Wiki source code of LX3V-8EX/16EX
Last modified by Wecon on 2025/09/03 21:02
Hide last authors
| author | version | line-number | content |
|---|---|---|---|
| |
1.1 | 1 | This manual is applied to LX3V-8EX and LX3V-16EX digital input expansion modules. |
| 2 | |||
| 3 | = **1 Naming rule** = | ||
| 4 | |||
| 5 | Naming rule of LX3V I/O input expansion module: | ||
| 6 | |||
| 7 | (% style="text-align:center" %) | ||
| 8 | [[image:image-20220704140755-1.png]] | ||
| 9 | |||
| 10 | 1. WECON PLC; | ||
| 11 | 1. Main module; | ||
| 12 | 1. The number of input points | ||
| 13 | 1. Product type: E means expansion; | ||
| 14 | 1. Expansion input(X) | ||
| 15 | |||
| 16 | = **2 Dimensions ** = | ||
| 17 | |||
| 18 | [[image:image-20220704141033-9.png||height="404" width="358" class="img-thumbnail"]] [[image:image-20220704141040-10.png||height="375" width="370" class="img-thumbnail"]] | ||
| 19 | |||
| 20 | (% style="text-align:center" %) | ||
| 21 | [[image:image-20220704141048-11.png||height="729" width="859" class="img-thumbnail"]] | ||
| 22 | |||
| 23 | 1. Extension cable | ||
| 24 | 1. Input indicator light of each channel | ||
| 25 | 1. LINK: Communication indicator between PLC and expansion module | ||
| 26 | 1. Expansion module name | ||
| 27 | 1. Digital signal output terminal | ||
| 28 | 1. Extension module interface | ||
| 29 | 1. DIN rail mounting slot | ||
| 30 | 1. DIN rail hook | ||
| 31 | 1. Mounting holes (φ4.5) | ||
| 32 | |||
| 33 | |=(% scope="row" style="width: 72px;" %)Name|=(% style="width: 437px;" %)Description|=(% style="width: 151px;" %)Status|=(% style="width: 419px;" %)Event status | ||
| 34 | |=(% rowspan="3" style="width: 72px;" %)LINK|(% rowspan="3" style="width:437px" %)Communication indicator between PLC and expansion module|(% style="width:151px" %)Flashes|(% style="width:419px" %)Normal data transmission(normal communication) | ||
| 35 | |=(% style="width: 151px;" %)OFF|(% style="width:419px" %)Data transmission is abnormal, stopped, or failed | ||
| 36 | |=(% style="width: 151px;" %)ON|(% style="width:419px" %)Software is abnormal or hardware is faulty | ||
| 37 | |||
| 38 | (% class="box infomessage" %) | ||
| 39 | ((( | ||
| 40 | **✎Note:** Except different I/O input points, LX3V-8EX and LX3V-16EX have the same dimensions and the same other functions. | ||
| 41 | ))) | ||
| 42 | |||
| 43 | == Crimp terminals == | ||
| 44 | |||
| 45 | (% style="text-align:center" %) | ||
| 46 | [[image:image-20220704140755-3.png||class="img-thumbnail"]] | ||
| 47 | |||
| 48 | 1. Please use crimp terminals as indicated on the graph. | ||
| 49 | 1. The tightening torque should be applied 5 to 8 Kg.cm. | ||
| 50 | 1. Other terminals should be empty but only wiring terminals mention in this manual. | ||
| 51 | |||
| 52 | = **3 Output specification** = | ||
| 53 | |||
| 54 | |=**Item**|=**DC input** | ||
| 55 | |Model|LX3V-8EX or LX3V-16EX | ||
| 56 | |Output circuit|((( | ||
| 57 | (% style="text-align:center" %) | ||
| 58 | [[image:image-20220704140755-4.png]] | ||
| 59 | ))) | ||
| 60 | |Input signal voltage|DC ± 24V ± 10% *1 | ||
| 61 | |Input signal current|5mA/ DC 24V | ||
| 62 | |Input ON current|More than 3.5mA | ||
| 63 | |Input OFF current|Less than 1.5mA | ||
| 64 | |(% rowspan="2" %)Input response time|About 10ms | ||
| 65 | |X0 to X7 built-in digital filter, setting time 0 ~~ 60ms | ||
| 66 | |Input signal|Contactor input or NPN or PNP | ||
| 67 | |Circuit insulation|Optocoupler insulation | ||
| 68 | |LED|Lights when input ON | ||
| 69 | |||
| 70 | = **4 Instructions** = | ||
| 71 | |||
| 72 | The I/O input points on the module are named from the next X point, using the points on the host as endpoints. For example: | ||
| 73 | |||
| 74 | 1. If the host is LX3V-1212MR-A and there are 12 input points (X0 to X7, X10 to X13). | ||
| 75 | 1. If you expand an LX3V-16EX module on the host, the X points defined in the module on the host are X20 to X27 and X30 to X37. | ||
| 76 | 1. If you expand multiple I/O input point modules on the host, the I/Os on the module will be named in the same order. | ||
| 77 | |||
| 78 | (% class="box infomessage" %) | ||
| 79 | ((( | ||
| 80 | **✎Note: **When adding IO expansion modules to the host, in principle, the number of all input points X must not exceed 256 points. When adding IO expansion modules to the host, if the host needs to connect multiple IO modules, it is recommended to add a separate power supply board to the module for power supply. | ||
| 81 | ))) | ||
| 82 | |||
| 83 | = **5 Program** = | ||
| 84 | |||
| 85 | [[image:image-20220704141326-13.png||class="img-thumbnail"]] | ||
| 86 | |||
| 87 | As shown in the example above, it is LX3V-3624MT with two LX3V-16EX modules and one LX3V-4DA module. The host has 36 input points X: X0 to X7, X10 to X17, X20 to X27. X30 to X37 and X40 to X43. The input point in the module ① called by host are X50 to X57 and X60 to X67, and the input points in the module ③ called by host are X70 to X77 and X100 to X107. | ||