Last modified by Iris on 2025/09/17 20:56

From version 2.3
edited by Iris
on 2025/09/17 19:41
Change comment: There is no comment for this version
To version 2.5
edited by Iris
on 2025/09/17 19:48
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -31,13 +31,13 @@
31 31  
32 32  This instruction is to complete the PID operation and is used to control the parameters of the closed-loop control system. PID control has a wide range of applications in mechanical equipment, pneumatic equipment, constant pressure water supply and electronic equipment, etc. among them:
33 33  
34 -[[image:11_html_1c6bb88c06ac24cf.png||class="img-thumbnail"]] is the target value of PID control;
34 +[[image:11_html_1c6bb88c06ac24cf.png]] is the target value of PID control;
35 35  
36 -[[image:11_html_fb5122fb6e3a43d5.png||class="img-thumbnail"]] is the measured feedback value;
36 +[[image:11_html_fb5122fb6e3a43d5.png]] is the measured feedback value;
37 37  
38 -[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] The starting address of the buffer area for setting parameters required for PID operation and saving intermediate results, occupies a total of 26 variable units in the subsequent addresses, the value range is D0 to D7974, it is best to specify the power failure retention area, which will remain after the power is OFF Set the value, otherwise the buffer area needs to be assigned value before starting the operation for the first time. The function and parameter description of each unit are described in this section;
38 +[[image:11_html_6c3fad4a32a3db43.png]] The starting address of the buffer area for setting parameters required for PID operation and saving intermediate results, occupies a total of 26 variable units in the subsequent addresses, the value range is D0 to D7974, it is best to specify the power failure retention area, which will remain after the power is OFF Set the value, otherwise the buffer area needs to be assigned value before starting the operation for the first time. The function and parameter description of each unit are described in this section;
39 39  
40 -[[image:11_html_b126b1b2673dc1f4.png||class="img-thumbnail"]] is the storage unit of the PID calculation result. Please designate [[image:11_html_d47cd1f59b766ed3.png||class="img-thumbnail"]] as a non-battery holding area, otherwise it needs to be initialized and cleared before starting the calculation for the first time.
40 +[[image:11_html_b126b1b2673dc1f4.png]] is the storage unit of the PID calculation result. Please designate [[image:11_html_d47cd1f59b766ed3.png]] as a non-battery holding area, otherwise it needs to be initialized and cleared before starting the calculation for the first time.
41 41  
42 42  **Programming example**
43 43  
... ... @@ -51,29 +51,29 @@
51 51  
52 52  The D130 unit is used to store the calculated control output value to control the execution of the action.
53 53  
54 -The function and setting method of the parameter value of each unit about starting of [[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] are described in the following table:
54 +The function and setting method of the parameter value of each unit about starting of [[image:11_html_6c3fad4a32a3db43.png]] are described in the following table:
55 55  
56 56  |**Unit**|**Features**|**Setting instructions**
57 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]]|Sampling time (TS)|The setting range is 1 to 32767 (ms), but it needs to be greater than the PLC program scan period
58 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +1|Action direction (ACT)|(((
57 +|[[image:11_html_6c3fad4a32a3db43.png]]|Sampling time (TS)|The setting range is 1 to 32767 (ms), but it needs to be greater than the PLC program scan period
58 +|[[image:11_html_6c3fad4a32a3db43.png]] +1|Action direction (ACT)|(((
59 59  bit0: 0 = positive action; 1 = reverse action bit3: 0 = unidirectional; 1 = bidirectional
60 60  
61 61  bit4: 0 = auto-tuning does not work; 1 = auto-tuning is executed, others cannot be used.
62 62  )))
63 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +2|Maximum ascent rate (DeltaT)|Setting range 0 to 32000 is the threshold of integral increment
64 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +3|Proportional gain (Kp)|Setting range 0 to 32767, note that this value is enlarged by 256 times, the actual value is Kp/256
65 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +4|Integral gain (Ki)|Setting range 0 to 32767, Ki=16384Ts/Ti, Ti is the integral time
66 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +5|Differential gain (Kd)|Setting range 0 to 32767, Kd≈Td/Ts, Td is the derivative time
67 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +6|Filtering (C0)|Setting range 0 to 1023, integral part filtering
68 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +7|Output lower limit|(((
63 +|[[image:11_html_6c3fad4a32a3db43.png]] +2|Maximum ascent rate (DeltaT)|Setting range 0 to 32000 is the threshold of integral increment
64 +|[[image:11_html_6c3fad4a32a3db43.png]] +3|Proportional gain (Kp)|Setting range 0 to 32767, note that this value is enlarged by 256 times, the actual value is Kp/256
65 +|[[image:11_html_6c3fad4a32a3db43.png]] +4|Integral gain (Ki)|Setting range 0 to 32767, Ki=16384Ts/Ti, Ti is the integral time
66 +|[[image:11_html_6c3fad4a32a3db43.png]] +5|Differential gain (Kd)|Setting range 0 to 32767, Kd≈Td/Ts, Td is the derivative time
67 +|[[image:11_html_6c3fad4a32a3db43.png]] +6|Filtering (C0)|Setting range 0 to 1023, integral part filtering
68 +|[[image:11_html_6c3fad4a32a3db43.png]] +7|Output lower limit|(((
69 69  Recommended setting range -2000 to 2000
70 70  
71 71  {{id name="OLE_LINK630"/}}When bit3 of S3+1=0, set to 0; When bit3 of S3+1=1, set to -2000;
72 72  )))
73 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +8|Output upper limit|Recommended setting value 2000
74 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +9|Reserved|Reserved
73 +|[[image:11_html_6c3fad4a32a3db43.png]] +8|Output upper limit|Recommended setting value 2000
74 +|[[image:11_html_6c3fad4a32a3db43.png]] +9|Reserved|Reserved
75 75  |︙|︙|︙
76 -|[[image:11_html_6c3fad4a32a3db43.png||class="img-thumbnail"]] +25|Reserved|Reserved
76 +|[[image:11_html_6c3fad4a32a3db43.png]] +25|Reserved|Reserved
77 77  
78 78  **Auto tuning example**
79 79  
... ... @@ -156,13 +156,20 @@
156 156  |4085H|When the device specified in the read application instructions (s1), (s2), (s3), (d) exceeds the range of the corresponding device.
157 157  |4086H|When the device specified in the write application instruction (s3) and (d) exceeds the range of the corresponding device.
158 158  |4D80H|The sampling time is out of range.​(T,,S,,≤0)
159 -|4D81H|Input filter constant (α) is out of range (α​<0 or α>1023)
160 -|4D82H|The maximum ascent rate (△//T//) is out of range.(△//T//​<0 or △//T//​>1023)
161 -|4D86H|The sampling time (Ts) is less than the operation cycle.​​​​​​​​​​​(T//s//<Scanning cycle)
162 -|4D87H|The proportional gain (K//p//) is out of range.​​​​(K//p//<1 or K//p//>32000)​​​​​​​
163 -|4D88H|The integral time constant (Ti) is out of range.(K//i​//<0 or K//i//>3600)
164 -|4D89H|The differential time constant (T//d//) is out of range.(K//d//<0 or K//d//>1000)
165 -|4D90H|The upper limit of CCPID output is less than the lower limit.
159 +|4D81H|Input filter constant (Co) is out of range (Co<0 or Co≥1023)
160 +|4D82H|The maximum ascent rate (△//T//) is out of range.(△//T//​<0 or △//T//​>32000)
161 +|4D83H|(((
162 +The proportional gain (Kp) is out of range. Kp<0[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps287.png]]
163 +)))
164 +|(((
165 +4D84H
166 +)))|(((
167 +The integral gain (Ki) is out of range. Ki<0[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps288.png]]
168 +)))
169 +|4D85H|(((
170 +The differential gain (Kd) is out of range. Kd<0[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps289.png]]
171 +)))
172 +|4D86H|The sampling time (Ts) is less than the operation cycle.​​​​(T//s//<Scan cycle)
166 166  
167 167  **Example**
168 168  
... ... @@ -327,13 +327,13 @@
327 327  
328 328  **Device used**
329 329  
330 -[[image:11_html_954290ac172c672b.jpg||class="img-thumbnail"]] is the target value (SV) of PID control;
337 +[[image:11_html_954290ac172c672b.jpg]] is the target value (SV) of PID control;
331 331  
332 -[[image:11_html_31f47ac5eec30067.jpg||class="img-thumbnail"]] is the measured feedback value (PV);
339 +[[image:11_html_31f47ac5eec30067.jpg]] is the measured feedback value (PV);
333 333  
334 -[[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] is the start address of the buffer area for setting parameters required for PID operation and saving intermediate results, occupying a total of 52 variable units of subsequent addresses (recommended to reserve 100 continuous spaces).The value range is D0 to D7,948, it is better to specify power failure retention, and the setting value remains after power supply is off. Otherwise,the buffer needs to be assigned value before starting the calculation for the first time. The function and parameter description of each unit are described in this section;
341 +[[image:11_html_6dcdd8fc88703a47.jpg]] is the start address of the buffer area for setting parameters required for PID operation and saving intermediate results, occupying a total of 52 variable units of subsequent addresses (recommended to reserve 100 continuous spaces).The value range is D0 to D7,948, it is better to specify power failure retention, and the setting value remains after power supply is off. Otherwise,the buffer needs to be assigned value before starting the calculation for the first time. The function and parameter description of each unit are described in this section;
335 335  
336 -[[image:11_html_7e06d96423d5de52.jpg||class="img-thumbnail"]] is the storage unit (MV) of the PID calculation result. Please specify it as a non-battery retentive area, otherwise it needs to be initialized and cleared before the first start of calculation.
343 +[[image:11_html_7e06d96423d5de52.jpg]] is the storage unit (MV) of the PID calculation result. Please specify it as a non-battery retentive area, otherwise it needs to be initialized and cleared before the first start of calculation.
337 337  
338 338  (% style="text-align:center" %)
339 339  [[image:11_html_8eeef07485b91193.jpg||class="img-thumbnail"]]
... ... @@ -348,13 +348,13 @@
348 348  
349 349  D130 unit is used to store the calculated control output value to control the execution of the action.
350 350  
351 -The functions and setting methods of the parameter values of each unit used by [[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] are described in the following table:
358 +The functions and setting methods of the parameter values of each unit used by [[image:11_html_6dcdd8fc88703a47.jpg]] are described in the following table:
352 352  
353 -[[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] to [[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] +14 is the parameter range that can be set (parameters set when CCPID is executed).
360 +[[image:11_html_6dcdd8fc88703a47.jpg]] to [[image:11_html_6dcdd8fc88703a47.jpg]] +14 is the parameter range that can be set (parameters set when CCPID is executed).
354 354  
355 -[[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] +15 to [[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] +21 is the space used internally by CCPID control.
362 +[[image:11_html_6dcdd8fc88703a47.jpg]] +15 to [[image:11_html_6dcdd8fc88703a47.jpg]] +21 is the space used internally by CCPID control.
356 356  
357 -[[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] +22 to [[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] +51 is the parameter space used in the auto-tuning process.
364 +[[image:11_html_6dcdd8fc88703a47.jpg]] +22 to [[image:11_html_6dcdd8fc88703a47.jpg]] +51 is the parameter space used in the auto-tuning process.
358 358  
359 359  |**Unit**|**Features**|**Setting instructions**|**Supplement**
360 360  | |Sample time (TS)|The set range is 1 to 32,767 (ms), but greater than PLC program scan cycle.|It is how often the instruction calculates and updates the output value (MV). When TS is less than one scan time, PID instruction is executed with one scan time and alarm 4D86H. When TS ≤ 0, alarm 4D80H and no execution.