Changes for page 11 PID Control Instruction
Last modified by Iris on 2025/09/17 20:56
Summary
-
Page properties (1 modified, 0 added, 0 removed)
-
Attachments (0 modified, 17 added, 0 removed)
- 1758111151287-920.png
- 1758111592778-873.png
- 1758111614838-309.png
- 1758111642557-547.png
- 1758111693192-390.png
- 1758111738993-165.png
- 1758111862269-781.png
- 1758113204827-229.png
- 1758113217569-229.png
- 1758113227549-844.png
- 1758113243743-809.png
- 1758113269397-376.png
- wps291.jpg
- 企业微信截图_17581105436817.png
- 企业微信截图_17581120459254.png
- 企业微信截图_17581134583885.png
- 企业微信截图_17581134696804.png
Details
- Page properties
-
- Content
-
... ... @@ -31,13 +31,13 @@ 31 31 32 32 This instruction is to complete the PID operation and is used to control the parameters of the closed-loop control system. PID control has a wide range of applications in mechanical equipment, pneumatic equipment, constant pressure water supply and electronic equipment, etc. among them: 33 33 34 -[[image:11_html_1c6bb88c06ac24cf.png ||class="img-thumbnail"]] is the target value of PID control;34 +[[image:11_html_1c6bb88c06ac24cf.png]] is the target value of PID control; 35 35 36 -[[image:11_html_fb5122fb6e3a43d5.png ||class="img-thumbnail"]] is the measured feedback value;36 +[[image:11_html_fb5122fb6e3a43d5.png]] is the measured feedback value; 37 37 38 -[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] The starting address of the buffer area for setting parameters required for PID operation and saving intermediate results, occupies a total of 26 variable units in the subsequent addresses, the value range is D0 to D7974, it is best to specify the power failure retention area, which will remain after the power is OFF Set the value, otherwise the buffer area needs to be assigned value before starting the operation for the first time. The function and parameter description of each unit are described in this section;38 +[[image:11_html_6c3fad4a32a3db43.png]] The starting address of the buffer area for setting parameters required for PID operation and saving intermediate results, occupies a total of 26 variable units in the subsequent addresses, the value range is D0 to D7974, it is best to specify the power failure retention area, which will remain after the power is OFF Set the value, otherwise the buffer area needs to be assigned value before starting the operation for the first time. The function and parameter description of each unit are described in this section; 39 39 40 -[[image:11_html_b126b1b2673dc1f4.png ||class="img-thumbnail"]] is the storage unit of the PID calculation result. Please designate [[image:11_html_d47cd1f59b766ed3.png||class="img-thumbnail"]] as a non-battery holding area, otherwise it needs to be initialized and cleared before starting the calculation for the first time.40 +[[image:11_html_b126b1b2673dc1f4.png]] is the storage unit of the PID calculation result. Please designate [[image:11_html_d47cd1f59b766ed3.png]] as a non-battery holding area, otherwise it needs to be initialized and cleared before starting the calculation for the first time. 41 41 42 42 **Programming example** 43 43 ... ... @@ -51,29 +51,29 @@ 51 51 52 52 The D130 unit is used to store the calculated control output value to control the execution of the action. 53 53 54 -The function and setting method of the parameter value of each unit about starting of [[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] are described in the following table:54 +The function and setting method of the parameter value of each unit about starting of [[image:11_html_6c3fad4a32a3db43.png]] are described in the following table: 55 55 56 56 |**Unit**|**Features**|**Setting instructions** 57 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]]|Sampling time (TS)|The setting range is 1 to 32767 (ms), but it needs to be greater than the PLC program scan period58 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +1|Action direction (ACT)|(((57 +|[[image:11_html_6c3fad4a32a3db43.png]]|Sampling time (TS)|The setting range is 1 to 32767 (ms), but it needs to be greater than the PLC program scan period 58 +|[[image:11_html_6c3fad4a32a3db43.png]] +1|Action direction (ACT)|((( 59 59 bit0: 0 = positive action; 1 = reverse action bit3: 0 = unidirectional; 1 = bidirectional 60 60 61 61 bit4: 0 = auto-tuning does not work; 1 = auto-tuning is executed, others cannot be used. 62 62 ))) 63 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +2|Maximum ascent rate (DeltaT)|Setting range 0 to 32000 is the threshold of integral increment64 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +3|Proportional gain (Kp)|Setting range 0 to 32767, note that this value is enlarged by 256 times, the actual value is Kp/25665 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +4|Integral gain (Ki)|Setting range 0 to 32767, Ki=16384Ts/Ti, Ti is the integral time66 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +5|Differential gain (Kd)|Setting range 0 to 32767, Kd≈Td/Ts, Td is the derivative time67 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +6|Filtering (C0)|Setting range 0 to 1023, integral part filtering68 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +7|Output lower limit|(((63 +|[[image:11_html_6c3fad4a32a3db43.png]] +2|Maximum ascent rate (DeltaT)|Setting range 0 to 32000 is the threshold of integral increment 64 +|[[image:11_html_6c3fad4a32a3db43.png]] +3|Proportional gain (Kp)|Setting range 0 to 32767, note that this value is enlarged by 256 times, the actual value is Kp/256 65 +|[[image:11_html_6c3fad4a32a3db43.png]] +4|Integral gain (Ki)|Setting range 0 to 32767, Ki=16384Ts/Ti, Ti is the integral time 66 +|[[image:11_html_6c3fad4a32a3db43.png]] +5|Differential gain (Kd)|Setting range 0 to 32767, Kd≈Td/Ts, Td is the derivative time 67 +|[[image:11_html_6c3fad4a32a3db43.png]] +6|Filtering (C0)|Setting range 0 to 1023, integral part filtering 68 +|[[image:11_html_6c3fad4a32a3db43.png]] +7|Output lower limit|((( 69 69 Recommended setting range -2000 to 2000 70 70 71 71 {{id name="OLE_LINK630"/}}When bit3 of S3+1=0, set to 0; When bit3 of S3+1=1, set to -2000; 72 72 ))) 73 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +8|Output upper limit|Recommended setting value 200074 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +9|Reserved|Reserved73 +|[[image:11_html_6c3fad4a32a3db43.png]] +8|Output upper limit|Recommended setting value 2000 74 +|[[image:11_html_6c3fad4a32a3db43.png]] +9|Reserved|Reserved 75 75 |︙|︙|︙ 76 -|[[image:11_html_6c3fad4a32a3db43.png ||class="img-thumbnail"]] +25|Reserved|Reserved76 +|[[image:11_html_6c3fad4a32a3db43.png]] +25|Reserved|Reserved 77 77 78 78 **Auto tuning example** 79 79 ... ... @@ -107,10 +107,8 @@ 107 107 108 108 **Example** 109 109 110 - Seemanual.110 +== **CCPID/CCPID calculation** == 111 111 112 -== {{id name="_Toc32463"/}}{{id name="_Toc21837"/}}{{id name="_Toc31152"/}}**CCPID/CCPID calculation** == 113 - 114 114 **CCPID** 115 115 116 116 This instruction is used to perform PID control that changes the output value according to the amount of input change. ... ... @@ -152,6 +152,7 @@ 152 152 153 153 **Error code** 154 154 153 + 155 155 |**Error code**|**Content** 156 156 |4085H|When the device specified in the read application instructions (s1), (s2), (s3), (d) exceeds the range of the corresponding device. 157 157 |4086H|When the device specified in the write application instruction (s3) and (d) exceeds the range of the corresponding device. ... ... @@ -158,8 +158,8 @@ 158 158 |4D80H|The sampling time is out of range.(T,,S,,≤0) 159 159 |4D81H|Input filter constant (α) is out of range (α<0 or α>1023) 160 160 |4D82H|The maximum ascent rate (△//T//) is out of range.(△//T//<0 or △//T//>1023) 161 -|4D86H|The sampling time (Ts) is less than the operation cycle. (T//s//<Scanning cycle)162 -|4D87H|The proportional gain (K//p//) is out of range.(K//p//<1 or K//p//>32000) 160 +|4D86H|The sampling time (Ts) is less than the operation cycle.(T//s//<Scanning cycle) 161 +|4D87H|The proportional gain (K//p//) is out of range.(K//p//<1 or K//p//>32000) 163 163 |4D88H|The integral time constant (Ti) is out of range.(K//i//<0 or K//i//>3600) 164 164 |4D89H|The differential time constant (T//d//) is out of range.(K//d//<0 or K//d//>1000) 165 165 |4D90H|The upper limit of CCPID output is less than the lower limit. ... ... @@ -166,9 +166,9 @@ 166 166 167 167 **Example** 168 168 169 -See " __CCPID Instruction Manual__".168 +See "CCPID Instruction Manual". 170 170 171 -== ** {{id name="_Toc8661"/}}{{id name="_Toc13227"/}}{{id name="_Toc18478"/}}{{id name="_Toc29418"/}}{{id name="_Toc5268"/}}{{id name="_Toc5168"/}}{{id name="_Toc307"/}}**FPID/FPID calculation ==170 +== **FPID/FPID calculation** == 172 172 173 173 **FPID** 174 174 ... ... @@ -327,13 +327,13 @@ 327 327 328 328 **Device used** 329 329 330 -[[image:11_html_954290ac172c672b.jpg ||class="img-thumbnail"]] is the target value (SV) of PID control;329 +[[image:11_html_954290ac172c672b.jpg]] is the target value (SV) of PID control; 331 331 332 -[[image:11_html_31f47ac5eec30067.jpg ||class="img-thumbnail"]] is the measured feedback value (PV);331 +[[image:11_html_31f47ac5eec30067.jpg]] is the measured feedback value (PV); 333 333 334 -[[image:11_html_6dcdd8fc88703a47.jpg ||class="img-thumbnail"]] is the start address of the buffer area for setting parameters required for PID operation and saving intermediate results, occupying a total of 52 variable units of subsequent addresses (recommended to reserve 100 continuous spaces).The value range is D0 to D7,948, it is better to specify power failure retention, and the setting value remains after power supply is off. Otherwise,the buffer needs to be assigned value before starting the calculation for the first time. The function and parameter description of each unit are described in this section;333 +[[image:11_html_6dcdd8fc88703a47.jpg]] is the start address of the buffer area for setting parameters required for PID operation and saving intermediate results, occupying a total of 52 variable units of subsequent addresses (recommended to reserve 100 continuous spaces).The value range is D0 to D7,948, it is better to specify power failure retention, and the setting value remains after power supply is off. Otherwise,the buffer needs to be assigned value before starting the calculation for the first time. The function and parameter description of each unit are described in this section; 335 335 336 -[[image:11_html_7e06d96423d5de52.jpg ||class="img-thumbnail"]] is the storage unit (MV) of the PID calculation result. Please specify it as a non-battery retentive area, otherwise it needs to be initialized and cleared before the first start of calculation.335 +[[image:11_html_7e06d96423d5de52.jpg]] is the storage unit (MV) of the PID calculation result. Please specify it as a non-battery retentive area, otherwise it needs to be initialized and cleared before the first start of calculation. 337 337 338 338 (% style="text-align:center" %) 339 339 [[image:11_html_8eeef07485b91193.jpg||class="img-thumbnail"]] ... ... @@ -348,17 +348,17 @@ 348 348 349 349 D130 unit is used to store the calculated control output value to control the execution of the action. 350 350 351 -The functions and setting methods of the parameter values of each unit used by [[image:11_html_6dcdd8fc88703a47.jpg ||class="img-thumbnail"]] are described in the following table:350 +The functions and setting methods of the parameter values of each unit used by [[image:11_html_6dcdd8fc88703a47.jpg]] are described in the following table: 352 352 353 -[[image:11_html_6dcdd8fc88703a47.jpg ||class="img-thumbnail"]] to [[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] +14 is the parameter range that can be set (parameters set when CCPID is executed).352 +[[image:11_html_6dcdd8fc88703a47.jpg]] to [[image:11_html_6dcdd8fc88703a47.jpg]] +14 is the parameter range that can be set (parameters set when CCPID is executed). 354 354 355 -[[image:11_html_6dcdd8fc88703a47.jpg ||class="img-thumbnail"]] +15 to [[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] +21 is the space used internally by CCPID control.354 +[[image:11_html_6dcdd8fc88703a47.jpg]] +15 to [[image:11_html_6dcdd8fc88703a47.jpg]] +21 is the space used internally by CCPID control. 356 356 357 -[[image:11_html_6dcdd8fc88703a47.jpg ||class="img-thumbnail"]] +22 to [[image:11_html_6dcdd8fc88703a47.jpg||class="img-thumbnail"]] +51 is the parameter space used in the auto-tuning process.356 +[[image:11_html_6dcdd8fc88703a47.jpg]] +22 to [[image:11_html_6dcdd8fc88703a47.jpg]] +51 is the parameter space used in the auto-tuning process. 358 358 359 359 |**Unit**|**Features**|**Setting instructions**|**Supplement** 360 -| 361 -|+1|Action direction (ACT)|((( 359 +|[[image:11_html_6dcdd8fc88703a47.jpg]]|Sample time (TS)|The set range is 1 to 32,767 (ms), but greater than PLC program scan cycle.|It is how often the instruction calculates and updates the output value (MV). When TS is less than one scan time, PID instruction is executed with one scan time and alarm 4D86H. When TS ≤ 0, alarm 4D80H and no execution. 360 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+1|Action direction (ACT)|((( 362 362 bit0: 0=positive action; 1=reverse action bit2: auto-tuning transition zone switch. 0=not open;1=open 363 363 364 364 bit3: 0=unidirection; 1=bidirection ... ... @@ -379,12 +379,12 @@ 379 379 380 380 bit4: **✎**When bit4=1 and bit6 and bit7 are not 1, auto-tuning is not executed. **✎**When bit4=0 and one of bit6 and bit7 is 1, auto-tuning is not executed. **✎**When bit4=1 and bit6 and bit7 are both 1, auto-tuning is executed 381 381 ))) 382 -|+2|Filter coefficient|The first-order inertia filter of feedback amount (0 to 100%) has a range of 0 to100|When the value is greater than or equal to 100, it will be executed as 0, that is, no filtering will be executed; 383 -|+3|Proportional gain(Kp)|Set range: 0 to 30,000[%]|Overrun error 4D87H 384 -|+4|Integration time (Ti)|Ti is integration time, and the range is 0 to 3,600 (s)|Overrun error 4D88H 385 -|+5|Differential time (Td)|Td is derivative time, and the range is 0 to 1,000 (s)|Overrun error 4D89H 386 -|+6|Working interval|Operating temperature setting enabled by PID (0 indicates no effect) The range is 0 to 1,000|It is recommended to be greater than 5°C, that is, 50 (precision 0.1°C). If it exceeds the range, the boundary value will be taken. 387 -|+7|Output low limit|((( 381 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+2|Filter coefficient|The first-order inertia filter of feedback amount (0 to 100%) has a range of 0 to100|When the value is greater than or equal to 100, it will be executed as 0, that is, no filtering will be executed; 382 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+3|Proportional gain(Kp)|Set range: 0 to 30,000[%]|Overrun error 4D87H 383 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+4|Integration time (Ti)|Ti is integration time, and the range is 0 to 3,600 (s)|Overrun error 4D88H 384 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+5|Differential time (Td)|Td is derivative time, and the range is 0 to 1,000 (s)|Overrun error 4D89H 385 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+6|Working interval|Operating temperature setting enabled by PID (0 indicates no effect) The range is 0 to 1,000|It is recommended to be greater than 5°C, that is, 50 (precision 0.1°C). If it exceeds the range, the boundary value will be taken. 386 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+7|Output low limit|((( 388 388 Range: -10,000 to 10,000. 389 389 390 390 Recommended setting range: -2,000 or 0 (when S3+1 bit3=0, the lower limit = 0; ... ... @@ -399,7 +399,7 @@ 399 399 400 400 2. During the control process, the lower limit is dynamically adjustable. If the lower limit is greater than or equal to the upper limit, error 4D90H will be reported. 401 401 ))) 402 -|+8|Output upper limit|((( 401 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+8|Output upper limit|((( 403 403 Value range: -10,000 to 10,000. 404 404 405 405 Recommended setting value is 2,000 ... ... @@ -412,7 +412,7 @@ 412 412 413 413 2. During the control process, the upper limit is dynamically adjustable. If the lower limit is greater than or equal to the upper limit, error 4D90H will be reported. 414 414 ))) 415 -|+9|Mode setting|((( 414 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+9|Mode setting|((( 416 416 0: Overshoot allowed 417 417 418 418 1: Slight overshoot or no overshoot ... ... @@ -423,44 +423,44 @@ 423 423 424 424 1: Slight overshoot or no overshoot mode (ukd = 300) 425 425 ))) 426 -|+10|((( 425 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+10|((( 427 427 Scale factor 428 428 429 429 (ukp) 430 430 )))|Typically sets value to 100 (default 100) [enabled when S3+9 is set to 2].The range is 1 to 500.|When the value is less than or equal to 0, or greater than 500, the boundary value will be taken. 431 -|+11|Integral coefficient (uki)|Typically sets value to 50 (default 50) [enabled when S3+9 is set to 2]. The range is 1 to 300.|When the value is less than or equal to 0, or greater than 300, the boundary value will be taken. 432 -|+12|Differential coefficient (ukd)|Typically sets value to 50 (default 100. 300 to 400 can be set when slight overshoot is required) [Enable when S3+9 is set to 2]. The range is 1 to 500.|When the value is less than or equal to 0, or greater than 500, the boundary value will be taken. 433 -|+13|Maximum ascent rate (DeltaT)|The range is 0 to 32,000, which is the threshold of integral increment|Overrun error 4D82H 434 -|+14|Filtering (C0)|The range is 0 to 1,023, integral part filtering|Overrun error 4D81H 435 -|+15|(% rowspan="3" %)reserved for internal control|(% rowspan="3" %)Internal control space occupation|(% rowspan="3" %) 430 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+11|Integral coefficient (uki)|Typically sets value to 50 (default 50) [enabled when S3+9 is set to 2]. The range is 1 to 300.|When the value is less than or equal to 0, or greater than 300, the boundary value will be taken. 431 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+12|Differential coefficient (ukd)|Typically sets value to 50 (default 100. 300 to 400 can be set when slight overshoot is required) [Enable when S3+9 is set to 2]. The range is 1 to 500.|When the value is less than or equal to 0, or greater than 500, the boundary value will be taken. 432 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+13|Maximum ascent rate (DeltaT)|The range is 0 to 32,000, which is the threshold of integral increment|Overrun error 4D82H 433 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+14|Filtering (C0)|The range is 0 to 1,023, integral part filtering|Overrun error 4D81H 434 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+15|(% rowspan="3" %)reserved for internal control|(% rowspan="3" %)Internal control space occupation|(% rowspan="3" %) 436 436 |┆ 437 -|+21 438 -|+22|(% rowspan="3" %)used space for self-tuning|(% rowspan="3" %)New self-tuning space for internal use|(% rowspan="3" %) 436 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+21 437 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+22|(% rowspan="3" %)used space for self-tuning|(% rowspan="3" %)New self-tuning space for internal use|(% rowspan="3" %) 439 439 |┆ 440 -|+51 439 +|[[image:11_html_6dcdd8fc88703a47.jpg]]+51 441 441 442 442 1) The auto-tuning process occupies the space of S3+22 to S3+51. When the auto-tuning is successful, the adjusted parameters will be written into the space of S3+2 to S3+21. 443 443 444 -2) +2 filter coefficient α: Processing in first-order inertial filter 443 +2)[[image:11_html_6dcdd8fc88703a47.jpg]] +2 filter coefficient α: Processing in first-order inertial filter 445 445 446 446 Formula: **T,,now,,=(100-α)×T,,α,,+α×T,,old,,** 447 447 448 448 T,,α ,,is the currently measured temperature. T,,old ,,is the temperature that participated in the PID calculation last time. T,,now ,,is the temperature used for the current PID calculation. α is the filter coefficient (when α=0, no filtering is performed, and the range of α is 0 to 100.(If there is a temperature with a small overshoot but a long stabilization time, the parameter can be set to 80, and analyze the specific problems in detail) 449 449 450 -3) +6 work range: Twork(example: 170 represents 17℃) 449 +3)[[image:11_html_6dcdd8fc88703a47.jpg]] +6 work range: Twork(example: 170 represents 17℃) 451 451 452 452 (% style="text-align:center" %) 453 -[[image: 11_html_7ab814bb49fffa5a.gif||class="img-thumbnail"]]452 +[[image:企业微信截图_17581105436817.png||height="197" width="652"]] 454 454 455 -4) +9 working mode: 454 +4) [[image:11_html_6dcdd8fc88703a47.jpg]]+9 working mode: 456 456 457 457 0: Working mode that allows overshoot 458 458 459 459 1: Slight overshoot or no overshoot working mode 460 460 461 -2: Custom settings; to achieve by setting +10, +11, +12 three coefficients. 460 +2: Custom settings; to achieve by setting [[image:1758111151287-920.png||height="15" width="28"]]+10, [[image:1758111151287-920.png||height="15" width="28"]]+11, [[image:1758111151287-920.png||height="15" width="28"]]+12 three coefficients. 462 462 463 -5) +1 bit2 self-tuning transition zone switch: (upper limit 1℃, low limit 0.5℃) 462 +5)[[image:11_html_6dcdd8fc88703a47.jpg]] +1 bit2 self-tuning transition zone switch: (upper limit 1℃, low limit 0.5℃) 464 464 465 465 The transition zone description in forward control: 466 466 ... ... @@ -546,7 +546,7 @@ 546 546 |D101|Control detail settings 547 547 |D102|First-order inertial filter coefficient 548 548 |D106|Working interval 549 -|D109| Operating mode548 +|D109|Working mode 550 550 551 551 **(4) Parameter control effect description** 552 552 ... ... @@ -615,11 +615,156 @@ 615 615 (% style="text-align:center" %) 616 616 [[image:11_html_74a7527eace55103.gif||class="img-thumbnail"]] 617 617 617 +== ** CCPIN_SHT operation** == 618 618 619 -** 11.6 LAGCDL Large time-delay temperature control instruction**619 +**CCPIN_SHT** 620 620 621 - [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps243.png]]**LAGCDL**621 +This instruction is used to perform PID control that changes the output value according to the variation of the input. 622 622 623 +-[CCPID_SHT (s1) (s2) (s3) (d)] 624 + 625 +**Content, range and data type** 626 + 627 +|**Parameter**|**Content**|**Range**|**Data type**|**Data type (label)** 628 +|(s1)|The device number that stores the target value (SV)|-32767 to 32767|Signed BIN 16 bit|ANY16 629 +|(s2)|The device number that stores the measured value (SV)|-32767 to 32767|Signed BIN 16 bit|ANY16 630 +|(s3)|The device number that stores parameters|1 to 32767|Signed BIN 16 bit|ANY16 631 +|(d)|The device number that stores the output value (SV)|-32767 to 32767|Signed BIN 16 bit|ANY16 632 + 633 +**Device used** 634 + 635 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="3" %)**Devices**|((( 636 +**Offset** 637 + 638 +**modification** 639 +)))|((( 640 +**Pulse** 641 + 642 +**extension** 643 +))) 644 +|**D**|**R**|**SD**|**[D]**|**XXP** 645 +|(% rowspan="4" %)CCPID_SHT|Parameter 1|●|●|●| | 646 +|Parameter 2|●|●|●| | 647 +|Parameter 3|●|●|●| | 648 +|Parameter 4|●|●|●| | 649 + 650 +**Features** 651 + 652 +This instruction is to complete the temperature control operation, used to control the parameters of the closed-loop control system. 653 + 654 +[[image:1758113204827-229.png]] is the target value of CCPID SHT control (SV). 655 + 656 +[[image:1758113217569-229.png]] is the measured feedback value (PV). 657 + 658 +[[image:1758113227549-844.png]] is the start address of the cache where the parameters required by CCPID_SHT operation and intermediate results are saved, 659 + 660 +occupying a total of 36 variable units of subsequent addresses. The value range is from D0 to D7946 or from R0 to R29964. It is better to specify power failure retention, and the setting value remains after power supply is off. Otherwise, the cache needs to be assigned value before starting the calculation for the first time. The function and parameter description of each unit are described in this section. 661 + 662 +[[image:1758113243743-809.png]] is the storage unit of the CCPID_SHT calculation result. Please specify it as a non-battery retentive area, otherwise it needs to be initialized and cleared before the first start of calculation. 663 + 664 +**Programming example** 665 + 666 +[[image:1758113269397-376.png]] 667 + 668 + 669 +The parameter description is as follows: 670 + 671 +The target value of CCPID_SHT adjustment is stored in D1, and D0 is the closed-loop feedback value. Note that D0 and D9 must be of the same dimension, such as both 0.01MPa units, or 1℃ units, etc.. 672 + 673 +A total of 36 units of D1000 to D1035 are used to store the set value and process value of CCPID_SHT operation. These values must be set item by item before the first CCPID_SHT calculation. 674 + 675 +D100 unit is used to store the calculated control output value to control the execution of the action. 676 + 677 +[[image:1758113227549-844.png]]The functions and setting methods of the parameter values of each unit at the beginning are described in the table below: 678 + 679 + [[image:1758113227549-844.png]]to[[image:1758113227549-844.png]] +15 is the parameter range that can be set (parameters set when CCPID_SHT is executed). 680 + 681 +[[image:1758113227549-844.png]]+2 to [[image:1758113227549-844.png]]+31 is the parameter space used in the self-tuning process. (This space is multiplexed with the parameter space during control) 682 + 683 + 684 +The functions and setting methods of the parameter values of each unit started by are described in the following table: 685 + 686 +|(% style="width:106px" %)**Unit**|(% style="width:146px" %)**Function**|**Description** 687 +|(% style="width:106px" %)[[image:1758113227549-844.png]]|(% style="width:146px" %)Sampling time (TS)|Range: 1 to 32767 (ms). It must be longer than PLC program scan cycle. 688 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+1|(% style="width:146px" %)Control flag bit|((( 689 +bit0: 0=Forward action; 1=Reverse action 690 + 691 +bit3: 0=one-way; 1=two-way 692 + 693 +bit4: 0=Self-tuning does not act; 1=Perform self-tuning and the others are not available. 694 + 695 +bit6: 0=Two-segment self-tuning does not act; 1=Perform two-segment self-tuning (bit4 must set to 1) 696 + 697 +bit7: 0=Three-segment self-tuning does not act; 1=Perform three-segment self-tuning (bit4 must set to 1) 698 + 699 +Bit15: The instruction initialization flag bit. When initialization is complete, it is set to 1. 700 +))) 701 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+2|(% style="width:146px" %)Maximum rate of increase (DeltaT)|Range: 0 to 32000. Threshold of integral increment 702 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+3|(% style="width:146px" %)Proportional gain (Kp)|Range: 0 to 32767. This value is magnified 256 times and the actual value is Kp/256. 703 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+4|(% style="width:146px" %)Integral gain (Ki)|Range: 0 to 32767, Ki=16384Ts/Ti,Ti is integral time 704 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+5|(% style="width:146px" %)Differential gain (Kd)|Range: 0 to 32767, Kd≈Td/Ts, Td is differential time 705 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+6|(% style="width:146px" %)Filter constant (Co)|Range: 0 to 1023, Integral partial filtering. 706 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+7|(% style="width:146px" %)Output lower limit|Recommended setting range: -2000 to 2000 707 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+8|(% style="width:146px" %)Output upper limit|Recommended setting value: 2000. When the upper and lower limits are both 0, the upper limit becomes 2000 and the lower limit becomes 0. 708 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+9|(% style="width:146px" %)Reserved|Reserved for internal use 709 +|(% style="width:106px" %)┇|(% style="width:146px" %)┇|┇ 710 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+35|(% style="width:146px" %)Reserved|Reserved for internal use 711 + 712 +Parameter space corresponding to the self-tuning time 713 + 714 +|(% style="width:106px" %)**Unit**|(% style="width:141px" %)**Function**|**Description** 715 +|(% style="width:106px" %)[[image:1758113227549-844.png]]|(% style="width:141px" %)Sampling time (TS)|Range: 1 to 32767 (ms). It must be longer than PLC program scan cycle. 716 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+1|(% style="width:141px" %)Control flag bit|((( 717 +bit0: 0=Forward action; 1=Reverse action 718 + 719 +bit3: 0=one-way; 1=two-way 720 + 721 +bit4: 0=Self-tuning does not act; 1=Perform self-tuning and the others are not available. 722 + 723 +bit6: 0=Two-segment self-tuning does not act; 1=Perform two-segment self-tuning (bit4 must set to 1) 724 + 725 +bit7: 0=Three-segment self-tuning does not act; 1=Perform three-segment self-tuning (bit4 must set to 1) 726 + 727 +Bit15: This instruction initializes the flag bit. When initialization is complete, the position is set to 1. 728 +))) 729 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+2|(% style="width:141px" %)Sampling time of PID running after self-tuning|Setting range: 1 to 32767 ms(). When Ts≦0, Ts=3000 730 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+3|(% style="width:141px" %)Coefficient ukp for PID parameter calculation|Setting range: 0 to 500. When ukp≦0, ukp=100; When ukp≧500, ukp=500. 731 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+4|(% style="width:141px" %)Coefficient uki for PID parameter calculation|Setting range: 0 to 32767. When uki≦0, uki=50. 732 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+5|(% style="width:141px" %)Coefficient ukd for PID parameter calculation|Setting range: 0 to 32767. When ukd≦0, ukd=50. 733 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+6|(% style="width:141px" %)Reserved|Reserved 734 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+7|(% style="width:141px" %)Output lower limit|Recommended setting range: -2000 to 2000 735 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+8|(% style="width:141px" %)Output upper limit|Recommended setting value: 2000. When the upper and lower limits are both 0, the upper limit becomes 2000 and the lower limit becomes 0. 736 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+9|(% style="width:141px" %)Reserved|Reserved for internal use 737 +|(% style="width:106px" %)┇|(% style="width:141px" %)┇|┇ 738 +|(% style="width:106px" %)[[image:1758113227549-844.png]]+35|(% style="width:141px" %)Reserved|Reserved for internal use 739 + 740 +**Error code** 741 + 742 +|**Error code**|**Content** 743 +|4085H|Read application instruction (S1), (S2), (S3) and (d) output results exceed the range of device. 744 +|4086H|The devices specified in write application instruction (S3) and (d) exceed the range of the corresponding device. 745 +|4DB0H|Sampling time (Ts) exceeds the range the object (Ts≦0) 746 +|4DB1H|Output filter constant (Co) exceeds the range the object (Co<0 or Co>1023) 747 +|4DB2H|Maximum rate of increase (DeltaT) exceeds the range the object (deltaT<0 or deltaT>32000) 748 +|4DB3H|Proportional gain (Kp) exceeds the range the object (Kp≦0) 749 +|4DB4H|Integral gain (Ki) exceeds the range the object (Ki≦0) 750 +|4DB5H|Differential gain (Kd) exceeds the range the object (Kd≦0) 751 +|4DB6H|Sampling time (Ts) < operation cycle 752 + 753 +**Example** 754 + 755 + 756 + 757 +(% style="text-align:center" %) 758 +[[image:企业微信截图_17581134583885.png]] 759 + 760 +(% style="text-align:center" %) 761 +[[image:企业微信截图_17581134696804.png]] 762 + 763 +== **LAGCDL Large time-delay temperature control instruction** == 764 + 765 +**LAGCDL** 766 + 623 623 This instruction is used to perform large time-delay system temperature control that changes the output value according to changes in the input. 624 624 625 625 -[LAGCDL (s1) (s2) (s3) (d)] ... ... @@ -634,7 +634,7 @@ 634 634 635 635 **Device used** 636 636 637 -|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan=" 24" %)**Devices**|(((781 +|(% rowspan="2" %)**Instruction**|(% rowspan="2" %)**Parameter**|(% colspan="8" %)**Devices**|((( 638 638 **Offset** 639 639 640 640 **modification** ... ... @@ -643,29 +643,29 @@ 643 643 644 644 **extension** 645 645 ))) 646 -|** X**|**Y**|**M**|**S**|**SM**|**T(bit)**|**C(bit)**|**LC(bit)**|**HSC(bit)**|**D.b**|**KnX**|**KnY**|**KnM**|**KnS**|**T**|**C**|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP**647 -|(% rowspan="4" %)LAGCDL|Parameter 1| | | | | | | | | | | | | | | | |●|●|●| | | | | | |648 -|Parameter 2| | | | | | | | | | | | | | | | |●|●|●| | | | | | |649 -|Parameter 3| | | | | | | | | | | | | | | | |●|●|●| | | | | | |650 -|Parameter 4| | | | | | | | | | | | | | | | |●|●|●| | | | | | |790 +|**D**|**R**|**SD**|**LC**|**HSC**|**K**|**H**|**E**|**[D]**|**XXP** 791 +|(% rowspan="4" %)LAGCDL|Parameter 1|●|●|●| | | | | | | 792 +|Parameter 2|●|●|●| | | | | | | 793 +|Parameter 3|●|●|●| | | | | | | 794 +|Parameter 4|●|●|●| | | | | | | 651 651 652 652 **Features** 653 653 654 654 This instruction is to complete large time-delay system control operation, and used to control the parameters of the closed-loop control system. 655 655 656 -[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps244.png]]800 +[[image:1758111592778-873.png]]is the target value of CCPID SHT control (SV). 657 657 658 -[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps245.png]]802 +[[image:1758111614838-309.png]]is the measured feedback value (PV). 659 659 660 -[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps246.png]]804 + [[image:1758111642557-547.png]]is the start address of the cache where the parameters required by LAGCDL operation and intermediate results are saved, 661 661 662 662 occupying a total of 634 variable units of subsequent addresses. The value range is from D0 to D7974 or from R0 to R35000. It is better to specify power failure retention, and the setting value remains after power supply is off. Otherwise, the cache needs to be assigned value before starting the calculation for the first time. The function and parameter description of each unit are described in this section. 663 663 664 -[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps247.png]] is the storage unit of the LAGCDL calculation result. Please specify it as a non-battery retentive area, otherwise it needs to be initialized and cleared before the first start of calculation.808 +[[image:1758111693192-390.png]] is the storage unit of the LAGCDL calculation result. Please specify it as a non-battery retentive area, otherwise it needs to be initialized and cleared before the first start of calculation. 665 665 666 666 **Programming example** 667 667 668 -[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps248.jpg]]812 +[[image:1758111738993-165.png||height="64" width="430"]] 669 669 670 670 The parameter description is as follows: 671 671 ... ... @@ -675,15 +675,15 @@ 675 675 676 676 D100 unit is used to store the calculated control output value to control the execution of the action. 677 677 678 -[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps249.png]] to [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps250.png]]+15 is the parameter range that can be set (parameters set when LAGCDL is executed). [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps251.png]]+28 to [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps252.png]]+631 is the historical data space for LAGCDL control internal use. [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps253.png]]+4 to [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps254.png]]+27 is the parameter space used in the self-tuning process. (This space is multiplexed with the parameter space during control)822 +[[image:1758111862269-781.png]] to [[image:1758111862269-781.png]]+15 is the parameter range that can be set (parameters set when LAGCDL is executed). [[image:1758111862269-781.png]]+28 to [[image:1758111862269-781.png]]+631 is the historical data space for LAGCDL control internal use. [[image:1758111862269-781.png]]+4 to [[image:1758111862269-781.png]]+27 is the parameter space used in the self-tuning process. (This space is multiplexed with the parameter space during control) 679 679 680 -The functions and setting methods of the parameter values of each unit started by [[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps255.png]] are described in the following table:824 +The functions and setting methods of the parameter values of each unit started by [[image:1758111862269-781.png]] are described in the following table: 681 681 682 682 683 683 684 -|**Unit**|**Function**|**Description** 685 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps256.png]]|Sampling time (TS)|Range: 1 to 32767 (ms). It must be longer than PLC program scan cycle.686 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps257.png]]+1|Control flag bit|(((828 +|(% style="width:108px" %)**Unit**|(% style="width:230px" %)**Function**|**Description** 829 +|(% style="width:108px" %)[[image:1758111862269-781.png]]|(% style="width:230px" %)Sampling time (TS)|Range: 1 to 32767 (ms). It must be longer than PLC program scan cycle. 830 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+1|(% style="width:230px" %)Control flag bit|((( 687 687 bit0: 0=Forward action; 1=Reverse action 688 688 689 689 bit1: Overshoot power limit output enable bit. 0=no limit; 1=limited ... ... @@ -696,32 +696,32 @@ 696 696 697 697 Bit15: The instruction initializes the flag bit. When initialization is complete, it is set to 1. 698 698 ))) 699 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps258.png]]+2|Output lower limit|Range: -32000 to 32000. Recommended setting range: -2000 or 0.700 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps259.png]]+3|Output upper limit|Range: 0 to 32000. Recommended setting value is 2000. When the upper and lower limits are both 0, the upper limit becomes 2000 and the lower limit becomes 0.701 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps260.png]]+4|Full power output boundary|The suggested value can be obtained by self-tuning, and can also be adjusted according to the actual situation.702 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps261.png]]+5|Half-power output boundary|The suggested value can be obtained by self-tuning, and can also be adjusted according to the actual situation.703 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps262.png]]+6|Stop output boundary|The suggested value can be obtained by self-tuning, and can also be adjusted according to the actual situation.704 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps263.png]]+7|The maximum rate of increase of the controlled system|Given by self-tuning705 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps264.png]]+8|The lagged time of the controlled system|Given by self-tuning. Unit: s706 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps265.png]]+9|The time constant of the controlled system|Given by self-tuning. Unit: s707 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps266.png]]+10|Ideal closed-loop time constant|Given by self-tuning. Unit: s708 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps267.png]]+11|Ideal closed-loop sampling time|Given by self-tuning. This parameter can be adjusted during the control process. Unit: s709 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps268.png]]+12|Maximum temperature difference during setting|Given by self-tuning. (for your reference)710 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps269.png]]+13|The temperature difference between the residual heat and temperature rise|Given by self-tuning. (for your reference)711 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps270.png]]+14|Heating time|Given by self-tuning. (for your reference)712 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps271.png]]+15|Setting time|Given by self-tuning. (for your reference)713 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps272.png]]+16|(% rowspan="3" %)Self-tuning use space|(% rowspan="3" %)Reserved for internal use714 -|┇ 715 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps273.png]]+27716 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps274.png]]+28|Current temperature difference|Used during control717 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps275.png]]+29|Previous temperature difference|Used during control718 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps276.png]]+30|The 1st operation flag bit|Used during control719 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps277.png]]+31|Number of valid history outputs|Used during control720 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps278.png]]+32|(% rowspan="3" %)Historical output data|(% rowspan="3" %)Used during control721 -|┇ 722 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps279.png]]+631723 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps280.png]]+632|(% rowspan="2" %)Previous sampling time stamp|(% rowspan="2" %)Reserved for internal use724 -|[[image: file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps281.png]]+633843 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+2|(% style="width:230px" %)Output lower limit|Range: -32000 to 32000. Recommended setting range: -2000 or 0. 844 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+3|(% style="width:230px" %)Output upper limit|Range: 0 to 32000. Recommended setting value is 2000. When the upper and lower limits are both 0, the upper limit becomes 2000 and the lower limit becomes 0. 845 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+4|(% style="width:230px" %)Full power output boundary|The suggested value can be obtained by self-tuning, and can also be adjusted according to the actual situation. 846 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+5|(% style="width:230px" %)Half-power output boundary|The suggested value can be obtained by self-tuning, and can also be adjusted according to the actual situation. 847 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+6|(% style="width:230px" %)Stop output boundary|The suggested value can be obtained by self-tuning, and can also be adjusted according to the actual situation. 848 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+7|(% style="width:230px" %)The maximum rate of increase of the controlled system|Given by self-tuning 849 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+8|(% style="width:230px" %)The lagged time of the controlled system|Given by self-tuning. Unit: s 850 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+9|(% style="width:230px" %)The time constant of the controlled system|Given by self-tuning. Unit: s 851 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+10|(% style="width:230px" %)Ideal closed-loop time constant|Given by self-tuning. Unit: s 852 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+11|(% style="width:230px" %)Ideal closed-loop sampling time|Given by self-tuning. This parameter can be adjusted during the control process. Unit: s 853 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+12|(% style="width:230px" %)Maximum temperature difference during setting|Given by self-tuning. (for your reference) 854 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+13|(% style="width:230px" %)The temperature difference between the residual heat and temperature rise|Given by self-tuning. (for your reference) 855 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+14|(% style="width:230px" %)Heating time|Given by self-tuning. (for your reference) 856 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+15|(% style="width:230px" %)Setting time|Given by self-tuning. (for your reference) 857 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+16|(% rowspan="3" style="width:230px" %)Self-tuning use space|(% rowspan="3" %)Reserved for internal use 858 +|(% style="width:108px" %)┇ 859 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+27 860 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+28|(% style="width:230px" %)Current temperature difference|Used during control 861 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+29|(% style="width:230px" %)Previous temperature difference|Used during control 862 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+30|(% style="width:230px" %)The 1st operation flag bit|Used during control 863 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+31|(% style="width:230px" %)Number of valid history outputs|Used during control 864 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+32|(% rowspan="3" style="width:230px" %)Historical output data|(% rowspan="3" %)Used during control 865 +|(% style="width:108px" %)┇ 866 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+631 867 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+632|(% rowspan="2" style="width:230px" %)Previous sampling time stamp|(% rowspan="2" %)Reserved for internal use 868 +|(% style="width:108px" %)[[image:1758111862269-781.png]]+633 725 725 726 726 **Error code** 727 727 ... ... @@ -736,8 +736,9 @@ 736 736 737 737 **Example** 738 738 739 -[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11524\wps282.png]] 740 740 884 +(% style="text-align:center" %) 885 +[[image:企业微信截图_17581120459254.png]] 741 741 742 742 == **PRUN/Octal digit transmission (16-bit data)** == 743 743
- 1758111151287-920.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +7.0 KB - Content
- 1758111592778-873.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +2.3 KB - Content
- 1758111614838-309.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +2.0 KB - Content
- 1758111642557-547.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +2.2 KB - Content
- 1758111693192-390.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +2.0 KB - Content
- 1758111738993-165.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +13.6 KB - Content
- 1758111862269-781.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +2.3 KB - Content
- 1758113204827-229.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +1.8 KB - Content
- 1758113217569-229.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +1.7 KB - Content
- 1758113227549-844.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +1.9 KB - Content
- 1758113243743-809.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +1.7 KB - Content
- 1758113269397-376.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +31.9 KB - Content
- wps291.jpg
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +42.2 KB - Content
- 企业微信截图_17581105436817.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +9.7 KB - Content
- 企业微信截图_17581120459254.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +42.1 KB - Content
- 企业微信截图_17581134583885.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +28.1 KB - Content
- 企业微信截图_17581134696804.png
-
- Author
-
... ... @@ -1,0 +1,1 @@ 1 +XWiki.Iris - Size
-
... ... @@ -1,0 +1,1 @@ 1 +23.9 KB - Content