1. Installation
- Before installation, it must be ensured that the PLC host and the related device of the BD board terminal wiring are powered off reliably. The module shell is inserted into the BD module slot of PLC host, and then locked with two standard screws for fixation.
- Two standard terminal heads are equipped with this Bd board. After connecting the wiring, insert them into its terminal. After confirming that the host, BD board, wiring, etc. are installed correctly, it can be powered on for use.
- ✎Note:
- When DAI current is output, ensure that the external load resistance is less than 500Ω. If the external load resistance is greater than 500Ω, the output current will be lower than normal value.
- Please install the BD board firmly and fix it on PLC. Poor contact may lead to failure.
- Tightening torque for fixing BD board or PLC top cover is 0.3N.m to0.6N.m. Please tighten it firmly to avoid malfunction.
- You can only use a LX5V-2PT2DAI-BD on the PLC main unit of LX5 series.
- Warning: Cut off the power before installing, removing or wiring the BD board to avoid electric shock or product damage.
2. Appearance and terminal
IN_2PT part 2-wire/3-wire PT100 thermal resistance | OUT_2DAI part Current output range: 4mA to 20mA | ||
L2- | Channel 2 sensor signal input negative | Io2- | Channel 2 sensor signal output negative |
L2+ | Channel 2 sensor signal input positive | Io2+ | Channel 2 sensor signal output positive |
VI- | Sensor common pole | NC | |
L1+ | Channel 1 sensor signal input positive | Io1+ | Channel 1 sensor signal output positive |
L1- | Channel 1 sensor Signal input negative | Io1- | Channel 1 sensor signal output negative |