Wiki source code of LX3V-8EX/16EX
Show last authors
author | version | line-number | content |
---|---|---|---|
1 | This manual is applied to LX3V-8EX and LX3V-16EX digital input expansion modules. | ||
2 | |||
3 | = **1 Naming rule** = | ||
4 | |||
5 | Naming rule of LX3V I/O input expansion module: | ||
6 | |||
7 | (% style="text-align:center" %) | ||
8 | [[image:image-20220704140755-1.png]] | ||
9 | |||
10 | 1. WECON PLC; | ||
11 | 1. Main module; | ||
12 | 1. The number of input points | ||
13 | 1. Product type: E means expansion; | ||
14 | 1. Expansion input(X) | ||
15 | |||
16 | = **2 Dimensions ** = | ||
17 | |||
18 | [[image:image-20220704141033-9.png||height="404" width="358"]] [[image:image-20220704141040-10.png||height="375" width="370"]] | ||
19 | |||
20 | (% style="text-align:center" %) | ||
21 | [[image:image-20220704141048-11.png||height="729" width="859"]] | ||
22 | |||
23 | 1. Extension cable | ||
24 | 1. Input indicator light of each channel | ||
25 | 1. LINK: Communication indicator between PLC and expansion module | ||
26 | 1. Expansion module name | ||
27 | 1. Digital signal output terminal | ||
28 | 1. Extension module interface | ||
29 | 1. DIN rail mounting slot | ||
30 | 1. DIN rail hook | ||
31 | 1. Mounting holes (φ4.5) | ||
32 | |||
33 | |Name|(% style="width:475px" %)Description|(% style="width:145px" %)Status|(% style="width:508px" %)Event status | ||
34 | |(% rowspan="3" %)LINK|(% rowspan="3" style="width:475px" %)Communication indicator between PLC and expansion module|(% style="width:145px" %)Flashes|(% style="width:508px" %)Normal data transmission(normal communication) | ||
35 | |(% style="width:145px" %)OFF|(% style="width:508px" %)Data transmission is abnormal, stopped, or failed | ||
36 | |(% style="width:145px" %)ON|(% style="width:508px" %)Software is abnormal or hardware is faulty | ||
37 | |||
38 | **✎Note:** Except different I/O input points, LX3V-8EX and LX3V-16EX have the same dimensions and the same other functions. | ||
39 | |||
40 | == **2.1 Crimp terminals** == | ||
41 | |||
42 | (% style="text-align:center" %) | ||
43 | [[image:image-20220704140755-3.png]] | ||
44 | |||
45 | 1. Please use crimp terminals as indicated on the graph. | ||
46 | 1. The tightening torque should be applied 5 to 8 Kg.cm. | ||
47 | 1. Other terminals should be empty but only wiring terminals mention in this manual. | ||
48 | |||
49 | = **3 Output specification** = | ||
50 | |||
51 | |**Item**|**DC input** | ||
52 | |Model|LX3V-8EX or LX3V-16EX | ||
53 | |Output circuit|[[image:image-20220704140755-4.png]] | ||
54 | |Input signal voltage|DC ± 24V ± 10% *1 | ||
55 | |Input signal current|5mA/ DC 24V | ||
56 | |Input ON current|More than 3.5mA | ||
57 | |Input OFF current|Less than 1.5mA | ||
58 | |(% rowspan="2" %)Input response time|About 10ms | ||
59 | |X0 to X7 built-in digital filter, setting time 0 ~~ 60ms | ||
60 | |Input signal|Contactor input or NPN or PNP | ||
61 | |Circuit insulation|Optocoupler insulation | ||
62 | |LED|Lights when input ON | ||
63 | |||
64 | = **4 Instructions** = | ||
65 | |||
66 | The I/O input points on the module are named from the next X point, using the points on the host as endpoints. For example: | ||
67 | |||
68 | 1. If the host is LX3V-1212MR-A and there are 12 input points (X0 to X7, X10 to X13). | ||
69 | 1. If you expand an LX3V-16EX module on the host, the X points defined in the module on the host are X20 to X27 and X30 to X37. | ||
70 | 1. If you expand multiple I/O input point modules on the host, the I/Os on the module will be named in the same order. | ||
71 | |||
72 | **✎Note: **When adding IO expansion modules to the host, in principle, the number of all input points X must not exceed 256 points. When adding IO expansion modules to the host, if the host needs to connect multiple IO modules, it is recommended to add a separate power supply board to the module for power supply. | ||
73 | |||
74 | = **5 Program** = | ||
75 | |||
76 | [[image:image-20220704141326-13.png]] | ||
77 | |||
78 | As shown in the example above, it is LX3V-3624MT with two LX3V-16EX modules and one LX3V-4DA module. The host has 36 input points X: X0 to X7, X10 to X17, X20 to X27. X30 to X37 and X40 to X43. The input point in the module ① called by host are X50 to X57 and X60 to X67, and the input points in the module ③ called by host are X70 to X77 and X80 to X87. | ||
79 | |||