LX5V-2ADVDAV

Last modified by Wecon on 2025/09/03 21:02

1.Installation

  • Before installation, it must be ensured that the PLC host and the related device of the BD module terminal wiring are powered off reliably. The module shell is inserted into the BD module slot of PLC host, and then locked with two standard screws for fixation.
  • Two standard terminal heads are equipped with this BD module. After connecting the wiring, insert them into its terminal. After confirming that the host, BD module, wiring, etc. are installed correctly, it can be powered on for use.
  • ✎Note:
    • When DAV current is output, ensure that the external load resistance is greater than or equal to 2KΩ. If the external load resistance is less than 2KΩ, the output current will be lower than normal value.
    • The ADV input cannot exceed the absolute maximum (-15V/+15V), otherwise the BD module will be damaged.
    • Please install the BD module firmly and fix it on PLC. Poor contact may lead to failure.
    • Tightening torque for fixing BD module or PLC top cover is 0.3N.m to 0.6N.m. Please tighten it firmly to avoid malfunction.
    • You can only use one LX5V-2ADV2DAV-BD on the PLC main unit of LX5 series.
  • Warning: Cut off the power before installing, removing or wiring the BD module to avoid electric shock or product damage.

2. Appearance and terminal

image-20221223103536-1.png

Table1 Terminal distribution

IN_2ADV part

Input voltage range: -10Vto10V

OUT_2DAV part

Voltage output range: -10Vto10V

Vi2-

Channel 2

Voltage input negative

Vo2-

Channel 2

voltage output negative

Vi2+

Channel 2

Voltage input positive

Vo2+

Channel 2

Voltage output positive

 NC NC
Vi1+

Channel 1

Voltage input positive

Vo1+

Channel 1

Voltage output positive

Vi1-

Channel 1

Voltage input negative

Vo1-

Channel 1

voltage output negative

Table2 LED lamp function description

Indicator lampDescription
PWRON when power-on (when the program is running, it will be ON).
COMIt flashes when communicating with PLC normally, and it is OFF when timeout.
CH1Channel 1 lamp: Always on in range; Flashing outside the range of (-10V to 10V); Off when the channel is closed.
CH2Channel 2 lamp: Always on in range; flashing outside the range of (-10V to 10V); Off when the channel is closed.
CH3

Channel 3 lamp: Set it always on in the digital value of -2000to 2000 (-10V to 10V); Flashes outside the digital value of -2000 to2000 (-10V to 10V).

When the channel is open, the light is on, and the voltage is output; When the channel is closed, the light is off, and the voltage is not output (approaching 0).

CH4Channel 4 lamp: Set it always on in the digital value of -2000to 2000 (-10V to 10V); Flashes outside the digital value of -2000 to2000 (-10V to 10V). When the channel is open, the light is on, and the voltage is output; When the channel is closed, the light is off, and the voltage is not output (approaching 0).

3.Specification

  1. General specification: Same as PLC main unit. (Please refer to the accompanying manual of the PLC main unit.)
  2. Power supply specification: The power supply is provided internally by PLC.
  3. Performance specifications:
ProjectDescription
Power supply24VDC±10%, 50mA; 5VDC±10%, 70mA (The power supply is provided internally by host)
ADV section
Analog input rangeDC -10V to 10V (input resistor 160KΩ). ✎Note: If the input voltage exceeds ±15V, the unit will be damaged.
Rated range(-10V to10V: -2000 to 2000)
Maximum display range-2048 to 2048
Resolution5mV (10V default range 1/2000)
Comprehensive precision±0.5% of full scale
A/D conversion time1 scan cycle (A/D conversion after ladder diagram END instruction is executed, and BD channel mapping value is updated)
Input featuresimage-20221223104016-6.png
InsulationThere is no insulation between the channels of the module
Points occupied0 point (2ADV is not affected by the standard maximum control points of the main PLC because it is operated through the data register)
DAV section
Analog output rangeDC -10V to 10V (external load resistance ≥ 2KΩ)
Rated range(-2000 to 2000:-10V to 10V)
Digital output12-bit binary
Resolution5mV (10V default range 1/2000)
Comprehensive precision±0.5% of full scale
D/A conversion timeOne scan cycle (D/A conversion after ladder diagram END instruction is executed, and BD channel output value is updated)
Output featuresimage-20221223103722-5.png
Points occupied0 point (2ADI is not affected by the standard maximum control points of the main PLC because it is operated through the data register)

4.Wiring

image-20221223104148-7.png
Cut off the power before installing, removing or wiring the BD module to avoid electric shock or product damage.

✎Note:


    • Do not place signal cables near high voltage power cables or in the same trunk line. Otherwise, it may be disturbed or surged. Keep a safe distance between signal cable and power cable, at least 100mm.
    • Ground the shielding of shielded wire or shielded cable. But the ground point and high voltage line cannot be the same.
    • Do not connect cables of impermissible size to avoid poor contact or product damage.
    • Fix the cable so that no force directly acts on the terminal line or cable connection area.
    • The tightening torque of terminal is 0.5Nm to 0.6N.m. Please tighten it to prevent malfunction.
    • Do not use empty terminals.

4.1 Applicable cables

  1. AWG25-16 is used for connection with output device.
  2. Maximum terminal tightening torque is 0.5N.m to 0.6N.m.
  3. Using different types of cables may cause poor contact with terminals. Please use pressfit terminals for good contact.

Line number and cross-sectional area

Line numberCross-sectional area (mm2)End processing
AWG260.1288

Stranded cable: Strip off the sheath, rub the core wire, and then connect the cable.

Single-core cable: Strip off the sheath and connect the cable.

......
AWG161.309

image-20221223104252-9.png

4.2 I/O Mode

image-20221223104446-10.png

  1. Analog inputs are received via twisted-pair shielded cables away from power lines or other wires that may cause electrical interference.
  2. If there is voltage fluctuation in the input or electrical interference in the external wiring, a smoothing capacitor can be connected (0.1uF   to 0.47uF, 25V).

image-20221223104534-11.png

  1. When using twisted pair shielded cables for the analog outputs, the cables should be located away from power lines or other wires that may generate electrical interference.
  2. Use single point grounding at the load end of the output cable. (Level 3 grounding: no more than 100 Ω).

If there is electrical noise or voltage fluctuation in the output, a smoothing capacitor(0.1 uF  to 0.47 uF, 25V) can be connected

5.Description of PLC device

  1. When connected to LX3 series PLC, please refer to LX3 series BD module manual.
  2. When connected to LX5 series PLC, if the firmware version of PLC is lower than 2.051 (excluding 2.051), or BD module is not configured by host computer, it can be controlled by the following system devices:

Table3Device allocation

PLC modelBD ModelDevicesDescriptionDevicesDescription
LX5V2ADV2DAVSM2010CH1 voltage input channel open flag

OFF: Open

ON: Close

SD2010

CH1 digital value

(-10V to10V: -2000 to 2000)

SM2011CH2 voltage input channel open flagSD2011

CH2 digital value

(-10V to10V: -2000 to 2000)

SM2012CH3 current output channel open flagSD2012

CH3 digital value

(-2000 to 2000:-10V to 10V)

SM2013CH4 current output channel open flagSD2013

CH4 digital value

(-2000 to 2000:-10V to 10V)

     3. You can select device through I/O mapping to use the configuration function of new BD module. For details, please refer to "6.1 Parameter configuration".

6. Instructions

6.1 Parameter configuration

① Open the host computer software and create a new project,  in “Project Manager” → “Extended Function” , double-click "BD Module Configuration" Noteto enter “BD settings” interface;

② Configure the currently connected PLC (take the LX5V-2416 model as an example) and BD module model on the BD module configuration interface: Select “LX5V-2ADV2DAV" in the device bar on the right side of the BD module configuration interface and double-click to add it to the corresponding slot position of PLC (slot number 1 or 2, the software will select slot 1 by default, and right-click to move down to slot 2);

③ After adding the BD module to the slot, double-click or right-click to select configuration parameters to enter LX5V-2ADV2DAV-BD configuration parameters interface, as shown in the following figure. Configure related parameters on this interface.

image-20221223105418-12.png

Note: This function is only supported in the following versions of host computer, slave computer and BD module:

(1) Supported host computer software versions: Wecon PLC Editor2 2.1.204 and above, as shown in the following figure:

image-20221223105439-13.png

(2) Supported  PLC firmware: 2.051 and above, as shown in the following figure:

image-20221223105636-14.png

(3) Supported BD module version number: 1013 and above, as shown in the following figure:

image-20221223105652-15.png

The parameter configuration interface is as below:

1. Module setting: Set response time (The response time is the interval time between PLC acquisition of BD module data. Range: 0.1ms to 3276.7ms).

image-20221223105755-16.png

2.ADV configuration:

image-20221223105813-17.png

  • Check enable channel to set whether to enable the current BD module channel.
  • The conversion mode is set to ADV conversion mode by default. The measurement range is -10V to 10V (-2000 to 2000).
  • Setting the filtering intensity can reduce the jitter of BD channel value. The default configuration of filter intensity is 4. Level 0 is the lowest and level 9 is the highest. The filter intensity can be adjusted according to actual use.
  • Check enable calibration, you could calculate the gain offset according to the following formula to convert the corresponding channel value:

Channel value = digital value × gain value + offset value

  • When the channel value deviates, you could also set the gain offset to calibrate the channel. For example:
  • When the channel input analog is 10V, the digital quantity of BD module acquisition channel value is 1970, and the actual digital value should be 2000.
  • When the channel input analog quantity is 0V, the digital quantity of BD module acquisition channel value is 30, and the actual digital value should be 0.

Suppose the gain is a, and the offset is b, thenimage-20221223105952-18.png

Solve and getimage-20221223110026-19.pngThe calibration can be completed by setting the corresponding gain offset to the current channel.

3.DAV configuration:

image-20221223110244-21.png

  • Check enable channel to set whether to enable the current BD module channel.
  • The conversion mode is set to DAV conversion mode by default, and the measurement range is -10V to 10V (-2000 to 2000).
  • Output state after stop: When PLC stops, the output state of BD module channel mainly includes the following three types:

Output clear: When PLC stops, the output voltage of BD module channel is 0V.

Output hold: When PLC stops, the channel output of the BD board maintains the digital voltage value set by the corresponding channel in the current I/O mapping device.

Output preset value: When the PLC STOP, the BD module channel outputs the voltage value corresponding to the preset digital quantity or the preset analog quantity.

  • Check enable calibration, you could calculate the gain offset according to the following formula to convert the corresponding channel value:

Channel input digital value = digital quantity of the actual voltage output pair × gain value + offset value

  • When the channel value deviates, you could also set the gain offset to calibrate the channel. For example:
  • When the channel input digital value is 0, the multimeter measures the output voltage of BD module channel to be 0.5V (corresponding digital value is 100).
  • When the channel input digital value is 2000, the multimeter measures the output current of BD module channel to be 9.5V (corresponding digital value is 1900).

Suppose the gain is a, and the offset is b, thenimage-20221223110338-23.png

Solve and getimage-20221223110348-24.png The calibration can be completed by setting the corresponding gain offset to the current channel.

4.Set I/O mapping. The channels are mapped to R device according to the current number of BD module channels by default. As shown in the following figure, BD module CH1 to CH4 is mapped to device R0 to R3.

image-20221223110908-25.png

5.After the above configuration is completed, check the program, download the configuration to PLC, and STOP→RUN configuration takes effect.

image-20221223110942-26.png

6.2 Ladder Diagram

  1. Programming example that does not use the host computer software "BD module configuration" function. For device allocation, please refer to "5 PLC device description".image-20221223111122-27.png
  2. .Programming example using the "BD module configuration" function of host computer software:image-20221223111206-28.png

6.3 BD monitoring interface and buffer memory

Open the module monitoring interface, select BD module, select LX5V-2ADV2DAV from the list of BD modules on the right to monitor it online, and check the current BD module communication status and error information in time.

image-20221223111322-29.png

① ADV buffer memory (BFM): used for BD module status monitoring.

BFM

Address

Power-off holdRead/writeMemory nameDefaultRangeDescription
0x2000×R/WChannel 1 channel enable10 to 10: Channel closed; 1: Channel open
0x2001×R/WChannel 1 channel mode selection110: Voltage mode (-10V to 10V)
0x2002×R/WChannel 1 filter intensity40 to 90: Minimum filter strength; 9: Maximum filter strength
0x2080×RChannel 1 channel value0-2000 to 2000 
0x2082×RChannel 1 status information00 to 2

0: Channel closed; 1: Channel opened 

2: Channel value exceeds the range

0x2084×RChannel 1 error code00 to 10: No error; 1: Channel value exceeds the range
0x2100×R/WChannel 2 channel enable10 to 10: Channel closed; 1: Channel open
0x2101×R/WChannel 2 channel mode selection110: Voltage mode (-10V to 10V)
0x2102×R/WChannel 2 filter intensity40 to 90: Minimum filter strength; 9: Maximum filter strength
0x2180×RChannel 2 channel value0-2000 to 2000 
0x2182×RChannel 2 status information00 to 2

0: Channel closed; 1: Channel opened 

2: Channel value exceeds the range

0x2184×RChannel 2 error code00 to 10: No error; 1: Channel value exceeds the range

② DAV buffer memory (BFM): used for BD module status monitoring.

BFM

Address

Power-off holdRead/writeMemory nameDefaultRangeDescription
0x2200×R/WChannel 3 channel enable10 to 10: Channel closed; 1: Channel open
0x2201×R/WChannel 3 channel mode selection000: Voltage mode (-10V to 10V)
0x2203×R/WOutput status after channel 3 stops00 to 2

0: Output cleared; 1: Output held 

2: Output preset value

0x2204×R/WChannel 3 output preset value0-32768 to 32767 
0x2280×RChannel 3 channel value0-2000 to 2000Only supported in channel mapping device setting
0x2282×RChannel 3 status information10 to 2

0: Channel closed; 1: Channel opened 

2: Channel value exceeds the range

0x2284×RChannel 3 error code00 to 10: No error; 1: Channel value exceeds the range
0x2300×R/WChannel 4 channel enable10 to 10: Channel closed; 1: Channel open
0x2301×R/WChannel 4 channel mode selection000: Voltage mode (-10V to 10V)
0x2303×R/WOutput status after channel 4 stops00 to 2

0: Output cleared; 1: Output held 

2: Output preset value

0x2304×R/WChannel 4 output preset value0-32768 to 32767 
0x2380×RChannel 4 channel value0-2000 to 2000Only supported in channel mapping device setting
0x2382×RChannel 4 status information10 to 2

0: Channel closed; 1: Channel opened 

2: Channel value exceeds the range

0x2384×RChannel 4 error code00 to 10: No error; 1: Channel value exceeds the range

③ Universal buffer memory (BFM): used to diagnose the communication status of the currently connected BD module.

BFM

Address

Power-off hold

Read/write

Function

Memory nameDefaultRangeDescription
0x200×RCurrent maximum package length00 to 0xFFFFThe maximum length of the currently sent package
0x202×RNumber of retransmissions00 to 0xFFFFNumber of retransmissions
0x204×RNumber of retransmissions of subpackages00 to 0xFFFFNumber of retransmissions of subpackages
0x206×RReceived times of sync frames00 to 0xFFFFReceived times of sync frames
0x208×RSent times of sync frame00 to 0xFFFFSent times of sync frame
0x20A×RControl the number of transmissions00 to 0xFFFFControl the number of transmissions
0x20C×RControl the number of receptions00 to 0xFFFFControl the number of receptions
0x20E×RNumber of subscriptions sent00 to 0xFFFFNumber of subscriptions sent
0x210×RNumber of subscriptions received00 to 0xFFFFNumber of subscriptions received
0x212R/WLatest error code0Only 0 can be written.Protocol internal error code, write 0 to clear
0x214×RNumber of bytes sent00 to 0xFFFFFFFNumber of bytes sent
0x218×RNumber of valid bytes sent00 to 0xFFFFFFFNumber of valid bytes sent
0x21C×RNumber of bytes received00 to 0xFFFFFFFNumber of bytes received
0x220×RNumber of valid bytes received00 to 0xFFFFFFFNumber of valid bytes received
0x224×RCommunication time (unit s)00 to 0xFFFFFFFNormal communication time since the BD

module is powered on