Changes for page 13 HMI Internal Registers

Last modified by xingzhi lin on 2025/11/03 09:28

From version 8.1
edited by xingzhi lin
on 2025/11/03 09:28
Change comment: There is no comment for this version
To version 5.1
edited by xingzhi lin
on 2025/09/24 09:47
Change comment: There is no comment for this version

Summary

Details

Page properties
Content
... ... @@ -130,89 +130,7 @@
130 130  )))
131 131  |=HUW1402|Keyboard note|It saves the text information of the keyboard notes when clicking object(HUW1402-HUW1433)
132 132  |=HUW1436|Current object level|Indicate current object security level
133 -|=HUW1502|Touch status prompt|(((
134 -* 0: Not touching
135 -* 1: Touching
136 -)))
137 -|=HUW1503|The current user's group prompt|(((
138 -A bit represents one of the groups. The administrator is bit 0, group 0 is bit 1, and group 1 is bit 2 and so on.
139 139  
140 -For example:
141 -
142 -* HUW1503.0=0 (administrator)
143 -* HUW1503.1=1 (group 0)
144 -* HUW1503.2=1 (group 1)
145 -* HUW1503.3=0 (group 2)
146 -
147 -This means the current user has the permissions of groups 0 and 1, but not administrator or group 2.
148 -)))
149 -|=HSW1908|Total available user storage|Displays total available user storage (64-bit floating-point, unit: MB).
150 -|=HSW1912|Remaining available user storage|Displays remaining available user storage (64-bit floating-point, unit: MB).
151 -|=HSW1921|Touch status indicator|(((
152 -* 0: Not touching
153 -* 1: Touching
154 -)))
155 -|=HSW1923|Exclusive mode switch|(((
156 -* 0: Disable exclusive mode
157 -* 1: Enable exclusive mode
158 -)))
159 -|=HSW11773|Control auto user logout |(((
160 -Controls the enable state of auto user logout.
161 -
162 -* HSX11773.0: =0 Follow project configuration
163 -* HSX11773.0: =1 Follow address configuration
164 -* HSX11773.1: =0 Disable auto logout
165 -* HSX11773.1: =1 Enable auto logout
166 -)))
167 -|=HSW11774|Auto user logout waiting time|Sets the waiting time before automatic logout (1–255 minutes).
168 -|=HSW11775|Enable NTP time synchronization|(((
169 -* 1: Enable NTP
170 -* 0: Disable NTP
171 -)))
172 -|=HSW11776|Immediate time synchronization|Perform immediate NTP sync after device startup.
173 -|=HSW11777~~11780|Primary time server IP (required when NTP is enabled)|Each register represents one byte of the IP address (high to low).
174 -|=HSW11781~~11784|Second time server IP (optional)|Each register represents one byte of the IP address (high to low).
175 -|=HSW11785~~11788|Third time server IP (optional)|Each register represents one byte of the IP address (high to low).
176 -|=HSW11789~~11792|Fourth time server IP (optional)|Each register represents one byte of the IP address (high to low).
177 -|=HSW11793|Time synchronization period|(((
178 -
179 -
180 -High byte of time synchronization period
181 -)))
182 -|=HSW11794|Time synchronization period|(((
183 -
184 -
185 -Low byte of time synchronization period
186 -)))
187 -|=HSW11795|Enable daylight saving time (DST)|(((
188 -* 1: Enable DST
189 -* 0: Disable DST
190 -)))
191 -|=HSW11796|Time adjustment|Hour adjustment
192 -|=HSW11797|Time adjustment|Minute adjustment
193 -|=HSW11798~~11807|DST start and end configuration|(((
194 -* Start month: 1–12
195 -* Week of month: 1–5
196 -* Day of week: 0–6 (0 = Sunday)
197 -* Hour: 0–23
198 -* Minute: 0–59
199 -* End month/week/day/hour/minute follow the same format.
200 -)))
201 -|=HSW11808|Whether currently in daylight saving time|(((
202 -* 1: In DST
203 -* 0: Not in DST
204 -)))
205 -|=HSW11811|Watchdog mode configuration|(((
206 -* 1: Register mode
207 -* 0: Project mode
208 -)))
209 -|=HSW11812|Enable watchdog|(((
210 -* 1: Enable
211 -* 0: Disable
212 -)))
213 -|=HSW11813|Watchdog timeout setting|Unit: second
214 -|=HSW11814|Trigger watchdog|=0 Reboot
215 -
216 216  = **Special data area (HSW/HSX)** =
217 217  
218 218  It is used for system special registers (reserved by system).