1 1  = **1. Installation** =
2 2  
3 -* Before installation, it must be ensured that the PLC host and the related device of the BD board terminal wiring are powered off reliably. The module shell is inserted into the BD module slot of PLC host, and then locked with two standard screws for fixation.
4 -* Two standard terminal heads are equipped with this Bd board. After connecting the wiring, insert them into its terminal. After confirming that the host, BD board, wiring, etc. are installed correctly, it can be powered on for use.
3 +* Before installation, it must be ensured that the PLC host and the related device of the BD module terminal wiring are powered off reliably. The module shell is inserted into the BD module slot of PLC host, and then locked with two standard screws for fixation.
4 +* Two standard terminal heads are equipped with this BD module. After connecting the wiring, insert them into its terminal. After confirming that the host, BD module, wiring, etc. are installed correctly, it can be powered on for use.
5 5  * **✎Note:**
6 6  ** When DAI current is output, ensure that the external load resistance is less than 500Ω. If the external load resistance is greater than 500Ω, the output current will be lower than normal value.
7 -** Please install the BD board firmly and fix it on PLC. Poor contact may lead to failure.
8 -** Tightening torque for fixing BD board or PLC top cover is 0.3N.m to0.6N.m. Please tighten it firmly to avoid malfunction.
7 +** Please install the BD module firmly and fix it on PLC. Poor contact may lead to failure.
8 +** Tightening torque for fixing BD module or PLC top cover is 0.3N.m to0.6N.m. Please tighten it firmly to avoid malfunction.
9 9  ** You can only use a LX5V-2PT2DAI-BD on the PLC main unit of LX5 series.
10 -* **Warning: Cut off the power before installing, removing or wiring the BD board to avoid electric shock or product damage.**
10 +* **Warning: Cut off the power before installing, removing or wiring the BD module to avoid electric shock or product damage.**
11 11  
12 12  = **2. Appearance and terminal** =
13 13  
... ... @@ -120,11 +120,11 @@
120 120  1. 3-wire PT100: When using channel 1, two leads of the same color are connected to L1- and VI- respectively, and the other lead of different color is connected to L1+. Channel 2 is connected in the same way.
121 121  
122 122  |[[image:image-20221222110545-3.png]]
123 -|Cut off the power before installing, removing or wiring the BD board to avoid electric shock or product damage.
123 +|Cut off the power before installing, removing or wiring the BD module to avoid electric shock or product damage.
124 124  
125 125  **✎Note:**
126 126  
127 -*
127 +*
128 128  ** Do not place signal cables near high voltage power cables or in the same trunk line. Otherwise, it may be disturbed or surged. Keep a safe distance between signal cable and power cable, at least 100mm.
129 129  ** Ground the shielding of shielded wire or shielded cable. But the ground point and high voltage line cannot be the same.
130 130  ** Do not connect cables of impermissible size to avoid poor contact or product damage.
... ... @@ -165,11 +165,11 @@
165 165  
166 166  = **5. Description of PLC device** =
167 167  
168 -~1. When connected to LX3 series PLC, please refer to LX3 series BD board manual.
168 +~1. When connected to LX3 series PLC, please refer to LX3 series BD module manual.
169 169  
170 -2. When connected to LX5 series PLC, if the firmware version of PLC is lower than 2.051 (excluding 2.051), or BD board is not configured by host computer, it can be controlled by the following system devices:
170 +2. When connected to LX5 series PLC, if the firmware version of PLC is lower than 2.051 (excluding 2.051), or BD module is not configured by host computer, it can be controlled by the following system devices:
171 171  
172 -3. User can select device through I/O mapping to use the configuration function of new BD board. For details, please refer to "[[6.1 Parameter configuration>>path:#_6.1 参数配置]]".
172 +3. User can select device through I/O mapping to use the configuration function of new BD module. For details, please refer to "[[6.1 Parameter configuration>>path:#_6.1 参数配置]]".
173 173  
174 174  **Device allocation**