Changes for page 13 HMI Internal Registers

Last modified by Jett on 2025/04/28 16:07

From version 4.3
edited by Stone Wu
on 2022/08/06 14:11
Change comment: There is no comment for this version
To version 16.1
edited by Hunter
on 2023/01/14 11:08
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Stone
1 +XWiki.Hunter
Content
... ... @@ -4,11 +4,11 @@
4 4  
5 5  *HSW, HDW, HUW, HAW are word address, HSX, HDX, HUX, HAX are bit address.
6 6  
7 -1. **System data area (HSW): **A special register defined by the system.
8 -1. **Data storage area (HDW/HDX): **Users store user data.
9 -1. **System data area (HUW): **A special register defined by the system.
10 -1. **System Data (HAW)**: System register used for power-off save.
11 -1. **Recipe index area (RPW): **System register used for recipe index.
7 +* **System data area (HSW): **A special register defined by the system.
8 +* **Data storage area (HDW/HDX): **Users store user data.
9 +* **System data area (HUW): **A special register defined by the system.
10 +* **System Data (HAW)**: System register used for power-off save.
11 +* **Recipe index area (RPW): **System register used for recipe index.
12 12  
13 13  HMI internal registers are divided into bit address and word address, which can be accessed in two ways (take HDW as an example).
14 14  
... ... @@ -241,8 +241,8 @@
241 241  * =2: HSX521.1=1, delete all trend graph.
242 242  * =4: HSX521.2=1, delete all alarms.
243 243  * =16: HSX521.4=1, delete history XY plot.
244 -* =32: HSX521.5=1, delete data records in SD card or flash dish;(Please make a setting which is saved to flash disk or SD card in project setting).
245 -* =64: HSX521.6=1, delete alarms records in SD card or flash dish; (Please make a setting which is saved to flash disk or SD card in project setting).
244 +* =32: HSX521.5=1, delete data records in SD card or USB flash disk;(Please make a setting which is saved to USB flash disk or SD card in project setting).
245 +* =64: HSX521.6=1, delete alarms records in SD card or USB flash disk; (Please make a setting which is saved to USB flash disk or SD card in project setting).
246 246  )))
247 247  |=(% style="width: 160px;" %)HSW522|(% style="width:282px" %)Copy and paste the alarm/data files in flash to the USB flash disk|(% style="width:452px" %)(((
248 248  * =0: No operation
... ... @@ -485,6 +485,8 @@
485 485  * =0, Default value
486 486  * =1, Release the alarm generated before the last power-down when starting up
487 487  )))
488 +|=(% style="width: 160px;" %)HSW1200|(% colspan="1" rowspan="2" style="width:282px" %)TSAP settings for HMI in the Siemens LOGO! 8 protocol(ig series or HMI V2.0)|(% style="width:452px" %)HMI local TSAP, which corresponds to the remote TSAP of PLC
489 +|=(% style="width: 160px;" %)HSW1201|(% style="width:452px" %)HMI remote TSAP, which corresponds to the local TSAP of PLC
488 488  |=(% style="width: 160px;" %)HSW1450|(% style="width:282px" %)Enable objects level password function|(% style="width:452px" %)(((
489 489  * =0, Disable
490 490  * =1, Enable
... ... @@ -618,6 +618,174 @@
618 618  * =1: Server connection is OK
619 619  )))
620 620  |=(% style="width: 160px;" %)HSW1761|(% style="width:282px" %)Display 4G network signal strength|(% style="width:452px" %)Signal strength: 0~~31. The greater the value ,the signal is stronger
623 +|=(% style="width: 160px;" %)(((
624 +HSW1762
625 +)))|(% colspan="1" rowspan="13" style="width:282px" %)(((
626 +Note: Valid when Ethernet2 of HMI is plugged into the network cable.
627 +①、When the Ethernet setting is enabled in the project parameters, this register displays the set value.
628 +②. When the Ethernet setting is not enabled in the engineering parameters, the register displays the Ethernet IP automatically acquired by the HMI.
629 +③. When the HMI is not plugged into the network cable, the register will show 0 whether the engineering parameters are set or not.
630 +④.IP related registers can be read and written (only static IP mode can be written).
631 +)))|(% style="width:452px" %)(((
632 +Ethernet2 Local IP address high byte 1
633 +)))
634 +|=(% style="width: 160px;" %)(((
635 +HSW1763
636 +)))|(% style="width:452px" %)(((
637 +Ethernet2 Local IP address high byte 2
638 +)))
639 +|=(% style="width: 160px;" %)(((
640 +HSW1764
641 +)))|(% style="width:452px" %)(((
642 +Ethernet2 Local IP address high byte 3
643 +)))
644 +|=(% style="width: 160px;" %)(((
645 +HSW1765
646 +)))|(% style="width:452px" %)(((
647 +Ethernet2 Local IP address high byte 4
648 +)))
649 +|=(% style="width: 160px;" %)(((
650 +HSW1766
651 +)))|(% style="width:452px" %)(((
652 +Ethernet2 Local mask IP address high byte 1
653 +)))
654 +|=(% style="width: 160px;" %)(((
655 +HSW1767
656 +)))|(% style="width:452px" %)(((
657 +Ethernet2 Local mask IP address high byte 2
658 +)))
659 +|=(% style="width: 160px;" %)(((
660 +HSW1768
661 +)))|(% style="width:452px" %)Ethernet2 Local mask IP address high byte 3
662 +|=(% style="width: 160px;" %)HSW1769|(% style="width:452px" %)Ethernet2 Local mask IP address high byte 4
663 +|=(% style="width: 160px;" %)(((
664 +HSW1770
665 +)))|(% style="width:452px" %)(((
666 +Ethernet2 Local gateway IP address high byte 1
667 +)))
668 +|=(% style="width: 160px;" %)(((
669 +HSW1771
670 +)))|(% style="width:452px" %)(((
671 +Ethernet2 Local gateway IP address high byte 2
672 +)))
673 +|=(% style="width: 160px;" %)(((
674 +HSW1772
675 +)))|(% style="width:452px" %)(((
676 +Ethernet2 Local gateway IP address high byte 3
677 +)))
678 +|=(% style="width: 160px;" %)(((
679 +HSW1773
680 +)))|(% style="width:452px" %)(((
681 +Ethernet2 Local gateway IP address high byte 4
682 +)))
683 +|=(% style="width: 160px;" %)(((
684 +HSW1774
685 +)))|(% style="width:452px" %)(((
686 +Ethernet2 Local Port Address
687 +)))
688 +|=(% style="width: 160px;" %)(((
689 +HSW1775
690 +)))|(% colspan="1" rowspan="6" style="width:282px" %)(((
691 +①Display the MAC code of Ethernet2 NIC
692 +
693 +(hexadecimal display)
694 +
695 +②Read-only mode, not modifiable
696 +)))|(% style="width:452px" %)(((
697 +Ethernet2 Local MAC code high byte 1
698 +)))
699 +|=(% style="width: 160px;" %)(((
700 +HSW1776
701 +)))|(% style="width:452px" %)(((
702 +Ethernet2 Local MAC code high byte 2
703 +)))
704 +|=(% style="width: 160px;" %)(((
705 +HSW1777
706 +)))|(% style="width:452px" %)(((
707 +Ethernet2 Local MAC code high byte 3
708 +)))
709 +|=(% style="width: 160px;" %)(((
710 +HSW1778
711 +)))|(% style="width:452px" %)(((
712 +Ethernet2 Local MAC code high byte 4
713 +)))
714 +|=(% style="width: 160px;" %)(((
715 +HSW1779
716 +)))|(% style="width:452px" %)(((
717 +Ethernet2 Local MAC code high byte 5
718 +)))
719 +|=(% style="width: 160px;" %)(((
720 +HSW1780
721 +)))|(% style="width:452px" %)(((
722 +Ethernet2 Local MAC code high byte 6
723 +)))
724 +|=(% style="width: 160px;" %)(((
725 +HSW1781
726 +)))|(% colspan="1" rowspan="8" style="width:282px" %)(((
727 +①Display and modify DNS1 and DNS2 of Ethernet2
728 +
729 +②Related registers can be read and written mode (only static IP mode can be written)
730 +)))|(% style="width:452px" %)(((
731 +Ethernet2 Local DNS1 address high byte 1
732 +)))
733 +|=(% style="width: 160px;" %)(((
734 +HSW1782
735 +)))|(% style="width:452px" %)(((
736 +Ethernet2 Local DNS1 address high byte 2
737 +)))
738 +|=(% style="width: 160px;" %)(((
739 +HSW1783
740 +)))|(% style="width:452px" %)(((
741 +Ethernet2 Local DNS1 address high byte 3
742 +)))
743 +|=(% style="width: 160px;" %)(((
744 +HSW1784
745 +)))|(% style="width:452px" %)(((
746 +Ethernet2 Local DNS1 address high byte 4
747 +)))
748 +|=(% style="width: 160px;" %)(((
749 +HSW1785
750 +)))|(% style="width:452px" %)(((
751 +Ethernet2 Local DNS2 address high byte 1
752 +)))
753 +|=(% style="width: 160px;" %)(((
754 +HSW1786
755 +)))|(% style="width:452px" %)(((
756 +Ethernet2 Local DNS2 address high byte 2
757 +)))
758 +|=(% style="width: 160px;" %)(((
759 +HSW1787
760 +)))|(% style="width:452px" %)(((
761 +Ethernet2 Local DNS2 address high byte 3
762 +)))
763 +|=(% style="width: 160px;" %)(((
764 +HSW1788
765 +)))|(% style="width:452px" %)(((
766 +Ethernet2 Local DNS2 address high byte 4
767 +)))
768 +|=(% style="width: 160px;" %)(((
769 +HSW1789
770 +)))|(% colspan="1" style="width:282px" %)(((
771 +Display or set the dynamic or static IP mode of Ethernet2
772 +)))|(% style="width:452px" %)(((
773 +HSX1789.0 = 0, Static IP mode
774 +
775 +HSX1789.0 = 1, dynamic IP mode
776 +)))
777 +|=(% style="width: 160px;" %)(((
778 +HSW1790
779 +)))|(% colspan="1" style="width:282px" %)(((
780 +Confirm Ethernet2 IP, subnet mask, gateway, DNS1, DNS2, and dynamic static IP settings
781 +)))|(% style="width:452px" %)(((
782 +~= 1, confirm the setting (i.e., after modifying IP-related information, set this address to 1, representing confirmation of the modification, after which it will be reset to 0)
783 +)))
784 +|=(% style="width: 160px;" %)(((
785 +HSW1791
786 +)))|(% colspan="1" style="width:282px" %)(((
787 +Network status of the Ethernet2 connection server
788 +)))|(% style="width:452px" %)(((
789 +~= 0, connection to the server is abnormal = 1, connection to the server is normal
790 +)))
621 621  |=(% style="width: 160px;" %)HSW1852|(% style="width:282px" %)Control the interval in two consecutive clicks|(% style="width:452px" %)Limit range: 1~~500ms. The default is 100 ms.
622 622  |=(% style="width: 160px;" %)HSW1853|(% style="width:282px" %)File format for exporting data records to USB flash drive or SD card|(% style="width:452px" %)(((
623 623  * =0: db database
... ... @@ -643,14 +643,87 @@
643 643  * =1: download firmware
644 644  * =2: enter the background
645 645  )))
816 +|=(% style="width: 160px;" %)HSW1865|(% style="width:282px" %)Priority connection to the cloud|(% style="width:452px" %)(((
817 +* =0: priority Ethernet
818 +* =1: priority WLAN
819 +* =2: priority 4G
820 +)))
821 +|=(% style="width: 160px;" %)HSW1866|(% style="width:282px" %)Delete the LUa extension module file|(% style="width:452px" %)(((
822 +* =0: delete;
823 +* = Others: do not delete
824 +)))
825 +|=(% style="width: 160px;" %)HSW1867|(% style="width:282px" %)Reset mode|(% style="width:452px" %)(((
826 +Monitor address is set during reset of reset switch, whether to cancel reset,
827 +
828 +* = 0: yes (default);
829 +* = 1: no
830 +)))
831 +|=(% style="width: 160px;" %)HSW1868|(% style="width:282px" %)Double-click or long press the record type table mode|(% style="width:452px" %)(((
832 +Controls whether the button pops up when double-clicking or long pressing on record type table object
833 +
834 +* = 0: yes (default);
835 +* = 1: no
836 +)))
837 +|=(% style="width: 160px;" %)(((
838 +HSW1869
839 +)))|(% style="width:282px" %)(((
840 +Dynamic screensaver countdown
841 +)))|(% style="width:452px" %)(((
842 +Countdown to enter dynamic screensaver effect, unit (S)
843 +)))
844 +|=(% style="width: 160px;" %)(((
845 +HSW1870
846 +)))|(% style="width:282px" %)(((
847 +Display or set the dynamic or static IP mode of Ethernet1
848 +)))|(% style="width:452px" %)(((
849 +HSX1870.0 = 0, Static IP mode
850 +
851 +HSX1870.0 = 1, dynamic IP mode
852 +)))
853 +|=(% style="width: 160px;" %)(((
854 +HSW1871
855 +)))|(% style="width:282px" %)(((
856 +Confirm the IP, subnet mask, gateway, DNS1, DNS2, and dynamic static IP settings for Ethernet1
857 +)))|(% style="width:452px" %)(((
858 +~= 1, confirm the setting (i.e., after modifying IP-related information, set this address to 1, representing confirmation of the modification, after which it will be reset to 0)
859 +)))
860 +|=(% style="width: 160px;" %)(((
861 +HSW1872
862 +)))|(% colspan="1" rowspan="8" style="width:282px" %)(((
863 +①Display and modify DNS1 and DNS2 of Ethernet1
864 +
865 +②Related registers can be read and written mode (only static IP mode can be written)
866 +)))|(% style="width:452px" %)(((
867 +Ethernet1 Local DNS1 address high byte 1
868 +)))
869 +|=(% style="width: 160px;" %)(((
870 +HSW1873
871 +)))|(% style="width:452px" %)Ethernet1 Local DNS1 address high byte 2
872 +|=(% style="width: 160px;" %)(((
873 +HSW1874
874 +)))|(% style="width:452px" %)Ethernet1 Local DNS1 address high byte 3
875 +|=(% style="width: 160px;" %)(((
876 +HSW1875
877 +)))|(% style="width:452px" %)Ethernet1 Local DNS1 address high byte 4
878 +|=(% style="width: 160px;" %)(((
879 +HSW1876
880 +)))|(% style="width:452px" %)Ethernet1 Local DNS2 address high byte 1
881 +|=(% style="width: 160px;" %)(((
882 +HSW1877
883 +)))|(% style="width:452px" %)Ethernet1 Local DNS2 address high byte 2
884 +|=(% style="width: 160px;" %)(((
885 +HSW1878
886 +)))|(% style="width:452px" %)Ethernet1 Local DNS2 address high byte 3
887 +|=(% style="width: 160px;" %)(((
888 +HSW1879
889 +)))|(% style="width:452px" %)Ethernet1 Local DNS2 address high byte 4
646 646  |=(% style="width: 160px;" %)HSW10000~~19999|(% style="width:282px" %)Power-down storage area|(% style="width:452px" %)After restart, the data remains
647 647  |=(% style="width: 160px;" %)HSW10035|(% rowspan="13" style="width:282px" %)(((
648 -**✎Note: **Only valid when the HMI is plugged into the Ethernet cable.
649 -
650 -1. If Ethernet settings is enabled in project parameters, this register displays the set value.
651 -1. If Ethernet settings is not enabled in project parameters, IP would automatically obtained IP.
652 -1. If HMI is not connected to the network, the register is displayed as 0 whether the engineering parameters are set.
653 -1. 4. All IP registers of HMI are read-only.
892 +Note: Valid when Ethernet1 of HMI is plugged into the network cable.
893 +①、When the Ethernet setting is enabled in the project parameters, this register displays the set value.
894 +②. When the Ethernet setting is not enabled in the engineering parameters, the register displays the Ethernet IP automatically acquired by the HMI.
895 +③. When the HMI is not plugged into the network cable, the register will show 0 whether the engineering parameters are set or not.
896 +④.IP related registers can be read and written (only static IP mode can be written).
654 654  )))|(% style="width:452px" %)Local IP address high byte 1
655 655  |=(% style="width: 160px;" %)HSW10036|(% style="width:452px" %)Local IP address high byte 2
656 656  |=(% style="width: 160px;" %)HSW10037|(% style="width:452px" %)Local IP address high byte 3
... ... @@ -665,9 +665,11 @@
665 665  |=(% style="width: 160px;" %)HSW10046|(% style="width:452px" %)Local gateway address high byte 4
666 666  |=(% style="width: 160px;" %)HSW10047|(% style="width:452px" %)Local port address
667 667  |=(% style="width: 160px;" %)HSW10048|(% rowspan="6" style="width:282px" %)(((
668 -Displays the MAC code of the current network card
911 +Display the MAC code of Ethernet1 NIC
669 669  
670 -(Hexadecimal display)
913 +(hexadecimal display)
914 +
915 +②Read-only mode, not modifiable
671 671  )))|(% style="width:452px" %)Local MAC code high word 1
672 672  |=(% style="width: 160px;" %)HSW10049|(% style="width:452px" %)Local MAC code high word 2
673 673  |=(% style="width: 160px;" %)HSW10050|(% style="width:452px" %)Local MAC code high word 3
... ... @@ -674,7 +674,7 @@
674 674  |=(% style="width: 160px;" %)HSW10051|(% style="width:452px" %)Local MAC code high word 4
675 675  |=(% style="width: 160px;" %)HSW10052|(% style="width:452px" %)Local MAC code high word 5
676 676  |=(% style="width: 160px;" %)HSW10053|(% style="width:452px" %)Local MAC code high word 6
677 -|=(% style="width: 160px;" %)HSW10118|(% colspan="1" rowspan="2" style="width:282px" %)TSAP settings for HMI in the Siemens logo! 8 protocol|(% style="width:452px" %)HMI local TSAP, which corresponds to the remote TSAP of PLC
922 +|=(% style="width: 160px;" %)HSW10118|(% colspan="1" rowspan="2" style="width:282px" %)TSAP settings for HMI in the Siemens LOGO! 8 protocol|(% style="width:452px" %)HMI local TSAP, which corresponds to the remote TSAP of PLC
678 678  |=(% style="width: 160px;" %)HSW10119|(% style="width:452px" %)HMI remote TSAP, which corresponds to the local TSAP of PLC
679 679  |=(% style="width: 160px;" %)HSW10461~~10493|(% style="width:282px" %)Remote access password|(% style="width:452px" %)8-character remote access password
680 680  |=(% style="width: 160px;" %)HSW10494~~10558|(% style="width:282px" %)Machine ID (Read only)|(% style="width:452px" %)Machine ID for remote access (read only 64-bit)
... ... @@ -756,11 +756,38 @@
756 756  )))
757 757  |=(% style="width: 160px;" %)HSW11760|(% style="width:282px" %)Screensaver countdown|(% style="width:452px" %)Display the countdown to enter the Screensaver, unit: second.
758 758  |=(% style="width: 160px;" %)HSW11761|(% style="width:282px" %)Screensaver screen number|(% style="width:452px" %)Set the screen number for Screensaver
1004 +|=(% style="width: 160px;" %)(((
1005 +HSW11762
1006 +)))|(% style="width:282px" %)(((
1007 +Dynamic screensaver control address
1008 +)))|(% style="width:452px" %)(((
1009 +HSX11762.0=0, initialize with project configuration;
759 759  
760 -== **Serial port communication configuration** ==
1011 +HSX11762.0=1, initialize with special register configuration;
761 761  
1013 +HSX11762.1=0, disable dynamic screensaver;
1014 +
1015 +HSX11762.1=1, enable dynamic screensaver
1016 +)))
1017 +|=(% style="width: 160px;" %)(((
1018 +HSW11763
1019 +)))|(% style="width:282px" %)(((
1020 +Waiting time to enter the dynamic screensaver
1021 +)))|(% style="width:452px" %)(((
1022 +Waiting time when the screen is not operated, range 1~~720 minutes
1023 +)))
1024 +|=(% style="width: 160px;" %)(((
1025 +HSW11764
1026 +)))|(% style="width:282px" %)(((
1027 +Animated screensaver animation type
1028 +)))|(% style="width:452px" %)(((
1029 +~=0: Raster,=1: Blinds,=2: Bubble
1030 +)))
1031 +
1032 +== Serial port communication configuration ==
1033 +
762 762  (% class="table-bordered" %)
763 -|=(% style="width: 102px;" %)Port|=(% style="width: 173px;" %)**Function**|=(% style="width: 122px;" %)**Address**|=(% colspan="2" style="width: 506px;" %)**Description**
1035 +|=(% scope="row" style="width: 102px;" %)Port|=(% style="width: 173px;" %)**Function**|=(% style="width: 122px;" %)**Address**|=(% colspan="2" style="width: 506px;" %)**Description**
764 764  |(% colspan="1" rowspan="11" style="width:102px" %)COM1|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10061|(% colspan="2" style="width:506px" %)(((
765 765  * =0: RS232
766 766  * =1: RS485
... ... @@ -790,10 +790,22 @@
790 790  * =1: ODD
791 791  * =2: EVEN
792 792  )))
793 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10066|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
794 -|(% style="width:173px" %)reveive timeout|(% style="width:122px" %)HSW10067|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
795 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10068|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
796 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10069|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~300
1065 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10066|(% colspan="2" style="width:506px" %)(((
1066 +* Unit: ms.
1067 +* Range: 0 to 30000
1068 +)))
1069 +|(% style="width:173px" %)reveive timeout|(% style="width:122px" %)HSW10067|(% colspan="2" style="width:506px" %)(((
1070 +* Unit: ms.
1071 +* Range: 0 to 30000
1072 +)))
1073 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10068|(% colspan="2" style="width:506px" %)(((
1074 +* Unit: times.
1075 +* Range: 0 to 100
1076 +)))
1077 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10069|(% colspan="2" style="width:506px" %)(((
1078 +* Unit: s.
1079 +* Range: 0 to 300
1080 +)))
797 797  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10070|(% colspan="2" style="width:506px" %)
798 798  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10071|(% colspan="2" style="width:506px" %)
799 799  |(% colspan="1" rowspan="11" style="width:102px" %)COM1-2|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10094|(% colspan="2" style="width:506px" %)(((
... ... @@ -826,10 +826,22 @@
826 826  * =1: ODD
827 827  * =2: EVEN
828 828  )))
829 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10099|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
830 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10100|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
831 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10101|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
832 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10102|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
1113 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10099|(% colspan="2" style="width:506px" %)(((
1114 +* Unit: ms.
1115 +* Range: 0 to 30000
1116 +)))
1117 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10100|(% colspan="2" style="width:506px" %)(((
1118 +* Unit: ms.
1119 +* Range: 0 to 30000
1120 +)))
1121 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10101|(% colspan="2" style="width:506px" %)(((
1122 +* Unit: times.
1123 +* Range: 0 to 100
1124 +)))
1125 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10102|(% colspan="2" style="width:506px" %)(((
1126 +* Unit: s.
1127 +* Range: 0 to 30
1128 +)))
833 833  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10103|(% colspan="2" style="width:506px" %)
834 834  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10104|(% colspan="2" style="width:506px" %)
835 835  |(% colspan="1" rowspan="11" style="width:102px" %)COM1-3|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10120|(% colspan="2" style="width:506px" %)(((
... ... @@ -862,10 +862,22 @@
862 862  * =1: ODD
863 863  * =2: EVEN
864 864  )))
865 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10125|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
866 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10126|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
867 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10127|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
868 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10128|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
1161 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10125|(% colspan="2" style="width:506px" %)(((
1162 +* Unit: ms.
1163 +* Range: 0 to 30000
1164 +)))
1165 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10126|(% colspan="2" style="width:506px" %)(((
1166 +* Unit: ms.
1167 +* Range: 0 to 30000
1168 +)))
1169 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10127|(% colspan="2" style="width:506px" %)(((
1170 +* Unit: times.
1171 +* Range: 0 to 100
1172 +)))
1173 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10128|(% colspan="2" style="width:506px" %)(((
1174 +* Unit: s.
1175 +* Range: 0 to 30
1176 +)))
869 869  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10129|(% colspan="2" style="width:506px" %)
870 870  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10130|(% colspan="2" style="width:506px" %)
871 871  |(% colspan="1" rowspan="11" style="width:102px" %)COM2|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10072|(% colspan="2" style="width:506px" %)(((
... ... @@ -896,10 +896,22 @@
896 896  * =1: ODD
897 897  * =2: EVEN
898 898  )))
899 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10077|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
900 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10078|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
901 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10079|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
902 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10080|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
1207 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10077|(% colspan="2" style="width:506px" %)(((
1208 +* Unit: ms.
1209 +* Range: 0 to 30000
1210 +)))
1211 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10078|(% colspan="2" style="width:506px" %)(((
1212 +* Unit: ms.
1213 +* Range: 0 to 30000
1214 +)))
1215 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10079|(% colspan="2" style="width:506px" %)(((
1216 +* Unit: times.
1217 +* Range: 0 to 100
1218 +)))
1219 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10080|(% colspan="2" style="width:506px" %)(((
1220 +* Unit: s.
1221 +* Range: 0 to 30
1222 +)))
903 903  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10081|(% colspan="2" style="width:506px" %)
904 904  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10082|(% colspan="2" style="width:506px" %)
905 905  |(% colspan="1" rowspan="11" style="width:102px" %)COM2-2|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10105|(% colspan="2" style="width:506px" %)(((
... ... @@ -930,10 +930,22 @@
930 930  * =1: ODD
931 931  * =2: EVEN
932 932  )))
933 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10110|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
934 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10111|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
935 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10112|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
936 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10113|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
1253 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10110|(% colspan="2" style="width:506px" %)(((
1254 +* Unit: ms.
1255 +* Range: 0 to 30000
1256 +)))
1257 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10111|(% colspan="2" style="width:506px" %)(((
1258 +* Unit: ms.
1259 +* Range: 0 to 30000
1260 +)))
1261 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10112|(% colspan="2" style="width:506px" %)(((
1262 +* Unit: times.
1263 +* Range: 0 to 100
1264 +)))
1265 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10113|(% colspan="2" style="width:506px" %)(((
1266 +* Unit: s.
1267 +* Range: 0 to 30
1268 +)))
937 937  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10114|(% colspan="2" style="width:506px" %)
938 938  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10115|(% colspan="2" style="width:506px" %)
939 939  |(% colspan="1" rowspan="11" style="width:102px" %)COM3|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10083|(% colspan="2" style="width:506px" %)(((
... ... @@ -963,29 +963,48 @@
963 963  * =1: ODD
964 964  * =2: EVEN
965 965  )))
966 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10088|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
967 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10089|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
968 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10090|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
969 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10091|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
1298 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10088|(% colspan="2" style="width:506px" %)(((
1299 +* Unit: ms.
1300 +* Range: 0 to 30000
1301 +)))
1302 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10089|(% colspan="2" style="width:506px" %)(((
1303 +* Unit: ms.
1304 +* Range: 0 to 30000
1305 +)))
1306 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10090|(% colspan="2" style="width:506px" %)(((
1307 +* Unit: times.
1308 +* Range: 0 to 100
1309 +)))
1310 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10091|(% colspan="2" style="width:506px" %)(((
1311 +* Unit: s.
1312 +* Range: 0 to 30
1313 +)))
970 970  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10092|(% colspan="2" style="width:506px" %)
971 971  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10093|(% colspan="2" style="width:506px" %)
972 972  |(% colspan="1" rowspan="2" style="width:102px" %)CAN port|(% style="width:173px" %)CAN1 baud rate|(% style="width:122px" %)HSW010116|(% style="width:299px" %)(((
973 -Unit: K, the baud rate must be an integer, for example, when the baud rate required is 250000, just enter 250.
1317 +Unit: K, the baud rate must be an integer.
1318 +
1319 +For example, when the baud rate required is 250000, just enter 250.
974 974  )))|(% colspan="1" rowspan="2" style="width:218px" %)**✎Note: **If baud rate has been modified,please wait 5 seconds,then restart the HMI to take effect.
975 -|(% style="width:173px" %)CAN2 baud rate|(% style="width:122px" %)HSW010117|(% style="width:299px" %)Unit: K, the baud rate must be an integer, for example, when the baud rate required is 250000, just enter 250.
1321 +|(% style="width:173px" %)CAN2 baud rate|(% style="width:122px" %)HSW010117|(% style="width:299px" %)(((
1322 +Unit: K, the baud rate must be an integer.
976 976  
977 -== **Ethernet communication configuration** ==
1324 +For example, when the baud rate required is 250000, just enter 250.
1325 +)))
978 978  
1327 +== Ethernet communication configuration ==
1328 +
979 979  (% class="table-bordered" %)
980 -|=(% style="width: 40px;" %)**No.**|=(% style="width: 295px;" %)**Function**|=(% style="width: 220px;" %)**Address**|=(% style="width: 336px;" %)**Description**
1330 +|(% style="width:40px" %)**No.**|(% style="width:295px" %)**Function**|(% style="width:220px" %)**Address**|(% style="width:336px" %)**Description**
981 981  |(% rowspan="7" style="width:40px" %)1|(% colspan="1" rowspan="7" style="width:295px" %)Ethernet parameter configuration for communication number 1 in list. Configure those addresses according to connected device. After configuration, wait for 5 seconds and restart the HMI.|(% style="width:220px" %)HSW11004|(% style="width:336px" %)Device IP address high word 1
982 982  |(% style="width:220px" %)HSW11005|(% style="width:336px" %)Device IP address high word 2
983 983  |(% style="width:220px" %)HSW11006|(% style="width:336px" %)Device IP address high word 3
984 984  |(% style="width:220px" %)HSW11007|(% style="width:336px" %)Device IP address high word 4
985 985  |(% style="width:220px" %)HSW11008|(% style="width:336px" %)Device Port number
986 -|(% style="width:220px" %)HSW11009|=(% style="width: 336px;" %)(((
987 -* =2 TCP
988 -* =3 UDP
1336 +|(% style="width:220px" %)HSW11009|(% style="width:336px" %)(((
1337 +~=2 TCP
1338 +
1339 +~=3 UDP
989 989  )))
990 990  |(% style="width:220px" %)HSW11010|(% style="width:336px" %)Reserved
991 991  |(% rowspan="7" style="width:40px" %)2|(% colspan="1" rowspan="7" style="width:295px" %)Ethernet parameter configuration for communication number 2 in list. Configure those addresses according to connected device. After configuration, wait for 5 seconds and restart the HMI.|(% style="width:220px" %)HSW11011|(% style="width:336px" %)Device IP address high word 1
... ... @@ -993,9 +993,10 @@
993 993  |(% style="width:220px" %)HSW11013|(% style="width:336px" %)Device IP address high word 3
994 994  |(% style="width:220px" %)HSW11014|(% style="width:336px" %)Device IP address high word 4
995 995  |(% style="width:220px" %)HSW11015|(% style="width:336px" %)Device Port number
996 -|(% style="width:220px" %)HSW11016|=(% style="width: 336px;" %)(((
997 -* =2 TCP
998 -* =3 UDP
1347 +|(% style="width:220px" %)HSW11016|(% style="width:336px" %)(((
1348 +~=2 TCP
1349 +
1350 +~=3 UDP
999 999  )))
1000 1000  |(% style="width:220px" %)HSW11017|(% style="width:336px" %)Reserved
1001 1001  |(% style="width:40px" %)…|(% style="width:295px" %) |(% style="width:220px" %)…|(% style="width:336px" %)…
... ... @@ -1004,7 +1004,11 @@
1004 1004  |(% style="width:220px" %)HSW11223|(% style="width:336px" %)Device IP address high word 3
1005 1005  |(% style="width:220px" %)HSW11224|(% style="width:336px" %)Device IP address high word 4
1006 1006  |(% style="width:220px" %)HSW11225|(% style="width:336px" %)Device Port number
1007 -|(% style="width:220px" %)HSW11226|=(% style="width: 336px;" %)2 TCP; =3 UDP
1359 +|(% style="width:220px" %)HSW11226|(% style="width:336px" %)(((
1360 +~=2 TCP;
1361 +
1362 +~=3 UDP
1363 +)))
1008 1008  |(% style="width:220px" %)HSW11227|(% style="width:336px" %)Reserved
1009 1009  
1010 1010  (% class="box infomessage" %)
... ... @@ -1012,7 +1012,7 @@
1012 1012  **✎Note:** The number of Ethernet connections supported by different HMI series varies.
1013 1013  )))
1014 1014  
1015 -== **Communication control** ==
1371 +== Communication control ==
1016 1016  
1017 1017  (% class="table-bordered" %)