Iris 6.1 1 = **1 Introduction** =
Iris 2.1 2
Iris 6.1 3 (% style="text-align:center" %)
Iris 7.1 4 [[image:1761790581619-130.png||height="397" width="397"]]
Iris 2.1 5
6 LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.
7
8 LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.
9
10 Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.
11
12 **✎Note: **The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.
13
Iris 6.1 14 = **2 Appearance and terminal description** =
Iris 2.1 15
Iris 6.1 16 == **2.1 ​​​​​Appearance and size** ==
Iris 2.1 17
Iris 6.1 18 (% style="text-align:center" %)
19 [[image:1761790728530-525.png]]
Iris 2.1 20
Iris 6.1 21 ① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5); ⑤ DIN rail buckle.
Iris 2.1 22
Iris 6.1 23 == **2.2 Terminal description** ==
Iris 2.1 24
25 The 4PT expansion module terminal are arranged as follows:
26
Iris 6.1 27 (% style="margin-left:auto; margin-right:auto" %)
28 |=(((
29 **Module model**
30 )))|=(% colspan="2" rowspan="1" %)(((
31 **Terminal arrangement**
32 )))
33 |=(((
34 LX6V-4PT
35 )))|(((
36 (% style="text-align:center" %)
37 [[image:1761790846633-145.png]]
38 )))|(((
39 (% style="text-align:center" %)
40 [[image:1761790839326-892.png]]
41 )))
Iris 2.1 42
Iris 6.1 43 == **2.3** **Installation** ==
Iris 2.1 44
45 Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:
46
47
Iris 6.1 48 (% style="text-align:center" %)
Iris 7.1 49 [[image:1761790902574-569.png||height="377" width="719"]]
Iris 2.1 50
Iris 6.1 51 == **2.4 Indicator** ==
Iris 2.1 52
53 The 4PT expansion module LED is shown below:
54
Iris 6.1 55 (% style="margin-left:auto; margin-right:auto" %)
56 |=**Indicator**|=**Description**
57 |=PWR|(((
Iris 2.1 58 Power indicator
59
60 1. Lights on: The module is powered on normally
61 1. Lights out: The module is not powered on or the module is abnormal
62 )))
Iris 6.1 63 |=LINK|(((
Iris 2.1 64 Communication indicator
65
66 1. Lights on: Data interaction is normal
67 1. Lights out: Data interaction is abnormal or stopped
68 )))
Iris 6.1 69 |=L1+/L2+/L3+/L4 +|(((
Iris 2.1 70 Channel indicator
71
72 1. Lights on: Channel enable
73 1. Lights out: Channel disable
74 1. Slow flash: Channel not calibrated
75 1. Fast flash: Channel abnormal (refer to status code for details)
76 )))
Iris 6.1 77 |=L1-/L2-/L3-/L4-|(% style="text-align:center" %)N/A
78 |=I1+/I2+/I3+/I4 +|(% style="text-align:center" %)N/A
Iris 2.1 79
Iris 6.1 80 == **3 Parameter Specification** ==
Iris 2.1 81
Iris 7.1 82 === **3.1 Input Specification** ===
Iris 2.1 83
Iris 6.1 84 (% style="margin-left:auto; margin-right:auto" %)
85 |=**Item**|=**Description**
86 |=Input channel|(% style="text-align:center" %)4
87 |=Digital resolution|(% style="text-align:center" %)16 bit
88 |=Sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
89 |=Input terminal|(% style="text-align:center" %)Thermocouple input
90 |=Sensor type|(% style="text-align:center" %)PT100, PT1000, CU50
91 |=Accuracy (normal temperature 25℃)|(% style="text-align:center" %)Full range ± 0.2%
92 |=Accuracy (working temperature -20℃ to 55℃)|(% style="text-align:center" %)Full range ± 0. 3%
93 |=Isolation or not|(% style="text-align:center" %)I/O terminals are isolated from power supply, channels are not isolated
94 |=Overlimit disconnection detection|(% style="text-align:center" %)Support
95 |=Power consumption|(% style="text-align:center" %)< 1.1W
96 |=Power supply|(% style="text-align:center" %)Power supply via interface, DC24V±10%, 40mA
Iris 2.1 97
Iris 6.1 98 == **3.2 Environmental specification** ==
Iris 2.1 99
Iris 6.1 100 (% style="margin-left:auto; margin-right:auto" %)
101 |=**Item**|=(% colspan="5" %)**Specification**
102 |=Usage environment|(% colspan="5" style="text-align:center" %)No corrosive, combustible gas, no large amount of conductive dust
103 |=Environment temperature|(% colspan="5" style="text-align:center" %)(((
Iris 2.1 104 Working temperature: 0℃ to 55℃
105
106 Storage temperature: -20℃ to 70℃
107 )))
Iris 6.1 108 |=(% style="text-align: center;" %)Environment humidity|(% colspan="5" style="text-align:center" %)(((
Iris 2.1 109 Working humidity: 10% to 90%RH (no condensation)
110
111 Storage humidity: ≤ 90% RH (no condensation)
112 )))
Iris 6.1 113 |=Installation|(% colspan="5" style="text-align:center" %)Snap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
114 |=(% rowspan="6" %)Vibration resistance|(% colspan="5" style="text-align:center" %)According to JISC0040 standard
115 |=Installation|(% style="text-align:center" %)Frequency|(% style="text-align:center" %)Acceleration|(% style="text-align:center" %)Amplitude|(% rowspan="5" %)(((
Iris 2.1 116 X, Y, Z
117
118 10 times in each of three directions
119
120 (80 minutes in each direction)
121 )))
Iris 6.1 122 |=(% rowspan="2" %)DIN rail installation|(% style="text-align:center" %)10 to 57Hz|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0.035mm
123 |=(% style="text-align: center;" %)57 to 150Hz|(% style="text-align:center" %)4.9m/S^^2^^|(% style="text-align:center" %)~-~-
124 |=(% rowspan="2" %)Direct installation|(% style="text-align:center" %)10 to 57Hz|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0.075mm
125 |=(% style="text-align: center;" %)57 to 150Hz|(% style="text-align:center" %)9.8m/S^^2^^|(% style="text-align:center" %)~-~-
126 |=Shock resistance|(% colspan="5" %)(((
Iris 2.1 127 Compliant with JISC0041 standard
128
129 (147 m/S^^2^^, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)
130 )))
Iris 6.1 131 |=EMC immunity level|(% colspan="5" style="text-align:center" %)Zone B (per IEC 61131-2)
132 |=Altitude requirements|(% colspan="5" style="text-align:center" %)≤2000m (80 kPa)
133 |=Protection level|(% colspan="5" style="text-align:center" %)IP20
134 |=Grounding|(% colspan="5" style="text-align:center" %)Not co-located with the strong current system
Iris 2.1 135
Iris 6.1 136 == **3.3 Software Specifications** ==
137
138 |(% style="text-align:center" %)**Item**|(% style="text-align:center" %)**Specification**
139 |(% style="text-align:center" %)Input PDO data volume|(% style="text-align:center" %)Maximum 24 byte
140 |(% style="text-align:center" %)Diagnostic reporting function configuration|(% style="text-align:center" %)Support
141 |(% style="text-align:center" %)Diagnostic detection enable configuration|(% style="text-align:center" %)Support overlimit and disconnection detection
142 |(% style="text-align:center" %)Sensor type configuration|(% style="text-align:center" %)(((
Iris 2.1 143 Support thermal resistor type: PT100, PT1000, CU50, default is
144
145 PT100 thermal resistance
146 )))
Iris 6.1 147 |(% style="text-align:center" %)Filter time|(% style="text-align:center" %)0s to 100s (can be configured by software, default 5s)
148 |(% style="text-align:center" %)Overflow detection|(% style="text-align:center" %)Support
149 |(% style="text-align:center" %)Overlimit detection enable configuration|(% style="text-align:center" %)Support
150 |(% style="text-align:center" %)Independent channel configuration|(% style="text-align:center" %)Support
151 |(% style="text-align:center" %)Temperature offset enable configuration|(% style="text-align:center" %)Support
152 |(% style="text-align:center" %)Temperature offset configuration range|(% style="text-align:center" %)-300 to +300, temperature unit
153 |(% style="text-align:center" %)Display mode|(% style="text-align:center" %)Celsius (℃), Fahrenheit (℉)
154 |(% style="text-align:center" %)Display sensitivity|(% style="text-align:center" %)0.01℃, 0.01℉
155 |(% style="text-align:center" %)Sample refresh|(% style="text-align:center" %)Refresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
156 |(% style="text-align:center" %)Stop mode|(% style="text-align:center" %)Output according to the maximum value, no more refresh
157 |(% style="text-align:center" %)Disconnected or overlimit|(% style="text-align:center" %)Output according to the maximum value, no more refresh
158 |(% style="text-align:center" %)System diagnostics|(% style="text-align:center" %)System power abnormality
159 |(% style="text-align:center" %)Channel diagnosis|(% style="text-align:center" %)Over upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
160 |(% style="text-align:center" %)Configuration diagnostics|(% style="text-align:center" %)Configuration error identification, channel parameter configuration error
Iris 2.1 161
Iris 8.1 162 == **3.4 Accuracy calculation** ==
Iris 2.1 163
164 Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.
165
Iris 6.1 166 |(% style="text-align:center" %)**Sensor type**|(% style="text-align:center" %)**Detection range**|(% style="text-align:center" %)**Accuracy**
167 |(% style="text-align:center" %)PT100|(% style="text-align:center" %)(((
Iris 2.1 168 -200.0℃ to +850.0℃,
169
170 -328.0℉ to +1562.0℉
Iris 6.1 171 )))|(% style="text-align:center" %)(((
Iris 2.1 172 T < 300°C: ±0.6℃
173
174 300℃ ≤ T ≤ 700℃: ±1.4℃
175
176 T > 700°C: ±1.7℃
177 )))
Iris 6.1 178 |(% style="text-align:center" %)PT1000|(% style="text-align:center" %)(((
Iris 2.1 179 -200.0℃ to +850.0℃,
180
181 -328.0℉ to +1562.0℉
Iris 6.1 182 )))|(% style="text-align:center" %)(((
Iris 2.1 183 T < 300°C: ±0.6℃
184
185 300℃ ≤ T ≤ 700℃: ±1.4℃
186
187 T > 700 °C: ±1.7℃
188 )))
Iris 6.1 189 |(% style="text-align:center" %)CU50|(% style="text-align:center" %)(((
Iris 2.1 190 -50.0℃ to + 150.0℃,
191
192 -58.0℉ to +302.0℉
Iris 6.1 193 )))|(% style="text-align:center" %)-50℃ ≤ T ≤ 150℃: ±0.3℃
Iris 5.1 194
Iris 6.1 195 = **4 Usage** =
Iris 5.1 196
Iris 6.1 197 This module is suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler. The two usage methods are as follow.
Iris 5.1 198
Iris 8.1 199 == **4.1 Use on LX6V/LX6S** ==
Iris 5.1 200
Iris 6.1 201 (% style="text-align:center" %)
Iris 7.1 202 [[image:1761791554402-822.png||height="324" width="537"]]
Iris 5.1 203
Iris 6.1 204 **(1 ) Add Module**
Iris 5.1 205
206 Steps:
207
208 ① Double-click the expansion module configuration to open the configuration interface;
209
210 ② In the module list, select LX6V-4PT and double-click to add a module;
211
212 ③ Double-click the module in the current machine slot to open the parameter configuration interface;
213
Iris 6.1 214 (% style="text-align:center" %)
Iris 8.1 215 [[image:图片1.png]]
Iris 5.1 216
Iris 6.1 217 **(2) Configuration module**
Iris 5.1 218
Iris 6.1 219 **~ 1) General configuration**
Iris 5.1 220
Iris 8.1 221 (% style="text-align:center" %)
Iris 5.1 222 [[image:1761790435591-998.jpeg]]
223
224 ① Temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;
225
226 ② Power frequency suppression: It can eliminate or reduce electromagnetic interference from the power system frequency (50Hz or 60Hz) on electronic equipment, especially signal acquisition systems. The power frequency suppression can be set to the module according to the actual application scenario.
227
Iris 6.1 228 **~ 2) Channel configuration**
Iris 5.1 229
Iris 8.1 230 (% style="text-align:center" %)
Iris 5.1 231 [[image:1761790435593-675.jpeg]]
232
233 ① Enable channels: It can be set whether to enable the current expansion module channel;
234
235 ② Sensor type: Set the sensor type connected to the module channel, the default sensor type is PT100, there are three sensor types supported by the PT module, which are: PT100, PT1000, CU50;
236
237 ③ Filtering time: The supported filtering time is 0 to 100s, it is used to reduce fluctuations in channel temperature data. The default filtering time is 5s. Please choose the appropriate filtering time according to the requirements of actual application scenarios for channel output data;
238
239 ④ Enable overlimit detection: Channel temperature data overlimit judgment switch, when overlimit detection is enabled, the upper and lower limits of temperature can be set. When the temperature output by the channel is greater than the upper limit of temperature or less than the lower limit of temperature, the state of this channel will output a channel overlimit warning;
240
241 ⑤ Enable temperature offset: Channel temperature data offset enable switch. When temperature offset is enabled, the output temperature data of the channel will be offset;
242
Iris 6.1 243 **~ 3) I/O mapping**
Iris 5.1 244
245 By default, channels are mapped to R device according to the number of current module channels. The figure below maps modules CH1 ~~ CH12 to R0 ~~ R11 device. The data type of temperature value of channel is REAL. If want to display the temperature value of channel 1, the temperature value can be viewed after assigning a variable using the DEMOV instruction.
246
Iris 8.1 247 (% style="text-align:center" %)
248 [[image:1761790435595-524.jpeg||height="638" width="806"]]
Iris 5.1 249
250 Supported status codes:
251
Iris 6.1 252 * 0x00: Channel normal;
253 * 0x40: Channel disconnection;
254 * 0x41: Channel overflow;
255 * 0x42: Channel overrun;
Iris 5.1 256
Iris 6.1 257 **(3) Download configuration**
Iris 5.1 258
259 After the module configuration is completed and the program is compiled correctly, the project can be downloaded (at present, it is not supported to download the extension module configuration separately). Before downloading, make sure that the connected expansion module model and configuration model are in the same order. Otherwise, the PLC will report an error and stop running.
260
261
262
Iris 8.1 263 == **4.2 Used on LX6V-EM□-ECAT coupler** ==
264
Iris 6.1 265 (% style="text-align:center" %)
266 [[image:1761791932607-101.png]]
Iris 5.1 267
268
Iris 6.1 269 **(1) First  add EtherCAT device**
Iris 5.1 270
271 According to steps ① to ④ in the figure below, right-click EtherCAT, and click [New]->[Import] to import the ESI device description file of the device;
272
273 [[image:1761790435601-438.jpeg]]
274
275 After the import is completed, select the coupler according to the module model and location connected to PLC. (the figure below takes LX6V-EMB-ECAT as an example);
276
277 [[image:1761790435610-644.jpeg]]
278
Iris 6.1 279 **(2) Configuration module**
Iris 5.1 280
281 Right-click the currently added coupler to add the expansion module mounted to the current coupler.
282
283 [[image:1761790435616-427.jpeg]]
284
285 **✎Note: **When the configuration module is inconsistent with the actual mounted module, an error will be reported that the OP cannot be successful.
286
Iris 6.1 287 **(3) Start configuration**
Iris 5.1 288
289 [[image:1761790435644-648.jpeg]]
290
291
292 [[image:1761790435655-470.jpeg]]
293
294
295 ① PT module temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;
296
297 0: Degree Celsius (℃);
298
299 Others: Degree Fahrenheit (℉)
300
301 ② PT module power frequency support: Set the power frequency suppression of the module to suppress 50Hz or suppress 60Hz, and the default suppression is 50Hz;
302
303 0: Suppress 50 Hz;
304
305 Others: Suppress 60 Hz;
306
307 ③ reserve: Reserve
308
309 ④ CHx sensor type: Set the type of sensor external to the channel;
310
311 Supported sensor types:
312
313 0: Disable
314
315 1: PT100;
316
317 3: PT1000
318
319 4: CU50;
320
321 ⑤ CHx filter time: Used to specify the filtering time of the current channel. The supported filtering time is 0 to 100s, it is used to reduce the fluctuation of channel temperature data. The default filtering time is 5s;
322
323 ⑥ CHx over limit detection: Overlimit detection enable configuration, 0: Overlimit detection detection is not enabled, others: Enable overlimit detection
324
325 ⑦ CHx temperature upper limit: The upper limit value of the channel overlimit detection temperature;
326
327 ⑧ CHx temperature lower limit: The lower limit value of the channel overlimit detection temperature;
328
329 ⑨ CHx temperature offset: The offset of channel data, supported offset range:-300 to +300;
330
331 **I/O mapping**
332
333 The temperature and state of the module can be mapped to variables/device. For example, the following figure maps the temperature values of the CH0 to CH3 channels to the D0 to D7 device, and the status codes of the CH0 to CH3 channels to the D8 to D11 device.
334
335 [[image:1761790435666-763.jpeg]]
336
337 Click save configuration and download the configuration to PLC.
338
Iris 6.1 339 = **5 Object dictionary** =
Iris 5.1 340
Iris 6.1 341 |(% style="text-align:center; width:77px" %)(((
Iris 5.1 342 **Index**
343
344 **(16#)**
Iris 6.1 345 )))|(% style="text-align:center; width:142px" %)(((
Iris 5.1 346 **Sub-index**
347
348 **(16#)**
Iris 6.1 349 )))|(% style="text-align:center; width:288px" %)**Description**|(% style="text-align:center" %)(((
Iris 5.1 350 **Data**
351
352 **Type**
Iris 6.1 353 )))|(% style="text-align:center" %)**Range**|(% style="text-align:center" %)**Read-write support**|(% style="text-align:center" %)**Unit**|(% style="text-align:center" %)**Default**|(% style="text-align:center" %)**Name**
354 |(% rowspan="5" style="text-align:center; width:77px" %)8000|(% style="text-align:center; width:142px" %)01|(% style="width:288px" %)(((
Iris 5.1 355 PT module temperature unit
356
357 0: Degree Celsius (℃)
358
359 Others: Degrees Fahrenheit (℉)
Iris 6.1 360 )))|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)PT module temperature unit
361 |(% style="text-align:center; width:142px" %)02|(% style="width:288px" %)(((
Iris 5.1 362 PT module power frequency suppression
363
364 0: Suppress 50 Hz
365
366 Others: Suppress 60Hz
Iris 6.1 367 )))|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)PT module power frequency suppression
368 |(% style="text-align:center; width:142px" %)03|(% style="width:288px" %)Reserve parameter 0|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 0
369 |(% style="text-align:center; width:142px" %)04|(% style="width:288px" %)Reserve Parameter 1|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 1
370 |(% style="text-align:center; width:142px" %)05|(% style="width:288px" %)Reserve parameter 2|(% style="text-align:center" %)UINT8|(% style="text-align:center" %)0 to 255|(% style="text-align:center" %)W|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)0|(% style="text-align:center" %)Reserve 2
371 |(% rowspan="4" style="text-align:center; width:77px" %)8001|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 372 Sensor type
373
374 0: Disable
375
376 1: PT100
377
378 3: PT1000
379
380 4: CU50
381
382 Others: Not supported
Iris 6.1 383 )))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 4|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)1|(% style="text-align:center" %)CH0 sensor type
384 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 sensor type
385 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 sensor type
386 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 sensor type
387 |(% rowspan="4" style="text-align:center; width:77px" %)8002|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 388 PT module channel filtering time: 0 to 100s
389
390 Others: 100s
Iris 6.1 391 )))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 255|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)s|(% rowspan="4" style="text-align:center" %)5|(% style="text-align:center" %)CH0 filter time
392 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 filter time
393 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 filter time
394 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 filter time
395 |(% rowspan="4" style="text-align:center; width:77px" %)8003|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 396 Overlimit detection enable
397
398 0: Disable
399
400 Others: Enable
Iris 6.1 401 )))|(% rowspan="4" style="text-align:center" %)UINT8|(% rowspan="4" style="text-align:center" %)0 to 255|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)0|(% style="text-align:center" %)CH0 overlimit detection
402 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 overlimit detection
403 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 overlimit detection
404 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 overlimit detection
405 |(% rowspan="4" style="text-align:center; width:77px" %)8004|(% style="text-align:center; width:142px" %)01|(% rowspan="8" style="width:288px" %)(((
Iris 5.1 406 Temperature unit: 0.1℃/0.1℉
407
408 The upper and lower limits of sensors are different for each model
Iris 6.1 409 )))|(% rowspan="4" style="text-align:center" %)INT32|(% rowspan="4" style="text-align:center" %)-32768 to 40000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)32767|(% style="text-align:center" %)CH0 temperature upper limit
410 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature upper limit
411 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 temperature upper limit
412 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature upper limit
413 |(% rowspan="4" style="text-align:center; width:77px" %)8005|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="text-align:center" %)INT32|(% rowspan="4" style="text-align:center" %)-32768 to 40000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)-32768|(% style="text-align:center" %)CH0 temperature lower limit
414 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature lower limit
415 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH1 temperature lower limit
416 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature lower limit
417 |(% rowspan="4" style="text-align:center; width:77px" %)8006|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 418 Offset temperature value (0.1℃/0.1 ℉)
419
420 0: No offset
421
422
Iris 6.1 423 )))|(% rowspan="4" style="text-align:center" %)INT16|(% rowspan="4" style="text-align:center" %)-3000 to 3000|(% rowspan="4" style="text-align:center" %)W|(% rowspan="4" style="text-align:center" %)~-~-|(% rowspan="4" style="text-align:center" %)0|(% style="text-align:center" %)CH0 temperature offset
424 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)CH1 temperature offset
425 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)CH2 temperature offset
426 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)CH3 temperature offset
427 |(% rowspan="3" style="text-align:center; width:77px" %)A000|(% style="text-align:center; width:142px" %)00|(% style="width:288px" %)Module status information|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Module status
428 |(% style="text-align:center; width:142px" %)01|(% style="width:288px" %)Version code|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Version
429 |(% style="text-align:center; width:142px" %)02|(% style="width:288px" %)Error status|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)Run status
430 |(% rowspan="4" style="text-align:center; width:77px" %)6000|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 431 PT CH0 to CH3 channel current temperature value (℃/℉)
432
433
Iris 6.1 434 )))|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH0 temperature
435 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH1 temperature
436 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH2 temperature
437 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)Float|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH3 temperature
438 |(% rowspan="4" style="text-align:center; width:77px" %)6001|(% style="text-align:center; width:142px" %)01|(% rowspan="4" style="width:288px" %)(((
Iris 5.1 439 PT CH0 to CH3 status code
440
441 0, no error
442
443 0xFF, sensor not supported
444
445 0x10, configuration error: Temperature overlimit configuration
446
447 0x11, configuration error: The upper limit of the overlimit configuration is less than the lower limit
448
449 0x12, configuration error: Temperature offset configuration temperature overlimit
450
451 0x13, configuration error: NTC B value overlimit
452
453 0x40, channel disconnection error
454
455 0x41, channel temperature overflow
456
457 0x42, channel temperature overlimit
Iris 6.1 458 )))|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH0 status
459 |(% style="text-align:center; width:142px" %)02|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH1 status
460 |(% style="text-align:center; width:142px" %)03|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH2 status
461 |(% style="text-align:center; width:142px" %)04|(% style="text-align:center" %)UINT16|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)R|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)~-~-|(% style="text-align:center" %)PT CH3 status
Iris 5.1 462
Iris 6.1 463 = **6 Error code** =
Iris 5.1 464
Iris 6.1 465 |(% style="text-align:center" %)**Error code**|(% style="text-align:center; width:354px" %)**Description**|(% style="text-align:center; width:153px" %)**Action**|(% style="text-align:center; width:366px" %)**Solution**|(% style="text-align:center; width:161px" %)**Detect time**
466 |(% style="text-align:center" %)7080|(% style="width:354px" %)Expansion module and checksum error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect whether there is external interference between the expansion module and the PLC.|(% style="text-align:center; width:161px" %)Instruction running
467 |(% style="text-align:center" %)7081|(% style="width:354px" %)Expansion module communication message error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect whether there is external interference between the expansion module and the PLC.|(% style="text-align:center; width:161px" %)Instruction running
468 |(% style="text-align:center" %)7083|(% style="width:354px" %)Expansion module access error|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Detect the link between the expansion module and the host|(% style="text-align:center; width:161px" %)Instruction running
469 |(% style="text-align:center" %)7084|(% style="width:354px" %)The number of expansion modules configured does not match the actual number|(% style="text-align:center; width:153px" %)Continue to run|(% style="width:366px" %)Check whether the configuration is correct.|(% style="text-align:center; width:161px" %)Instruction running
470 |(% style="text-align:center" %)7110|(% style="width:354px" %)Extension module configuration error|(% style="text-align:center; width:153px" %)Stop running|(% style="width:366px" %)Check that the extension module is configured correctly|(% style="text-align:center; width:161px" %)Instruction running
Iris 5.1 471
Iris 6.1 472 = **7 Version record** =
Iris 5.1 473