Changes for page 13 HMI Internal Registers

Last modified by Jett on 2025/04/28 16:07

From version 4.3
edited by Stone Wu
on 2022/08/06 14:11
Change comment: There is no comment for this version
To version 9.2
edited by Theodore Xu
on 2022/12/16 10:09
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Stone
1 +XWiki.AiXia
Content
... ... @@ -4,11 +4,11 @@
4 4  
5 5  *HSW, HDW, HUW, HAW are word address, HSX, HDX, HUX, HAX are bit address.
6 6  
7 -1. **System data area (HSW): **A special register defined by the system.
8 -1. **Data storage area (HDW/HDX): **Users store user data.
9 -1. **System data area (HUW): **A special register defined by the system.
10 -1. **System Data (HAW)**: System register used for power-off save.
11 -1. **Recipe index area (RPW): **System register used for recipe index.
7 +* **System data area (HSW): **A special register defined by the system.
8 +* **Data storage area (HDW/HDX): **Users store user data.
9 +* **System data area (HUW): **A special register defined by the system.
10 +* **System Data (HAW)**: System register used for power-off save.
11 +* **Recipe index area (RPW): **System register used for recipe index.
12 12  
13 13  HMI internal registers are divided into bit address and word address, which can be accessed in two ways (take HDW as an example).
14 14  
... ... @@ -643,6 +643,27 @@
643 643  * =1: download firmware
644 644  * =2: enter the background
645 645  )))
646 +|=(% style="width: 160px;" %)HSW1865|(% style="width:282px" %)Priority connection to the cloud|(% style="width:452px" %)(((
647 +* =0: priority  Ethernet
648 +* =1: priority WLAN
649 +* =2: priority 4G
650 +)))
651 +|=(% style="width: 160px;" %)HSW1866|(% style="width:282px" %)Delete the LUa extension module file|(% style="width:452px" %)(((
652 +* =0: delete;
653 +* = Others: do not delete
654 +)))
655 +|=(% style="width: 160px;" %)HSW1867|(% style="width:282px" %)Reset mode|(% style="width:452px" %)(((
656 +Monitor address is set during reset of reset switch, whether to cancel reset,
657 +
658 +* = 0: yes (default);
659 +* = 1: no
660 +)))
661 +|=(% style="width: 160px;" %)HSW1868|(% style="width:282px" %)Double-click or long press the record type table mode|(% style="width:452px" %)(((
662 +Controls whether the button pops up when double-clicking or long pressing on record type table object
663 +
664 +* = 0: yes (default);
665 +* = 1: no
666 +)))
646 646  |=(% style="width: 160px;" %)HSW10000~~19999|(% style="width:282px" %)Power-down storage area|(% style="width:452px" %)After restart, the data remains
647 647  |=(% style="width: 160px;" %)HSW10035|(% rowspan="13" style="width:282px" %)(((
648 648  **✎Note: **Only valid when the HMI is plugged into the Ethernet cable.
... ... @@ -757,10 +757,10 @@
757 757  |=(% style="width: 160px;" %)HSW11760|(% style="width:282px" %)Screensaver countdown|(% style="width:452px" %)Display the countdown to enter the Screensaver, unit: second.
758 758  |=(% style="width: 160px;" %)HSW11761|(% style="width:282px" %)Screensaver screen number|(% style="width:452px" %)Set the screen number for Screensaver
759 759  
760 -== **Serial port communication configuration** ==
781 +== Serial port communication configuration ==
761 761  
762 762  (% class="table-bordered" %)
763 -|=(% style="width: 102px;" %)Port|=(% style="width: 173px;" %)**Function**|=(% style="width: 122px;" %)**Address**|=(% colspan="2" style="width: 506px;" %)**Description**
784 +|=(% scope="row" style="width: 102px;" %)Port|=(% style="width: 173px;" %)**Function**|=(% style="width: 122px;" %)**Address**|=(% colspan="2" style="width: 506px;" %)**Description**
764 764  |(% colspan="1" rowspan="11" style="width:102px" %)COM1|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10061|(% colspan="2" style="width:506px" %)(((
765 765  * =0: RS232
766 766  * =1: RS485
... ... @@ -790,10 +790,22 @@
790 790  * =1: ODD
791 791  * =2: EVEN
792 792  )))
793 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10066|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
794 -|(% style="width:173px" %)reveive timeout|(% style="width:122px" %)HSW10067|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
795 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10068|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
796 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10069|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~300
814 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10066|(% colspan="2" style="width:506px" %)(((
815 +* Unit: ms.
816 +* Range: 0 to 30000
817 +)))
818 +|(% style="width:173px" %)reveive timeout|(% style="width:122px" %)HSW10067|(% colspan="2" style="width:506px" %)(((
819 +* Unit: ms.
820 +* Range: 0 to 30000
821 +)))
822 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10068|(% colspan="2" style="width:506px" %)(((
823 +* Unit: times.
824 +* Range: 0 to 100
825 +)))
826 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10069|(% colspan="2" style="width:506px" %)(((
827 +* Unit: s.
828 +* Range: 0 to 300
829 +)))
797 797  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10070|(% colspan="2" style="width:506px" %)
798 798  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10071|(% colspan="2" style="width:506px" %)
799 799  |(% colspan="1" rowspan="11" style="width:102px" %)COM1-2|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10094|(% colspan="2" style="width:506px" %)(((
... ... @@ -826,10 +826,22 @@
826 826  * =1: ODD
827 827  * =2: EVEN
828 828  )))
829 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10099|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
830 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10100|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
831 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10101|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
832 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10102|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
862 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10099|(% colspan="2" style="width:506px" %)(((
863 +* Unit: ms.
864 +* Range: 0 to 30000
865 +)))
866 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10100|(% colspan="2" style="width:506px" %)(((
867 +* Unit: ms.
868 +* Range: 0 to 30000
869 +)))
870 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10101|(% colspan="2" style="width:506px" %)(((
871 +* Unit: times.
872 +* Range: 0 to 100
873 +)))
874 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10102|(% colspan="2" style="width:506px" %)(((
875 +* Unit: s.
876 +* Range: 0 to 30
877 +)))
833 833  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10103|(% colspan="2" style="width:506px" %)
834 834  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10104|(% colspan="2" style="width:506px" %)
835 835  |(% colspan="1" rowspan="11" style="width:102px" %)COM1-3|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10120|(% colspan="2" style="width:506px" %)(((
... ... @@ -862,10 +862,22 @@
862 862  * =1: ODD
863 863  * =2: EVEN
864 864  )))
865 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10125|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
866 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10126|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
867 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10127|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
868 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10128|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
910 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10125|(% colspan="2" style="width:506px" %)(((
911 +* Unit: ms.
912 +* Range: 0 to 30000
913 +)))
914 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10126|(% colspan="2" style="width:506px" %)(((
915 +* Unit: ms.
916 +* Range: 0 to 30000
917 +)))
918 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10127|(% colspan="2" style="width:506px" %)(((
919 +* Unit: times.
920 +* Range: 0 to 100
921 +)))
922 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10128|(% colspan="2" style="width:506px" %)(((
923 +* Unit: s.
924 +* Range: 0 to 30
925 +)))
869 869  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10129|(% colspan="2" style="width:506px" %)
870 870  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10130|(% colspan="2" style="width:506px" %)
871 871  |(% colspan="1" rowspan="11" style="width:102px" %)COM2|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10072|(% colspan="2" style="width:506px" %)(((
... ... @@ -896,10 +896,22 @@
896 896  * =1: ODD
897 897  * =2: EVEN
898 898  )))
899 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10077|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
900 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10078|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
901 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10079|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
902 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10080|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
956 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10077|(% colspan="2" style="width:506px" %)(((
957 +* Unit: ms.
958 +* Range: 0 to 30000
959 +)))
960 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10078|(% colspan="2" style="width:506px" %)(((
961 +* Unit: ms.
962 +* Range: 0 to 30000
963 +)))
964 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10079|(% colspan="2" style="width:506px" %)(((
965 +* Unit: times.
966 +* Range: 0 to 100
967 +)))
968 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10080|(% colspan="2" style="width:506px" %)(((
969 +* Unit: s.
970 +* Range: 0 to 30
971 +)))
903 903  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10081|(% colspan="2" style="width:506px" %)
904 904  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10082|(% colspan="2" style="width:506px" %)
905 905  |(% colspan="1" rowspan="11" style="width:102px" %)COM2-2|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10105|(% colspan="2" style="width:506px" %)(((
... ... @@ -930,10 +930,22 @@
930 930  * =1: ODD
931 931  * =2: EVEN
932 932  )))
933 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10110|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
934 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10111|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
935 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10112|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
936 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10113|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
1002 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10110|(% colspan="2" style="width:506px" %)(((
1003 +* Unit: ms.
1004 +* Range: 0 to 30000
1005 +)))
1006 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10111|(% colspan="2" style="width:506px" %)(((
1007 +* Unit: ms.
1008 +* Range: 0 to 30000
1009 +)))
1010 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10112|(% colspan="2" style="width:506px" %)(((
1011 +* Unit: times.
1012 +* Range: 0 to 100
1013 +)))
1014 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10113|(% colspan="2" style="width:506px" %)(((
1015 +* Unit: s.
1016 +* Range: 0 to 30
1017 +)))
937 937  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10114|(% colspan="2" style="width:506px" %)
938 938  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10115|(% colspan="2" style="width:506px" %)
939 939  |(% colspan="1" rowspan="11" style="width:102px" %)COM3|(% style="width:173px" %)Communication mode|(% style="width:122px" %)HSW10083|(% colspan="2" style="width:506px" %)(((
... ... @@ -963,29 +963,48 @@
963 963  * =1: ODD
964 964  * =2: EVEN
965 965  )))
966 -|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10088|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
967 -|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10089|(% colspan="2" style="width:506px" %)Unit: ms. Range: 0~~30000
968 -|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10090|(% colspan="2" style="width:506px" %)Unit: times. Range: 0~~100
969 -|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10091|(% colspan="2" style="width:506px" %)Unit: s. Range: 0~~30
1047 +|(% style="width:173px" %)Wait timeout|(% style="width:122px" %)HSW10088|(% colspan="2" style="width:506px" %)(((
1048 +* Unit: ms.
1049 +* Range: 0 to 30000
1050 +)))
1051 +|(% style="width:173px" %)receive timeout|(% style="width:122px" %)HSW10089|(% colspan="2" style="width:506px" %)(((
1052 +* Unit: ms.
1053 +* Range: 0 to 30000
1054 +)))
1055 +|(% style="width:173px" %)Retry time|(% style="width:122px" %)HSW10090|(% colspan="2" style="width:506px" %)(((
1056 +* Unit: times.
1057 +* Range: 0 to 100
1058 +)))
1059 +|(% style="width:173px" %)Retry timeout|(% style="width:122px" %)HSW10091|(% colspan="2" style="width:506px" %)(((
1060 +* Unit: s.
1061 +* Range: 0 to 30
1062 +)))
970 970  |(% style="width:173px" %)HMI station number|(% style="width:122px" %)HSW10092|(% colspan="2" style="width:506px" %)
971 971  |(% style="width:173px" %)PLC station number|(% style="width:122px" %)HSW10093|(% colspan="2" style="width:506px" %)
972 972  |(% colspan="1" rowspan="2" style="width:102px" %)CAN port|(% style="width:173px" %)CAN1 baud rate|(% style="width:122px" %)HSW010116|(% style="width:299px" %)(((
973 -Unit: K, the baud rate must be an integer, for example, when the baud rate required is 250000, just enter 250.
1066 +Unit: K, the baud rate must be an integer.
1067 +
1068 +For example, when the baud rate required is 250000, just enter 250.
974 974  )))|(% colspan="1" rowspan="2" style="width:218px" %)**✎Note: **If baud rate has been modified,please wait 5 seconds,then restart the HMI to take effect.
975 -|(% style="width:173px" %)CAN2 baud rate|(% style="width:122px" %)HSW010117|(% style="width:299px" %)Unit: K, the baud rate must be an integer, for example, when the baud rate required is 250000, just enter 250.
1070 +|(% style="width:173px" %)CAN2 baud rate|(% style="width:122px" %)HSW010117|(% style="width:299px" %)(((
1071 +Unit: K, the baud rate must be an integer.
976 976  
977 -== **Ethernet communication configuration** ==
1073 +For example, when the baud rate required is 250000, just enter 250.
1074 +)))
978 978  
1076 +== Ethernet communication configuration ==
1077 +
979 979  (% class="table-bordered" %)
980 -|=(% style="width: 40px;" %)**No.**|=(% style="width: 295px;" %)**Function**|=(% style="width: 220px;" %)**Address**|=(% style="width: 336px;" %)**Description**
1079 +|(% style="width:40px" %)**No.**|(% style="width:295px" %)**Function**|(% style="width:220px" %)**Address**|(% style="width:336px" %)**Description**
981 981  |(% rowspan="7" style="width:40px" %)1|(% colspan="1" rowspan="7" style="width:295px" %)Ethernet parameter configuration for communication number 1 in list. Configure those addresses according to connected device. After configuration, wait for 5 seconds and restart the HMI.|(% style="width:220px" %)HSW11004|(% style="width:336px" %)Device IP address high word 1
982 982  |(% style="width:220px" %)HSW11005|(% style="width:336px" %)Device IP address high word 2
983 983  |(% style="width:220px" %)HSW11006|(% style="width:336px" %)Device IP address high word 3
984 984  |(% style="width:220px" %)HSW11007|(% style="width:336px" %)Device IP address high word 4
985 985  |(% style="width:220px" %)HSW11008|(% style="width:336px" %)Device Port number
986 -|(% style="width:220px" %)HSW11009|=(% style="width: 336px;" %)(((
987 -* =2 TCP
988 -* =3 UDP
1085 +|(% style="width:220px" %)HSW11009|(% style="width:336px" %)(((
1086 +~=2 TCP
1087 +
1088 +~=3 UDP
989 989  )))
990 990  |(% style="width:220px" %)HSW11010|(% style="width:336px" %)Reserved
991 991  |(% rowspan="7" style="width:40px" %)2|(% colspan="1" rowspan="7" style="width:295px" %)Ethernet parameter configuration for communication number 2 in list. Configure those addresses according to connected device. After configuration, wait for 5 seconds and restart the HMI.|(% style="width:220px" %)HSW11011|(% style="width:336px" %)Device IP address high word 1
... ... @@ -993,9 +993,10 @@
993 993  |(% style="width:220px" %)HSW11013|(% style="width:336px" %)Device IP address high word 3
994 994  |(% style="width:220px" %)HSW11014|(% style="width:336px" %)Device IP address high word 4
995 995  |(% style="width:220px" %)HSW11015|(% style="width:336px" %)Device Port number
996 -|(% style="width:220px" %)HSW11016|=(% style="width: 336px;" %)(((
997 -* =2 TCP
998 -* =3 UDP
1096 +|(% style="width:220px" %)HSW11016|(% style="width:336px" %)(((
1097 +~=2 TCP
1098 +
1099 +~=3 UDP
999 999  )))
1000 1000  |(% style="width:220px" %)HSW11017|(% style="width:336px" %)Reserved
1001 1001  |(% style="width:40px" %)…|(% style="width:295px" %) |(% style="width:220px" %)…|(% style="width:336px" %)…
... ... @@ -1004,7 +1004,11 @@
1004 1004  |(% style="width:220px" %)HSW11223|(% style="width:336px" %)Device IP address high word 3
1005 1005  |(% style="width:220px" %)HSW11224|(% style="width:336px" %)Device IP address high word 4
1006 1006  |(% style="width:220px" %)HSW11225|(% style="width:336px" %)Device Port number
1007 -|(% style="width:220px" %)HSW11226|=(% style="width: 336px;" %)2 TCP; =3 UDP
1108 +|(% style="width:220px" %)HSW11226|(% style="width:336px" %)(((
1109 +~=2 TCP;
1110 +
1111 +~=3 UDP
1112 +)))
1008 1008  |(% style="width:220px" %)HSW11227|(% style="width:336px" %)Reserved
1009 1009  
1010 1010  (% class="box infomessage" %)
... ... @@ -1012,7 +1012,7 @@
1012 1012  **✎Note:** The number of Ethernet connections supported by different HMI series varies.
1013 1013  )))
1014 1014  
1015 -== **Communication control** ==
1120 +== Communication control ==
1016 1016  
1017 1017  (% class="table-bordered" %)
1018 1018  |=(% style="width: 135px;" %)**Communication No.**|=(% style="width: 102px;" %)**Station No.**|=(% style="width: 185px;" %)**Control bit**|=(% style="width: 191px;" %)**Communication lamp**|=(% style="width: 271px;" %)**Description**