Changes for page LX3V-8EX/16EX

Last modified by Jim on 2022/12/15 14:00

From version 3.1
edited by Stone Wu
on 2022/07/04 14:13
Change comment: There is no comment for this version
To version 8.1
edited by Stone Wu
on 2022/09/14 16:05
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,1 +1,1 @@
1 -LX3V-16EX
1 +LX3V-8EX/16EX
Content
... ... @@ -13,12 +13,12 @@
13 13  1. Product type: E means expansion;
14 14  1. Expansion input(X)
15 15  
16 -= **Dimensions ** =
16 += **2 Dimensions ** =
17 17  
18 - [[image:image-20220704141033-9.png||height="404" width="358"]] [[image:image-20220704141040-10.png||height="402" width="395"]]
18 + [[image:image-20220704141033-9.png||height="404" width="358" class="img-thumbnail"]] [[image:image-20220704141040-10.png||height="375" width="370" class="img-thumbnail"]]
19 19  
20 20  (% style="text-align:center" %)
21 -[[image:image-20220704141048-11.png||height="905" width="1065"]]
21 +[[image:image-20220704141048-11.png||height="729" width="859" class="img-thumbnail"]]
22 22  
23 23  1. Extension cable
24 24  1. Input indicator light of each channel
... ... @@ -30,18 +30,20 @@
30 30  1. DIN rail hook
31 31  1. Mounting holes (φ4.5)
32 32  
33 +|=(% scope="row" style="width: 72px;" %)Name|=(% style="width: 437px;" %)Description|=(% style="width: 151px;" %)Status|=(% style="width: 419px;" %)Event status
34 +|=(% rowspan="3" style="width: 72px;" %)LINK|(% rowspan="3" style="width:437px" %)Communication indicator between PLC and expansion module|(% style="width:151px" %)Flashes|(% style="width:419px" %)Normal data transmission(normal communication)
35 +|=(% style="width: 151px;" %)OFF|(% style="width:419px" %)Data transmission is abnormal, stopped, or failed
36 +|=(% style="width: 151px;" %)ON|(% style="width:419px" %)Software is abnormal or hardware is faulty
33 33  
34 -|Name|(% style="width:475px" %)Description|(% style="width:145px" %)Status|(% style="width:508px" %)Event status
35 -|(% rowspan="3" %)LINK|(% rowspan="3" style="width:475px" %)Communication indicator between PLC and expansion module|(% style="width:145px" %)Flashes|(% style="width:508px" %)Normal data transmission(normal communication)
36 -|(% style="width:145px" %)OFF|(% style="width:508px" %)Data transmission is abnormal, stopped, or failed
37 -|(% style="width:145px" %)ON|(% style="width:508px" %)Software is abnormal or hardware is faulty
38 -
38 +(% class="box infomessage" %)
39 +(((
39 39  **✎Note:** Except different I/O input points, LX3V-8EX and LX3V-16EX have the same dimensions and the same other functions.
41 +)))
40 40  
41 -== **2.1 Crimp terminals** ==
43 +== Crimp terminals ==
42 42  
43 43  (% style="text-align:center" %)
44 -[[image:image-20220704140755-3.png]]
46 +[[image:image-20220704140755-3.png||class="img-thumbnail"]]
45 45  
46 46  1. Please use crimp terminals as indicated on the graph.
47 47  1. The tightening torque should be applied 5 to 8 Kg.cm.
... ... @@ -49,9 +49,12 @@
49 49  
50 50  = **3 Output specification** =
51 51  
52 -|**Item**|**DC input**
54 +|=**Item**|=**DC input**
53 53  |Model|LX3V-8EX or LX3V-16EX
54 -|Output circuit|[[image:image-20220704140755-4.png]]
56 +|Output circuit|(((
57 +(% style="text-align:center" %)
58 +[[image:image-20220704140755-4.png]]
59 +)))
55 55  |Input signal voltage|DC ± 24V ± 10% *1
56 56  |Input signal current|5mA/ DC 24V
57 57  |Input ON current|More than 3.5mA
... ... @@ -70,14 +70,17 @@
70 70  1. If you expand an LX3V-16EX module on the host, the X points defined in the module on the host are X20 to X27 and X30 to X37.
71 71  1. If you expand multiple I/O input point modules on the host, the I/Os on the module will be named in the same order.
72 72  
78 +(% class="box infomessage" %)
79 +(((
73 73  **✎Note: **When adding IO expansion modules to the host, in principle, the number of all input points X must not exceed 256 points. When adding IO expansion modules to the host, if the host needs to connect multiple IO modules, it is recommended to add a separate power supply board to the module for power supply.
81 +)))
74 74  
75 75  = **5 Program** =
76 76  
77 -[[image:image-20220704141326-13.png]]
85 +[[image:image-20220704141326-13.png||class="img-thumbnail"]]
78 78  
79 79  As shown in the example above, it is LX3V-3624MT with two LX3V-16EX modules and one LX3V-4DA module. The host has 36 input points X: X0 to X7, X10 to X17, X20 to X27. X30 to X37 and X40 to X43. The input point in the module ① called by host are X50 to X57 and X60 to X67, and the input points in the module ③ called by host are X70 to X77 and X80 to X87.
80 80  
81 -[[image:image-20220704141313-12.png]]
89 +[[image:image-20220704141313-12.png||class="img-thumbnail"]]
82 82  
83 83  As shown in the example above, it is LX3V-3624MT with one LX3V-16EX and two LX3V-4DA modules. The host has 36 input points X: X0 to X7, X10 to X17, X20 to X27, X30 to X37 and X40 to X43. The input point in the module ③ called by host are X50 to X57 and X60 to X67.