LX6V-4PT

Version 9.1 by Iris on 2025/10/30 11:17

1 Introduction

1761790581619-130.png

LX6V-4PT (4-channal analog inputs), used for the acquisition of thermocouple input analog signals. Suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler.

LX6V-EM□-ECAT firmware version that supports this module: V2.022 and above, the corresponding XML version: 1.3 and above.

Upper computer software version that supports this module: 2.6. 236 and above, PLC firmware version:2.321. 1032 and above.

✎Note: The total power of expansion modules connected to LX6 series PLC and LX6V-EM□-ECAT cannot be greater than 48W.

2 Appearance and terminal description

2.1 ​​​​​Appearance and size

1761790728530-525.png

① LED; ② Terminal; ③ Expansion module interface; ④ Mounting hole: 2 places (Φ4.5); ⑤ DIN rail buckle.

2.2 Terminal description

The 4PT expansion module terminal are arranged as follows:

Module model

Terminal arrangement

LX6V-4PT

1761790846633-145.png

1761790839326-892.png

2.3 Installation

Please install the end cover on the right side of the last expansion module, align it with the module interface slot and connect it, as shown in the figure below:

图片7.png

2.4 Indicator

The 4PT expansion module LED is shown below:

IndicatorDescription
PWR

Power indicator

  1. Lights on: The module is powered on normally
  2. Lights out: The module is not powered on or the module is abnormal
LINK

Communication indicator

  1. Lights on: Data interaction is normal
  2. Lights out: Data interaction is abnormal or stopped
L1+/L2+/L3+/L4 +

Channel indicator

  1. Lights on: Channel enable
  2. Lights out: Channel disable
  3. Slow flash: Channel not calibrated
  4. Fast flash: Channel abnormal (refer to status code for details)
L1-/L2-/L3-/L4-N/A
I1+/I2+/I3+/I4 +N/A

3 Parameter Specification

3.1 Input Specification

ItemDescription
Input channel4
Digital resolution16 bit
Sensitivity0.01℃, 0.01℉
Input terminalThermocouple input
Sensor typePT100, PT1000, CU50
Accuracy (normal temperature 25℃)Full range ± 0.2%
Accuracy (working temperature -20℃ to 55℃)Full range ± 0. 3%
Isolation or notI/O terminals are isolated from power supply, channels are not isolated
Overlimit disconnection detectionSupport
Power consumption< 1.1W
Power supplyPower supply via interface, DC24V±10%, 40mA

3.2 Environmental specification

ItemSpecification
Usage environmentNo corrosive, combustible gas, no large amount of conductive dust
Environment temperature

Working temperature: 0℃ to 55℃

Storage temperature: -20℃ to 70℃

Environment humidity

Working humidity: 10% to 90%RH (no condensation)

Storage humidity: ≤ 90% RH (no condensation)

InstallationSnap mount on DIN46277 (width 35mm) rail or direct positioning hole mount
Vibration resistanceAccording to JISC0040 standard
InstallationFrequencyAccelerationAmplitude

X, Y, Z

10 times in each of three directions

(80 minutes in each direction)

DIN rail installation10 to 57Hz--0.035mm
57 to 150Hz4.9m/S2--
Direct installation10 to 57Hz--0.075mm
57 to 150Hz9.8m/S2--
Shock resistance

Compliant with JISC0041 standard

(147 m/S2, action time 11ms, three sinusoidal half-wave pulses in each of X, Y, and Z directions)

EMC immunity levelZone B (per IEC 61131-2)
Altitude requirements≤2000m (80 kPa)
Protection levelIP20
GroundingNot co-located with the strong current system

3.3 Software Specifications

ItemSpecification
Input PDO data volumeMaximum 24 byte
Diagnostic reporting function configurationSupport
Diagnostic detection enable configurationSupport overlimit and disconnection detection
Sensor type configuration

Support thermal resistor type: PT100, PT1000, CU50, default is

PT100 thermal resistance

Filter time0s to 100s (can be configured by software, default 5s)
Overflow detectionSupport
Overlimit detection enable configurationSupport
Independent channel configurationSupport
Temperature offset enable configurationSupport
Temperature offset configuration range-300 to +300, temperature unit
Display modeCelsius (℃), Fahrenheit (℉)
Display sensitivity0.01℃, 0.01℉
Sample refreshRefresh asynchronously according to the sampling time, do not require synchronization refresh according to the bus cycle
Stop modeOutput according to the maximum value, no more refresh
Disconnected or overlimitOutput according to the maximum value, no more refresh
System diagnosticsSystem power abnormality
Channel diagnosisOver upper limit alarm, over lower limit alarm, disconnection alarm, overflow alarm
Configuration diagnosticsConfiguration error identification, channel parameter configuration error

3.4 Accuracy calculation

Within the working temperature range, when the temperature change rate is less than 0.3°C/min, the accuracy of this product = ADC sampling accuracy + line resistance error + contact impedance error. According to the measure principle, it is necessary to wait for the module to be powered on for 45 minutes before measuring.

Sensor typeDetection rangeAccuracy
PT100

-200.0℃ to +850.0℃,

-328.0℉ to +1562.0℉

T < 300°C: ±0.6℃

300℃ ≤ T ≤ 700℃: ±1.4℃

T > 700°C: ±1.7℃

PT1000

-200.0℃ to +850.0℃,

-328.0℉ to +1562.0℉

T < 300°C: ±0.6℃

300℃ ≤ T ≤ 700℃: ±1.4℃

T > 700 °C: ±1.7℃

CU50

-50.0℃ to + 150.0℃,

-58.0℉ to +302.0℉

-50℃ ≤ T ≤ 150℃: ±0.3℃

4 Usage

This module is suitable for Wecon LX6 series PLC and LX6V-EM□-ECAT coupler. The two usage methods are as follow.

4.1 Use on LX6V/LX6S

图片8.png

(1 ) Add Module

Steps:

① Double-click the expansion module configuration to open the configuration interface;

② In the module list, select LX6V-4PT and double-click to add a module;

③ Double-click the module in the current machine slot to open the parameter configuration interface;

图片1.png

(2) Configuration module

     1) General configuration

1761790435591-998.jpeg

① Temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;

② Power frequency suppression: It can eliminate or reduce electromagnetic interference from the power system frequency (50Hz or 60Hz) on electronic equipment, especially signal acquisition systems. The power frequency suppression can be set to the module according to the actual application scenario.

     2) Channel configuration

1761790435593-675.jpeg

① Enable channels: It can be set whether to enable the current expansion module channel;

② Sensor type: Set the sensor type connected to the module channel, the default sensor type is PT100, there are three sensor types supported by the PT module, which are: PT100, PT1000, CU50;

③ Filtering time: The supported filtering time is 0 to 100s, it is used to reduce fluctuations in channel temperature data. The default filtering time is 5s. Please choose the appropriate filtering time according to the requirements of actual application scenarios for channel output data;

④ Enable overlimit detection: Channel temperature data overlimit judgment switch, when overlimit detection is enabled, the upper and lower limits of temperature can be set. When the temperature output by the channel is greater than the upper limit of temperature or less than the lower limit of temperature, the state of this channel will output a channel overlimit warning;

⑤ Enable temperature offset: Channel temperature data offset enable switch. When temperature offset is enabled, the output temperature data of the channel will be offset;

     3) I/O mapping

By default, channels are mapped to R device according to the number of current module channels. The figure below maps modules CH1 ~ CH12 to R0 ~ R11 device. The data type of temperature value of channel is REAL. If want to display the temperature value of channel 1, the temperature value can be viewed after assigning a variable using the DEMOV instruction.

1761790435595-524.jpeg

Supported status codes:

  • 0x00: Channel normal;
  • 0x40: Channel disconnection;
  • 0x41: Channel overflow;
  • 0x42: Channel overrun;

(3) Download configuration

After the module configuration is completed and the program is compiled correctly, the project can be downloaded (at present, it is not supported to download the extension module configuration separately). Before downloading, make sure that the connected expansion module model and configuration model are in the same order. Otherwise, the PLC will report an error and stop running.

图片2.png

4.2 Used on LX6V-EM□-ECAT coupler

1761791932607-101.png

(1) First  add EtherCAT device

According to steps ① to ④ in the figure below, right-click EtherCAT, and click [New]->[Import] to import the ESI device description file of the device;

图片3.png

After the import is completed, select the coupler according to the module model and location connected to PLC. (the figure below takes LX6V-EMB-ECAT as an example);

1761790435610-644.jpeg

(2) Configuration module

Right-click the currently added coupler to add the expansion module mounted to the current coupler.

图片4.png

✎Note: When the configuration module is inconsistent with the actual mounted module, an error will be reported that the OP cannot be successful.

(3) Start configuration

1761790435644-648.jpeg

图片6.png

① PT module temperature unit: Set the temperature unit for the module output. The supported temperature unit types are Celsius (℃) or Fahrenheit (℉), the default unit is: Celsius;

0: Degree Celsius (℃);

Others: Degree Fahrenheit (℉)

② PT module power frequency support: Set the power frequency suppression of the module to suppress 50Hz or suppress 60Hz, and the default suppression is 50Hz;

0: Suppress 50 Hz;

Others: Suppress 60 Hz;

③ reserve: Reserve

④ CHx sensor type: Set the type of sensor external to the channel;

Supported sensor types:

0: Disable

1: PT100;

3: PT1000

4: CU50;

⑤ CHx filter time: Used to specify the filtering time of the current channel. The supported filtering time is 0 to 100s, it is used to reduce the fluctuation of channel temperature data. The default filtering time is 5s;

⑥ CHx over limit detection: Overlimit detection enable configuration, 0: Overlimit detection detection is not enabled, others: Enable overlimit detection

⑦ CHx temperature upper limit: The upper limit value of the channel overlimit detection temperature;

⑧ CHx temperature lower limit: The lower limit value of the channel overlimit detection temperature;

⑨ CHx temperature offset: The offset of channel data, supported offset range:-300 to +300;

I/O mapping

The temperature and state of the module can be mapped to variables/device. For example, the following figure maps the temperature values of the CH0 to CH3 channels to the D0 to D7 device, and the status codes of the CH0 to CH3 channels to the D8 to D11 device.

1761790435666-763.jpeg

Click save configuration and download the configuration to PLC.

5 Object dictionary

Index

(16#)

Sub-index

(16#)

Description

Data

Type

RangeRead-write supportUnitDefaultName
800001

PT module temperature unit

0: Degree Celsius (℃)

Others: Degrees Fahrenheit (℉)

UINT80 to 255W--0PT module temperature unit
02

PT module power frequency suppression

0: Suppress 50 Hz

Others: Suppress 60Hz

UINT80 to 255W--0PT module power frequency suppression
03Reserve parameter 0UINT80 to 255W--0Reserve 0
04Reserve Parameter 1UINT80 to 255W--0Reserve 1
05Reserve parameter 2UINT80 to 255W--0Reserve 2
800101

Sensor type

0: Disable

1: PT100

3: PT1000

4: CU50

Others: Not supported

UINT80 to 4W--1CH0 sensor type
02CH1 sensor type
03CH2 sensor type
04CH3 sensor type
800201

PT module channel filtering time: 0 to 100s

Others: 100s

UINT80 to 255Ws5CH0 filter time
02CH1 filter time
03CH2 filter time
04CH3 filter time
800301

Overlimit detection enable

0: Disable

Others: Enable

UINT80 to 255W--0CH0 overlimit detection
02CH1 overlimit detection
03CH2 overlimit detection
04CH3 overlimit detection
800401

Temperature unit: 0.1℃/0.1℉

The upper and lower limits of sensors are different for each model

INT32-32768 to 40000W--32767CH0 temperature upper limit
02CH1 temperature upper limit
03CH2 temperature upper limit
04CH3 temperature upper limit
800501INT32-32768 to 40000W---32768CH0 temperature lower limit
02CH1 temperature lower limit
03CH1 temperature lower limit
04CH3 temperature lower limit
800601

Offset temperature value (0.1℃/0.1 ℉)

0: No offset

 

INT16-3000 to 3000W--0CH0 temperature offset
02CH1 temperature offset
03CH2 temperature offset
04CH3 temperature offset
A00000Module status informationUINT16--R----Module status
01Version codeUINT16--R----Version
02Error statusUINT16--R----Run status
600001

PT CH0 to  CH3 channel current temperature value (℃/℉)

 

Float--R----PT CH0 temperature
02Float--R----PT CH1 temperature
03Float--R----PT CH2 temperature
04Float--R----PT CH3 temperature
600101

PT CH0 to  CH3 status code

0, no error

0xFF, sensor not supported

0x10, configuration error: Temperature overlimit configuration

0x11, configuration error: The upper limit of the overlimit configuration is less than the lower limit

0x12, configuration error: Temperature offset configuration temperature overlimit

0x13, configuration error: NTC B value overlimit

0x40, channel disconnection error

0x41, channel temperature overflow

0x42, channel temperature overlimit

UINT16--R----PT CH0 status
02UINT16--R----PT CH1 status
03UINT16--R----PT CH2 status
04UINT16--R----PT CH3 status

6 Error code

Error codeDescriptionActionSolutionDetect time
7080Expansion module and checksum errorContinue to runDetect whether there is external interference between the expansion module and the PLC.Instruction running
7081Expansion module communication message errorContinue to runDetect whether there is external interference between the expansion module and the PLC.Instruction running
7083Expansion module access errorContinue to runDetect the link between the expansion module and the hostInstruction running
7084The number of expansion modules configured does not match the actual numberContinue to runCheck whether the configuration is correct.Instruction running
7110Extension module configuration errorStop runningCheck that the extension module is configured correctlyInstruction running