% style="text-align:center" %)**Version code**|(% style="text-align:center" %)**Modify content**|(% style="text-align:center" %)**Date**
487 |(% style="text-align:center" %)REV1.0|(% style="text-align:center" %)The first release|(% style="text-align:center" %)22 October 2025
Iris 5.1 488
489