... ... @@ -25,6 +25,20 @@
25 25  * The address of the bit address HDX is with a decimal point while word addresses are integers.
26 26  )))
27 27  
28 += Address ranges table =
29 +
30 +(% cellpadding="10" %)
31 +|=(% scope="row" style="width: 218px;" %)Address Type\HMI Series|=(% style="width: 228px;" %)General Series|=(% style="width: 200px;" %)i Series/HMI+ models|=(% style="width: 136px;" %)ie Series|=(% style="width: 232px;" %)ig Series
32 +|=(% style="width: 218px;" %)HDW|(% style="width:228px" %)HDW0-HDW299999|HDW0-HDW299999|HDW0-HDW299999|HDW0-HDW299999
33 +|=(% style="width: 218px;" %)HSW|(% style="width:228px" %)HSW0-HSW14999|HSW0-HSW14999|HSW0-HSW14999|HSW0-HSW14999
34 +|=(% style="width: 218px;" %)HAW|(% style="width:228px" %)HAW0-HAW199999|HAW0-HAW199999|HAW0-HAW199999|HAW0-HAW199999
35 +|=(% style="width: 218px;" %)HUW|(% style="width:228px" %)HUW0-HUW1599|HUW0-HUW1599|HUW0-HUW1599|HUW0-HUW1599
36 +|=(% style="width: 218px;" %)HDX|(% style="width:228px" %)HDX0.0-HDX299999.15|HDX0.0-HDX299999.15|HDX0.0-HDX299999.15|HDX0.0-HDX299999.15
37 +|=(% style="width: 218px;" %)HSX|(% style="width:228px" %)HSX0.0-HSX14999.15|HSX0.0-HSX14999.15|HSX0-HSX14999.15|HSX0.0-HSX14999.15
38 +|=(% style="width: 218px;" %)HAX|(% style="width:228px" %)HAX0.0-HAX199999.15|HAX0.0-HAX199999.15|HAX0.0-HAX199999.15|HAX0.0-HAX199999.15
39 +|=(% style="width: 218px;" %)HUX|(% style="width:228px" %)HUX0.0-HUX1599.15|HUX0.0-HUX1599.15|HUX0.0-HUX1599.15|HUX0.0-HUX1599.15
40 +|=(% style="width: 218px;" %)RPW|(% style="width:228px" %) |RPW000000-RPW990450|RPW000000-RPW990450|RPW000000-RPW990450
41 +
28 28  = **Data storage area (HDW/HDX)** =
29 29  
30 30  It is used to save the temporary data of project.
... ... @@ -593,6 +593,9 @@
593 593  * =0: Server connection exception
594 594  * =1: Server connection is OK
595 595  )))
610 +|=(% style="width: 160px;" %)HSW1740|(% style="width:282px" %)Wi-fi signal strength|(% style="width:452px" %)(((
611 +Display the value of Wi-fi signal signal strength, ranges from 0~~100 (Signal strength is automatically obtained only once when HMI is powered on, and it will not be automatically updated. It needs to be used with the HSW1890)
612 +)))
596 596  |=(% style="width: 160px;" %)HSW1741|(% colspan="1" rowspan="12" style="width:282px" %)Related IP register in 4Gnetwork status (It is valid when HMI is connected to 4G)|(% style="width:452px" %)Local IP address high byte 1
597 597  |=(% style="width: 160px;" %)HSW1742|(% style="width:452px" %)Local IP address high byte 2
598 598  |=(% style="width: 160px;" %)HSW1743|(% style="width:452px" %)Local IP address high byte 3
... ... @@ -792,6 +792,8 @@
792 792  |=(% style="width: 160px;" %)HSW1853|(% style="width:282px" %)File format for exporting data records to USB flash drive or SD card|(% style="width:452px" %)(((
793 793  * =0: db database
794 794  * =1: CSV
812 +
813 +(Only valid for script function DbToCsvFile)
795 795  )))
796 796  |=(% style="width: 160px;" %)HSW1854|(% style="width:282px" %)High and low word conversion type|(% style="width:452px" %)(((
797 797  * =0: use the old high-low word conversion (default)
... ... @@ -818,7 +818,7 @@
818 818  * =1: priority WLAN
819 819  * =2: priority 4G
820 820  )))
821 -|=(% style="width: 160px;" %)HSW1866|(% style="width:282px" %)Delete the LUa extension module file|(% style="width:452px" %)(((
840 +|=(% style="width: 160px;" %)HSW1866|(% style="width:282px" %)Delete the Lua extension module file|(% style="width:452px" %)(((
822 822  * =0: delete;
823 823  * = Others: do not delete
824 824  )))
... ... @@ -887,6 +887,15 @@
887 887  |=(% style="width: 160px;" %)(((
888 888  HSW1879
889 889  )))|(% style="width:452px" %)Ethernet1 Local DNS2 address high byte 4
909 +|=(% style="width: 160px;" %)HSW1890|(% colspan="1" style="width:282px" %)Enable refresh current network signal|(% style="width:452px" %)(((
910 +* =1: Refresh the network signal once after triggered (This register will be automatically reset after triggered, only update the signal value once after per 15 seconds, not able to update twice in the short interval)
911 +* =Others: not refresh
912 +)))
913 +|=(% style="width: 160px;" %)HSW1891|(% colspan="1" style="width:282px" %)Enable clear cache for screen data  |(% style="width:452px" %)(((
914 +* =1, not clear screen cache when switch language
915 +* =2, trigger clear cache of all screens for once time
916 +* =3, always clear cache of all screen data
917 +)))
890 890  |=(% style="width: 160px;" %)HSW10000~~19999|(% style="width:282px" %)Power-down storage area|(% style="width:452px" %)After restart, the data remains
891 891  |=(% style="width: 160px;" %)HSW10035|(% rowspan="13" style="width:282px" %)(((
892 892  Note: Valid when Ethernet1 of HMI is plugged into the network cable.