Wiki source code of LX6V-4PT

Version 6.1 by Iris on 2025/10/30 10:45

Hide last authors
Iris 6.1 1 = **1 Introduction** =
Iris 2.1 2
Iris 6.1 3 (% style="text-align:center" %)
4 [[image:1761790581619-130.png||height="359" width="359"]]
Iris 2.1 5
6
7 LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
8
9 LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
10
11 Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.
12
13 **✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.
14
Iris 6.1 15 = **2 Appearance and terminal description** =
Iris 2.1 16
Iris 6.1 17 == **2.1 ​​​​​Appearance and size** ==
Iris 2.1 18
Iris 6.1 19 (% style="text-align:center" %)
20 [[image:1761790728530-525.png]]
Iris 2.1 21
22
Iris 6.1 23 ① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5); ⑤ DIN rail buckle.
Iris 2.1 24
Iris 6.1 25 == **2.2 Terminal description** ==
Iris 2.1 26
27 The 4PT expansion module terminal are arranged as follows:
28
Iris 6.1 29 (% style="margin-left:auto; margin-right:auto" %)
30 |=(((
31 **Module model**
32 )))|=(% colspan="2" rowspan="1" %)(((
33 **Terminal arrangement**
34 )))
35 |=(((
36 LX6V-4PT
37 )))|(((
38 (% style="text-align:center" %)
39 [[image:1761790846633-145.png]]
40 )))|(((
41 (% style="text-align:center" %)
42 [[image:1761790839326-892.png]]
43 )))
Iris 2.1 44
Iris 6.1 45 == **2.3** **Installation** ==
Iris 2.1 46
47 Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:
48
49
Iris 6.1 50 (% style="text-align:center" %)
51 [[image:1761790902574-569.png]]
Iris 2.1 52
Iris 6.1 53 == **2.4 Indicator** ==
Iris 2.1 54
55 The 4PT expansion module LED is shown below:
56
Iris 6.1 57 (% style="margin-left:auto; margin-right:auto" %)
58 |=**Indicator**|=**Description**
59 |=PWR|(((
Iris 2.1 60 Power indicator
61
62 1. Lights on: The module is powered on normally
63 1. Lights out: The module is not powered on or the module is abnormal
64 )))
Iris 6.1 65 |=LINK|(((
Iris 2.1 66 Communication indicator
67
68 1. Lights on: Data interaction is normal
69 1. Lights out: Data interaction is abnormal or stopped
70 )))
Iris 6.1 71 |=L1+/L2+/L3+/L4 +|(((
Iris 2.1 72 Channel indicator
73
74 1. Lights on: Channel enable
75 1. Lights out: Channel disable
76 1. Slow flash: Channel not calibrated
77 1. Fast flash: Channel abnormal (refer to status code for details)
78 )))
Iris 6.1 79 |=L1-/L2-/L3-/L4-|(% style="text-align:center" %)N/A
80 |=I1+/I2+/I3+/I4 +|(% style="text-align:center" %)N/A
Iris 2.1 81
Iris 6.1 82 == **3 Parameter Specification** ==
Iris 2.1 83
Iris 6.1 84 === **3.1 ​​​​​​​Input Specification** ===
Iris 2.1 85
Iris 6.1 86 (% style="margin-left:auto; margin-right:auto" %)
87 |=**Item**|=**Description**
88 |=Input channel|(% style="text-align:center" %)4
89 |=Digital resolution|(% style="text-align:center" %)16 bit
90 |=Sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
91 |=Input terminal|(% style="text-align:center" %)Thermocouple input
92 |=Sensor type|(% style="text-align:center" %)PT100, PT1000, CU50
93 |=Accuracy (normal temperature 25℃)|(% style="text-align:center" %)Full range ± 0.2%
94 |=Accuracy (working temperature -20℃ to 55℃)|(% style="text-align:center" %)Full range ± 0. 3%
95 |=Isolation or not|(% style="text-align:center" %)I/O terminals are isolated from power supply, channels are not isolated
96 |=Overlimit disconnection detection|(% style="text-align:center" %)Support
97 |=Power consumption|(% style="text-align:center" %)< 1.1W
98 |=Power supply|(% style="text-align:center" %)Power supply via interface, DC24V±10%, 40mA
Iris 2.1 99
Iris 6.1 100 == **3.2 Environmental specification** ==
Iris 2.1 101
Iris 6.1 102 (% style="margin-left:auto; margin-right:auto" %)
103 |=**Item**|=(% colspan="5" %)**Specification**
104 |=Usage environment|(% colspan="5" style="text-align:center" %)No corrosive, combustible gas, no large amount of conductive dust
105 |=Environment temperature|(% colspan="5" style="text-align:center" %)(((
Iris 2.1 106 Working temperature: 0℃ to 55℃
107
108 Storage temperature: -20℃ to 70℃
109 )))
Iris 6.1 110 |=(% style="text-align: center;" %)Environment humidity|(% colspan="5" style="text-align:center" %)(((
Iris 2.1 111 Working humidity: 10% to 90%RH (no condensation)
112
113 Storage humidity: ≤ 90% RH (no condensation)
114 )))
Iris 6.1 115 |=Installation|(% colspan="5" style="text-align:center" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
116 |=(% rowspan="6" %)Vibration resistance|(% colspan="5" style="text-align:center" %)According to JISC0040 standard
117 |=Installation|(% style="text-align:center" %)Frequency|(% style="text-align:center" %)Acceleration|(% style="text-align:center" %)Amplitude|(% rowspan="5" %)(((
Iris 2.1 118 X, Y, Z
119
120 10 times in each of three directions
121
122 (80 minutes in each direction)
123 )))
Iris 6.1 124 |=(% rowspan="2" %)DIN rail installation|(% style="text-align:center" %)10 to 57Hz|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0.035mm
125 |=(% style="text-align: center;" %)57 to 150Hz|(% style="text-align:center" %)4.9m/S^^2^^|(% style="text-align:center" %)~-~-
126 |=(% rowspan="2" %)Direct installation|(% style="text-align:center" %)10 to 57Hz|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0.075mm
127 |=(% style="text-align: center;" %)57 to 150Hz|(% style="text-align:center" %)9.8m/S^^2^^|(% style="text-align:center" %)~-~-
128 |=Shock resistance|(% colspan="5" %)(((
Iris 2.1 129 Compliant with JISC0041 standard
130
131 (147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)
132 )))
Iris 6.1 133 |=EMC immunity level|(% colspan="5" style="text-align:center" %)Zone B (per IEC 61131-2)
134 |=Altitude requirements|(% colspan="5" style="text-align:center" %)≤2000m (80 kPa)
135 |=Protection level|(% colspan="5" style="text-align:center" %)IP20
136 |=Grounding|(% colspan="5" style="text-align:center" %)Not co-located with the strong current system
Iris 2.1 137
Iris 6.1 138 == **3.3 Software Specifications** ==
139
140 |(% style="text-align:center" %)**Item**|(% style="text-align:center" %)**Specification**
141 |(% style="text-align:center" %)Input PDO data volume|(% style="text-align:center" %)Maximum 24 byte
142 |(% style="text-align:center" %)Diagnostic reporting function configuration|(% style="text-align:center" %)Support
143 |(% style="text-align:center" %)Diagnostic detection enable configuration|(% style="text-align:center" %)Support overlimit and disconnection detection
144 |(% style="text-align:center" %)Sensor type configuration|(% style="text-align:center" %)(((
Iris 2.1 145 Support thermal resistor type: PT100, PT1000, CU50, default is
146
147 PT100 thermal resistance
148 )))
Iris 6.1 149 |(% style="text-align:center" %)Filter time|(% style="text-align:center" %)0s to 100s (can be configured by software, default 5s)
150 |(% style="text-align:center" %)Overflow detection|(% style="text-align:center" %)Support
151 |(% style="text-align:center" %)Overlimit detection enable configuration|(% style="text-align:center" %)Support
152 |(% style="text-align:center" %)Independent channel configuration|(% style="text-align:center" %)Support
153 |(% style="text-align:center" %)Temperature offset enable configuration|(% style="text-align:center" %)Support
154 |(% style="text-align:center" %)Temperature offset configuration range|(% style="text-align:center" %)-300 to +300, temperature unit
155 |(% style="text-align:center" %)Display mode|(% style="text-align:center" %)Celsius (℃), Fahrenheit (℉)
156 |(% style="text-align:center" %)Display sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
157 |(% style="text-align:center" %)Sample refresh|(% style="text-align:center" %)Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
158 |(% style="text-align:center" %)Stop mode|(% style="text-align:center" %)Output according to the maximum value, no more refresh
159 |(% style="text-align:center" %)Disconnected or overlimit|(% style="text-align:center" %)Output according to the maximum value, no more refresh
160 |(% style="text-align:center" %)System diagnostics|(% style="text-align:center" %)System power abnormality
161 |(% style="text-align:center" %)Channel diagnosis|(% style="text-align:center" %)Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
162 |(% style="text-align:center" %)Configuration diagnostics|(% style="text-align:center" %)Configuration error identification, channel parameter configuration error
Iris 2.1 163
Iris 6.1 164 == **​​​​​​​3.4 Accuracy calculation** ==
Iris 2.1 165
166 Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.
167
Iris 6.1 168 |(% style="text-align:center" %)**Sensor type**|(% style="text-align:center" %)**Detection range**|(% style="text-align:center" %)**Accuracy**
169 |(% style="text-align:center" %)PT100|(% style="text-align:center" %)(((
Iris 2.1 170 -200.0℃ to +850.0℃,
171
172 -328.0℉ to +1562.0℉
Iris 6.1 173 )))|(% style="text-align:center" %)(((
Iris 2.1 174 T < 300°C: ±0.6℃
175
176 300℃ ≤ T ≤ 700℃: ±1.4℃
177
178 T > 700°C: ±1.7℃
179 )))
Iris 6.1 180 |(% style="text-align:center" %)PT1000|(% style="text-align:center" %)(((
Iris 2.1 181 -200.0℃ to +850.0℃,
182
183 -328.0℉ to +1562.0℉
Iris 6.1 184 )))|(% style="text-align:center" %)(((
Iris 2.1 185 T < 300°C: ±0.6℃
186
187 300℃ ≤ T ≤ 700℃: ±1.4℃
188
189 T > 700 °C: ±1.7℃
190 )))
Iris 6.1 191 |(% style="text-align:center" %)CU50|(% style="text-align:center" %)(((
Iris 2.1 192 -50.0℃ to + 150.0℃,
193
194 -58.0℉ to +302.0℉
Iris 6.1 195 )))|(% style="text-align:center" %)-50℃ ≤ T ≤ 150℃: ±0.3℃
Iris 5.1 196
Iris 6.1 197 = **4 Usage** =
Iris 5.1 198
Iris 6.1 199 This module is suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler. The two usage methods are as follow.
Iris 5.1 200
Iris 6.1 201 == **​​​​​​​4.1 Use on LX6V/LX6S** ==
Iris 5.1 202
Iris 6.1 203 (% style="text-align:center" %)
204 [[image:1761791554402-822.png]]
Iris 5.1 205
Iris 6.1 206 **(1 ) Add Module**
Iris 5.1 207
208 Steps:
209
210 ① Double-click the expansion module configuration to open the configuration interface;
211
212 ② In the module list, select LX6V-4PT and double-click to add a module;
213
214 ③ Double-click the module in the current machine slot to open the parameter configuration interface;
215
Iris 6.1 216 (% style="text-align:center" %)
Iris 5.1 217 [[image:1761790435581-926.jpeg]]
218
Iris 6.1 219 **(2) Configuration module**
Iris 5.1 220
Iris 6.1 221 **~ 1) General configuration**
Iris 5.1 222
223 [[image:1761790435591-998.jpeg]]
224
225 ① Temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;
226
227 ② Power frequency suppression: It can eliminate or reduce electromagnetic interference from the power system frequency (50Hz or 60Hz) on electronic equipment, especially signal acquisition systems. The power frequency suppression can be set to the module according to the actual application scenario.
228
Iris 6.1 229 **~ 2) Channel configuration**
Iris 5.1 230
231 [[image:1761790435593-675.jpeg]]
232
233 ① Enable channels: It can be set whether to enable the current expansion module channel;
234
235 ② Sensor type: Set the sensor type connected to the module channel, the default sensor type is PT100, there are three sensor types supported by the PT module, which are: PT100, PT1000, CU50;
236
237 ③ Filtering time: The supported filtering time is 0 to 100s, it is used to reduce fluctuations in channel temperature data. The default filtering time is 5s. Please choose the appropriate filtering time according to the requirements of actual application scenarios for channel output data;
238
239 ④ Enable overlimit detection: Channel temperature data overlimit judgment switch, when overlimit detection is enabled, the upper and lower limits of temperature can be set. When the temperature output by the channel is greater than the upper limit of temperature or less than the lower limit of temperature, the state of this channel will output a channel overlimit warning;
240
241 ⑤ Enable temperature offset: Channel temperature data offset enable switch. When temperature offset is enabled, the output temperature data of the channel will be offset;
242
Iris 6.1 243 **~ 3) I/O mapping**
Iris 5.1 244
245 By default, channels are mapped to R device according to the number of current module channels. The figure below maps modules CH1 ~~ CH12 to R0 ~~ R11 device. The data type of temperature value of channel is REAL. If want to display the temperature value of channel 1, the temperature value can be viewed after assigning a variable using the DEMOV instruction.
246
247 [[image:1761790435595-524.jpeg]]
248
249 Supported status codes:
250
Iris 6.1 251 * 0x00: Channel normal;
252 * 0x40: Channel disconnection;
253 * 0x41: Channel overflow;
254 * 0x42: Channel overrun;
Iris 5.1 255
Iris 6.1 256 **(3) Download configuration**
Iris 5.1 257
258 After the module configuration is completed and the program is compiled correctly, the project can be downloaded (at present, it is not supported to download the extension module configuration separately). Before downloading, make sure that the connected expansion module model and configuration model are in the same order. Otherwise, the PLC will report an error and stop running.
259
260 [[image:1761790435597-964.jpeg]]
261
Iris 6.1 262 == ​​​​​​​**4.2 Used on LX6V-EM□-ECAT coupler** ==
Iris 5.1 263
Iris 6.1 264 (% style="text-align:center" %)
265 [[image:1761791932607-101.png]]
Iris 5.1 266
267
Iris 6.1 268 **(1) First  add EtherCAT device**
Iris 5.1 269
270 According to steps ① to ④ in the figure below, right-click EtherCAT, and click [New]->[Import] to import the ESI device description file of the device;
271
272 [[image:1761790435601-438.jpeg]]
273
274 After the import is completed, select the coupler according to the module model and location connected to PLC. (the figure below takes LX6V-EMB-ECAT as an example);
275
276 [[image:1761790435610-644.jpeg]]
277
Iris 6.1 278 **(2) Configuration module**
Iris 5.1 279
280 Right-click the currently added coupler to add the expansion module mounted to the current coupler.
281
282 [[image:1761790435616-427.jpeg]]
283
284 **✎Note: **When the configuration module is inconsistent with the actual mounted module, an error will be reported that the OP cannot be successful.
285
Iris 6.1 286 **(3) Start configuration**
Iris 5.1 287
288 [[image:1761790435644-648.jpeg]]
289
290
291 [[image:1761790435655-470.jpeg]]
292
293
294 ① PT module temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;
295
296 0: Degree Celsius (℃);
297
298 Others: Degree Fahrenheit (℉)
299
300 ② PT module power frequency support: Set the power frequency suppression of the module to suppress 50Hz or suppress 60Hz, and the default suppression is 50Hz;
301
302 0: Suppress 50 Hz;
303
304 Others: Suppress 60 Hz;
305
306 ③ reserve: Reserve
307
308 ④ CHx sensor type: Set the type of sensor external to the channel;
309
310 Supported sensor types:
311
312 0: Disable
313
314 1: PT100;
315
316 3: PT1000
317
318 4: CU50;
319
320 ⑤ CHx filter time: Used to specify the filtering time of the current channel. The supported filtering time is 0 to 100s, it is used to reduce the fluctuation of channel temperature data. The default filtering time is 5s;
321
322 ⑥ CHx over limit detection: Overlimit detection enable configuration, 0: Overlimit detection detection is not enabled, others: Enable overlimit detection
323
324 ⑦ CHx temperature upper limit: The upper limit value of the channel overlimit detection temperature;
325
326 ⑧ CHx temperature lower limit: The lower limit value of the channel overlimit detection temperature;
327
328 ⑨ CHx temperature offset: The offset of channel data, supported offset range:-300 to +300;
329
330 **I/O mapping**
331
332 The temperature and state of the module can be mapped to variables/device. For example, the following figure maps the temperature values of the CH0 to CH3 channels to the D0 to D7 device, and the status codes of the CH0 to CH3 channels to the D8 to D11 device.
333
334 [[image:1761790435666-763.jpeg]]
335
336 Click save configuration and download the configuration to PLC.
337
Iris 6.1 338 = **5 Object dictionary** =
Iris 5.1 339
Iris 6.1 340 |(% style="text-align:center; width:77px" %)(((
Iris 5.1 341 **Index**
342
343 **(16#)**
Iris 6.1 344 )))|(% style="text-align:center; width:142px" %)(((
Iris 5.1 345 **Sub-index**
346
347 **(16#)**
Iris 6.1 348 )))|(% style="text-align:center; width:288px" %)**Description**|(% style="text-align:center" %)(((
Iris 5.1 349 **Data**
350
351 **Type**
Iris 6.1 352 )))|(% style="text-align:center" %)**Range**|(% style="text-align:center" %)**Read-write support**|(% style="text-align:center" %)**Unit**|(% style="text-align:center" %)**Default**|(% style="text-align:center" %)**Name**
353 |(% rowspan="5" style="text-align:center; width:77px" %)8000|(% style="text-align:center; width:142px" %)01|(% style="width:288px" %)(((
Iris 5.1 354 PT module temperature unit
355
356 0: Degree Celsius (℃)
357
358 Others: Degrees Fahrenheit (℉)
Iris 6.1 359 )))|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)PT module temperature unit
360 |(% style="text-align:center; width:142px" %)02|(% style="width:288px" %)(((
Iris 5.1 361 PT module power frequency suppression
362
363 0: Suppress 50 Hz
364
365 Others: Suppress 60Hz
Iris 6.1 366 )))|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)PT module power frequency suppression
367 |(% style="text-align:center; width:142px" %)03|(% style="width:288px" %)Reserve parameter 0|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 0
368 |(% style="text-align:center; width:142px" %)04|(% style="width:288px" %)Reserve Parameter 1|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 1
369 |(% style="text-align:center; width:142px" %)05|(% style="width:288px" %)Reserve parameter 2|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 2
370 |(% rowspan="4" style="text-align:center; width:77px" %)8001|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 371 Sensor type
372
373 0: Disable
374
375 1: PT100
376
377 3: PT1000
378
379 4: CU50
380
381 Others: Not supported
Iris 6.1 382 )))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 4|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)1|(% style="text-align:center" %)CH0 sensor type
383 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 sensor type
384 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 sensor type
385 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 sensor type
386 |(% rowspan="4" style="text-align:center; width:77px" %)8002|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 387 PT module channel filtering time: 0 to 100s
388
389 Others: 100s
Iris 6.1 390 )))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 255|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)s|(% rowspan="4" style="text-align:center" %)5|(% style="text-align:center" %)CH0 filter time
391 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 filter time
392 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 filter time
393 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 filter time
394 |(% rowspan="4" style="text-align:center; width:77px" %)8003|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 395 Overlimit detection enable
396
397 0: Disable
398
399 Others: Enable
Iris 6.1 400 )))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 255|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)0|(% style="text-align:center" %)CH0 overlimit detection
401 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 overlimit detection
402 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 overlimit detection
403 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 overlimit detection
404 |(% rowspan="4" style="text-align:center; width:77px" %)8004|(% style="text-align:center; width:142px" %)01|(% rowspan="8" style="width:288px" %)(((
Iris 5.1 405 Temperature unit: 0.1℃/0.1℉
406
407 The upper and lower limits of sensors are different for each model
Iris 6.1 408 )))|(% rowspan="4" style="text-align:center" %)INT32|(% rowspan="4" style="text-align:center" %)-32768 to 40000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)32767|(% style="text-align:center" %)CH0 temperature upper limit
409 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature upper limit
410 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 temperature upper limit
411 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature upper limit
412 |(% rowspan="4" style="text-align:center; width:77px" %)8005|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="text-align:center" %)INT32|(% rowspan="4" style="text-align:center" %)-32768 to 40000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)-32768|(% style="text-align:center" %)CH0 temperature lower limit
413 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature lower limit
414 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH1 temperature lower limit
415 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature lower limit
416 |(% rowspan="4" style="text-align:center; width:77px" %)8006|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 417 Offset temperature value (0.1℃/0.1 ℉)
418
419 0: No offset
420
421
Iris 6.1 422 )))|(% rowspan="4" style="text-align:center" %)INT16|(% rowspan="4" style="text-align:center" %)-3000 to 3000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)0|(% style="text-align:center" %)CH0 temperature offset
423 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature offset
424 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 temperature offset
425 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature offset
426 |(% rowspan="3" style="text-align:center; width:77px" %)A000|(% style="text-align:center; width:142px" %)00|(% style="width:288px" %)Module status information|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Module status
427 |(% style="text-align:center; width:142px" %)01|(% style="width:288px" %)Version code|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Version
428 |(% style="text-align:center; width:142px" %)02|(% style="width:288px" %)Error status|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Run status
429 |(% rowspan="4" style="text-align:center; width:77px" %)6000|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 430 PT CH0 to CH3 channel current temperature value (℃/℉)
431
432
Iris 6.1 433 )))|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH0 temperature
434 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH1 temperature
435 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH2 temperature
436 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH3 temperature
437 |(% rowspan="4" style="text-align:center; width:77px" %)6001|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 438 PT CH0 to CH3 status code
439
440 0, no error
441
442 0xFF, sensor not supported
443
444 0x10, configuration error: Temperature overlimit configuration
445
446 0x11, configuration error: The upper limit of the overlimit configuration is less than the lower limit
447
448 0x12, configuration error: Temperature offset configuration temperature overlimit
449
450 0x13, configuration error: NTC B value overlimit
451
452 0x40, channel disconnection error
453
454 0x41, channel temperature overflow
455
456 0x42, channel temperature overlimit
Iris 6.1 457 )))|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH0 status
458 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH1 status
459 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH2 status
460 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH3 status
Iris 5.1 461
Iris 6.1 462 = **6 Error code** =
Iris 5.1 463
Iris 6.1 464 |(% style="text-align:center" %)**Error code**|(% style="text-align:center; width:354px" %)**Description**|(% style="text-align:center; width:153px" %)**Action**|(% style="text-align:center; width:366px" %)**Solution**|(% style="text-align:center; width:161px" %)**Detect time**
465 |(% style="text-align:center" %)7080|(% style="width:354px" %)Expansion module and checksum error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect whether there is external interference between the expansion module and the PLC.|(% style="text-align:center; width:161px" %)Instruction running
466 |(% style="text-align:center" %)7081|(% style="width:354px" %)Expansion module communication message error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect whether there is external interference between the expansion module and the PLC.|(% style="text-align:center; width:161px" %)Instruction running
467 |(% style="text-align:center" %)7083|(% style="width:354px" %)Expansion module access error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect the link between the expansion module and the host|(% style="text-align:center; width:161px" %)Instruction running
468 |(% style="text-align:center" %)7084|(% style="width:354px" %)The number of expansion modules configured does not match the actual number|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Check whether the configuration is correct.|(% style="text-align:center; width:161px" %)Instruction running
469 |(% style="text-align:center" %)7110|(% style="width:354px" %)Extension module configuration error|(% style="text-align:center; width:153px" %)Stop running|(% style="width:366px" %)Check that the extension module is configured correctly|(% style="text-align:center; width:161px" %)Instruction running
Iris 5.1 470
Iris 6.1 471 = **7 Version record** =
Iris 5.1 472
Iris 6.1 473 |(% colspan="3" style="text-align:center" %)Current version: REV1.0
474 |(% style="text-align:center" %)**Version code**|(% style="text-align:center" %)**Modify content**|(% style="text-align:center" %)**Date**
475 |(% style="text-align:center" %)REV1.0|(% style="text-align:center" %)The first release|(% style="text-align:center" %)22 October 2025
Iris 5.1 476