Wiki source code of LX5V-2PT2DAI

Version 2.1 by Jim on 2022/12/22 11:07

Show last authors
1 = **1. Installation** =
2
3 * Before installation, it must be ensured that the PLC host and the related device of the BD board terminal wiring are powered off reliably. The module shell is inserted into the BD module slot of PLC host, and then locked with two standard screws for fixation.
4 * Two standard terminal heads are equipped with this Bd board. After connecting the wiring, insert them into its terminal. After confirming that the host, BD board, wiring, etc. are installed correctly, it can be powered on for use.
5 * **✎Note:**
6 ** When DAI current is output, ensure that the external load resistance is less than 500Ω. If the external load resistance is greater than 500Ω, the output current will be lower than normal value.
7 ** Please install the BD board firmly and fix it on PLC. Poor contact may lead to failure.
8 ** Tightening torque for fixing BD board or PLC top cover is 0.3N.m to0.6N.m. Please tighten it firmly to avoid malfunction.
9 ** You can only use a LX5V-2PT2DAI-BD on the PLC main unit of LX5 series.
10 * **Warning: Cut off the power before installing, removing or wiring the BD board to avoid electric shock or product damage.**
11
12 == **2. Appearance and terminal** ==
13
14 [[image:image-20221222110100-1.png]]
15
16 (% class="table-bordered" %)
17 |(% colspan="2" %)(((
18 **IN_2PT part**
19
20 **2-wire/3-wire PT100 thermal resistance**
21 )))|(% colspan="2" %)(((
22 **OUT_2DAI part**
23
24 **Current output range: 4mA to 20mA**
25 )))
26 |L2-|(((
27 Channel 2 sensor
28
29 signal input negative
30 )))|Io2-|(((
31 Channel 2
32
33 sensor signal output negative
34 )))
35 |L2+|(((
36 Channel 2 sensor
37
38 signal input positive
39 )))|Io2+|(((
40 Channel 2
41
42 sensor signal output positive
43 )))
44 |VI-|Sensor common pole| |NC
45 |L1+|(((
46 Channel 1 sensor
47
48 signal input positive
49 )))|Io1+|(((
50 Channel 1
51
52 sensor signal output positive
53 )))
54 |L1-|(((
55 Channel 1 sensor
56
57 Signal input negative
58 )))|Io1-|(((
59 Channel 1
60
61 sensor signal output negative
62 )))
63
64 (% class="table-bordered" %)
65 |**Indicator lamp**|**Description**
66 |PWR|ON when power-on (when the program is running, it will be ON).
67 |COM|It flashes when communicating with PLC normally, and it is OFF when timeout.
68 |CH1|Channel 1 lamp: Always on in range; Flashing outside the range of -100℃to600℃; Off when the channel is closed.
69 |CH2|Channel 2 lamp: Always on in range; Flashing outside the range of -100℃to600℃; Off when the channel is closed.
70 |CH3|(((
71 Channel 3 lamp: Set the digital value 0to 2000 (4mA) to 20mA) to be always on; Flashes outside the digital value 0 to2000 (4mA to 20mA).
72
73 When the channel is open, the light is on, and the current is output; When the channel is closed, the light is off, and the current is not output (approaching 0).
74 )))
75 |CH4|(((
76 Channel 4 lamp: Set the digital value 0to 2000 (4mA) to 20mA) to be always on; Flashes outside the digital value 0 to2000 (4mA to 20mA).
77
78 When the channel is open, the light is on, and the current is output; When the channel is closed, the light is off, and the current is not output (approaching 0).
79 )))
80
81 = 3. ** Specification** =
82
83 ~1. General specification: Same as PLC main unit. (Please refer to the accompanying manual of the PLC main unit.)
84
85 2. Power supply specification: The power supply is provided internally by PLC.
86
87 3. Performance specifications:
88
89 (% class="table-bordered" %)
90 |**Project**|(% colspan="2" %)**Description**
91 |Power supply|(% colspan="2" %)24VDC±10%, 50mA; 5VDC±10%, 70mA (The power supply is provided internally by host)
92 |(% colspan="3" %)**PT part**
93 |Analog input signal|(% colspan="2" %)Platinum thermal resistance PT100 sensor (100Ω), 3-wire, 2-channel input (CH1, CH2)
94 |Sensor current|(% colspan="2" %)1mA sensor: 100 Ω (PT100)
95 |Compensation range|-100 ℃ to 600 ℃ (recommended range)|Over range display: 32767
96 |Digital output|(% colspan="2" %)-1000 to 6000 (unit 0.1 ℃)
97 |Measurement accuracy|(% colspan="2" %)0.2℃ to 0.3℃
98 |Total accuracy|(% colspan="2" %)Full range ±0.5% (compensation range)
99 |Conversion speed|(% colspan="2" %)2 channels 50ms
100 |Conversion features|(% colspan="2" %)[[image:image-20221222110430-1.png]]
101 |(% colspan="3" %)**DAI section**
102 |Rated range|(% colspan="2" %)0 to 2000: 4mA to 20mA
103 |Analog output range|(% colspan="2" %)DC 4mA to 20mA (external load resistance ≤ 500 Ω)
104 |Digital output|(% colspan="2" %)12-bit binary
105 |Resolution|(% colspan="2" %)8uA (4mA to 20mA/2000)
106 |Comprehensive precision|(% colspan="2" %)±0.5% of full scale (4mA to 20mA: ±0.08 mA)
107 |D/A conversion time|(% colspan="2" %)One scan cycle (D/A conversion after ladder diagram END instruction is executed, and BD channel output value is updated)
108 |Output features|(% colspan="2" %)(((
109 External load is 250Ω. 0 to 2000 was converted to 4mA to 20mA.
110
111 [[image:image-20221222110430-2.png]]
112 )))
113 |Points occupied|(% colspan="2" %)0 point (2DAI is not affected by the standard maximum control points of the main PLC because it is operated through the data register)
114
115 = **4.  Wiring ** =
116
117 **Wiring instructions:**
118
119 1. 2-wire PT100: When using channel 1, L1- and VI- are shorted with wires, and the two leads of the sensor are connected to L1+ and LI- respectively. Similarly, when using channel 2, L2- and VI- are shorted with wires, and the two leads of the sensor are connected to L2+ and L2- respectively.
120 1. 3-wire PT100: When using channel 1, two leads of the same color are connected to L1- and VI- respectively, and the other lead of different color is connected to L1+. Channel 2 is connected in the same way.
121
122 |[[image:image-20221222110545-3.png]]
123 |Cut off the power before installing, removing or wiring the BD board to avoid electric shock or product damage.
124
125 **✎Note:**
126
127 *
128 ** Do not place signal cables near high voltage power cables or in the same trunk line. Otherwise, it may be disturbed or surged. Keep a safe distance between signal cable and power cable, at least 100mm.
129 ** Ground the shielding of shielded wire or shielded cable. But the ground point and high voltage line cannot be the same.
130 ** Do not connect cables of impermissible size to avoid poor contact or product damage.
131 ** Fix the cable so that no force directly acts on the terminal line or cable connection area.
132 ** The tightening torque of terminal is 0.5Nm to 0.6N.m. Please tighten it to prevent malfunction.
133 ** Do not use empty terminals.
134
135 === **4.1 Applicable cables** ===
136
137 ~1. AWG25-16 is used for connection with output device.
138
139 2. Maximum terminal tightening torque is 0.5N.m to 0.6N.m.
140
141 3. Using different types of cables may cause poor contact with terminals. Please use pressfit terminals for good contact.
142
143 **Line number and cross-sectional area**
144
145 |**Line number**|**Cross-sectional area (mm^^2^^)**|**End processing**
146 |AWG26|0.1288|(% rowspan="3" %)(((
147 Stranded cable: Strip off the sheath, rub the core wire, and then connect the cable.
148
149 Single-core cable: Strip off the sheath and connect the cable.
150 )))
151 |...|...