Changes for page 13 HMI Internal Registers

Last modified by Jett on 2025/04/28 16:07

From version 9.2
edited by Theodore Xu
on 2022/12/16 10:09
Change comment: There is no comment for this version
To version 16.1
edited by Hunter
on 2023/01/14 11:08
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.AiXia
1 +XWiki.Hunter
Content
... ... @@ -241,8 +241,8 @@
241 241  * =2: HSX521.1=1, delete all trend graph.
242 242  * =4: HSX521.2=1, delete all alarms.
243 243  * =16: HSX521.4=1, delete history XY plot.
244 -* =32: HSX521.5=1, delete data records in SD card or flash dish;(Please make a setting which is saved to flash disk or SD card in project setting).
245 -* =64: HSX521.6=1, delete alarms records in SD card or flash dish; (Please make a setting which is saved to flash disk or SD card in project setting).
244 +* =32: HSX521.5=1, delete data records in SD card or USB flash disk;(Please make a setting which is saved to USB flash disk or SD card in project setting).
245 +* =64: HSX521.6=1, delete alarms records in SD card or USB flash disk; (Please make a setting which is saved to USB flash disk or SD card in project setting).
246 246  )))
247 247  |=(% style="width: 160px;" %)HSW522|(% style="width:282px" %)Copy and paste the alarm/data files in flash to the USB flash disk|(% style="width:452px" %)(((
248 248  * =0: No operation
... ... @@ -485,6 +485,8 @@
485 485  * =0, Default value
486 486  * =1, Release the alarm generated before the last power-down when starting up
487 487  )))
488 +|=(% style="width: 160px;" %)HSW1200|(% colspan="1" rowspan="2" style="width:282px" %)TSAP settings for HMI in the Siemens LOGO! 8 protocol(ig series or HMI V2.0)|(% style="width:452px" %)HMI local TSAP, which corresponds to the remote TSAP of PLC
489 +|=(% style="width: 160px;" %)HSW1201|(% style="width:452px" %)HMI remote TSAP, which corresponds to the local TSAP of PLC
488 488  |=(% style="width: 160px;" %)HSW1450|(% style="width:282px" %)Enable objects level password function|(% style="width:452px" %)(((
489 489  * =0, Disable
490 490  * =1, Enable
... ... @@ -618,6 +618,174 @@
618 618  * =1: Server connection is OK
619 619  )))
620 620  |=(% style="width: 160px;" %)HSW1761|(% style="width:282px" %)Display 4G network signal strength|(% style="width:452px" %)Signal strength: 0~~31. The greater the value ,the signal is stronger
623 +|=(% style="width: 160px;" %)(((
624 +HSW1762
625 +)))|(% colspan="1" rowspan="13" style="width:282px" %)(((
626 +Note: Valid when Ethernet2 of HMI is plugged into the network cable.
627 +①、When the Ethernet setting is enabled in the project parameters, this register displays the set value.
628 +②. When the Ethernet setting is not enabled in the engineering parameters, the register displays the Ethernet IP automatically acquired by the HMI.
629 +③. When the HMI is not plugged into the network cable, the register will show 0 whether the engineering parameters are set or not.
630 +④.IP related registers can be read and written (only static IP mode can be written).
631 +)))|(% style="width:452px" %)(((
632 +Ethernet2 Local IP address high byte 1
633 +)))
634 +|=(% style="width: 160px;" %)(((
635 +HSW1763
636 +)))|(% style="width:452px" %)(((
637 +Ethernet2 Local IP address high byte 2
638 +)))
639 +|=(% style="width: 160px;" %)(((
640 +HSW1764
641 +)))|(% style="width:452px" %)(((
642 +Ethernet2 Local IP address high byte 3
643 +)))
644 +|=(% style="width: 160px;" %)(((
645 +HSW1765
646 +)))|(% style="width:452px" %)(((
647 +Ethernet2 Local IP address high byte 4
648 +)))
649 +|=(% style="width: 160px;" %)(((
650 +HSW1766
651 +)))|(% style="width:452px" %)(((
652 +Ethernet2 Local mask IP address high byte 1
653 +)))
654 +|=(% style="width: 160px;" %)(((
655 +HSW1767
656 +)))|(% style="width:452px" %)(((
657 +Ethernet2 Local mask IP address high byte 2
658 +)))
659 +|=(% style="width: 160px;" %)(((
660 +HSW1768
661 +)))|(% style="width:452px" %)Ethernet2 Local mask IP address high byte 3
662 +|=(% style="width: 160px;" %)HSW1769|(% style="width:452px" %)Ethernet2 Local mask IP address high byte 4
663 +|=(% style="width: 160px;" %)(((
664 +HSW1770
665 +)))|(% style="width:452px" %)(((
666 +Ethernet2 Local gateway IP address high byte 1
667 +)))
668 +|=(% style="width: 160px;" %)(((
669 +HSW1771
670 +)))|(% style="width:452px" %)(((
671 +Ethernet2 Local gateway IP address high byte 2
672 +)))
673 +|=(% style="width: 160px;" %)(((
674 +HSW1772
675 +)))|(% style="width:452px" %)(((
676 +Ethernet2 Local gateway IP address high byte 3
677 +)))
678 +|=(% style="width: 160px;" %)(((
679 +HSW1773
680 +)))|(% style="width:452px" %)(((
681 +Ethernet2 Local gateway IP address high byte 4
682 +)))
683 +|=(% style="width: 160px;" %)(((
684 +HSW1774
685 +)))|(% style="width:452px" %)(((
686 +Ethernet2 Local Port Address
687 +)))
688 +|=(% style="width: 160px;" %)(((
689 +HSW1775
690 +)))|(% colspan="1" rowspan="6" style="width:282px" %)(((
691 +①Display the MAC code of Ethernet2 NIC
692 +
693 +(hexadecimal display)
694 +
695 +②Read-only mode, not modifiable
696 +)))|(% style="width:452px" %)(((
697 +Ethernet2 Local MAC code high byte 1
698 +)))
699 +|=(% style="width: 160px;" %)(((
700 +HSW1776
701 +)))|(% style="width:452px" %)(((
702 +Ethernet2 Local MAC code high byte 2
703 +)))
704 +|=(% style="width: 160px;" %)(((
705 +HSW1777
706 +)))|(% style="width:452px" %)(((
707 +Ethernet2 Local MAC code high byte 3
708 +)))
709 +|=(% style="width: 160px;" %)(((
710 +HSW1778
711 +)))|(% style="width:452px" %)(((
712 +Ethernet2 Local MAC code high byte 4
713 +)))
714 +|=(% style="width: 160px;" %)(((
715 +HSW1779
716 +)))|(% style="width:452px" %)(((
717 +Ethernet2 Local MAC code high byte 5
718 +)))
719 +|=(% style="width: 160px;" %)(((
720 +HSW1780
721 +)))|(% style="width:452px" %)(((
722 +Ethernet2 Local MAC code high byte 6
723 +)))
724 +|=(% style="width: 160px;" %)(((
725 +HSW1781
726 +)))|(% colspan="1" rowspan="8" style="width:282px" %)(((
727 +①Display and modify DNS1 and DNS2 of Ethernet2
728 +
729 +②Related registers can be read and written mode (only static IP mode can be written)
730 +)))|(% style="width:452px" %)(((
731 +Ethernet2 Local DNS1 address high byte 1
732 +)))
733 +|=(% style="width: 160px;" %)(((
734 +HSW1782
735 +)))|(% style="width:452px" %)(((
736 +Ethernet2 Local DNS1 address high byte 2
737 +)))
738 +|=(% style="width: 160px;" %)(((
739 +HSW1783
740 +)))|(% style="width:452px" %)(((
741 +Ethernet2 Local DNS1 address high byte 3
742 +)))
743 +|=(% style="width: 160px;" %)(((
744 +HSW1784
745 +)))|(% style="width:452px" %)(((
746 +Ethernet2 Local DNS1 address high byte 4
747 +)))
748 +|=(% style="width: 160px;" %)(((
749 +HSW1785
750 +)))|(% style="width:452px" %)(((
751 +Ethernet2 Local DNS2 address high byte 1
752 +)))
753 +|=(% style="width: 160px;" %)(((
754 +HSW1786
755 +)))|(% style="width:452px" %)(((
756 +Ethernet2 Local DNS2 address high byte 2
757 +)))
758 +|=(% style="width: 160px;" %)(((
759 +HSW1787
760 +)))|(% style="width:452px" %)(((
761 +Ethernet2 Local DNS2 address high byte 3
762 +)))
763 +|=(% style="width: 160px;" %)(((
764 +HSW1788
765 +)))|(% style="width:452px" %)(((
766 +Ethernet2 Local DNS2 address high byte 4
767 +)))
768 +|=(% style="width: 160px;" %)(((
769 +HSW1789
770 +)))|(% colspan="1" style="width:282px" %)(((
771 +Display or set the dynamic or static IP mode of Ethernet2
772 +)))|(% style="width:452px" %)(((
773 +HSX1789.0 = 0, Static IP mode
774 +
775 +HSX1789.0 = 1, dynamic IP mode
776 +)))
777 +|=(% style="width: 160px;" %)(((
778 +HSW1790
779 +)))|(% colspan="1" style="width:282px" %)(((
780 +Confirm Ethernet2 IP, subnet mask, gateway, DNS1, DNS2, and dynamic static IP settings
781 +)))|(% style="width:452px" %)(((
782 +~= 1, confirm the setting (i.e., after modifying IP-related information, set this address to 1, representing confirmation of the modification, after which it will be reset to 0)
783 +)))
784 +|=(% style="width: 160px;" %)(((
785 +HSW1791
786 +)))|(% colspan="1" style="width:282px" %)(((
787 +Network status of the Ethernet2 connection server
788 +)))|(% style="width:452px" %)(((
789 +~= 0, connection to the server is abnormal = 1, connection to the server is normal
790 +)))
621 621  |=(% style="width: 160px;" %)HSW1852|(% style="width:282px" %)Control the interval in two consecutive clicks|(% style="width:452px" %)Limit range: 1~~500ms. The default is 100 ms.
622 622  |=(% style="width: 160px;" %)HSW1853|(% style="width:282px" %)File format for exporting data records to USB flash drive or SD card|(% style="width:452px" %)(((
623 623  * =0: db database
... ... @@ -644,7 +644,7 @@
644 644  * =2: enter the background
645 645  )))
646 646  |=(% style="width: 160px;" %)HSW1865|(% style="width:282px" %)Priority connection to the cloud|(% style="width:452px" %)(((
647 -* =0: priority  Ethernet
817 +* =0: priority Ethernet
648 648  * =1: priority WLAN
649 649  * =2: priority 4G
650 650  )))
... ... @@ -664,14 +664,66 @@
664 664  * = 0: yes (default);
665 665  * = 1: no
666 666  )))
837 +|=(% style="width: 160px;" %)(((
838 +HSW1869
839 +)))|(% style="width:282px" %)(((
840 +Dynamic screensaver countdown
841 +)))|(% style="width:452px" %)(((
842 +Countdown to enter dynamic screensaver effect, unit (S)
843 +)))
844 +|=(% style="width: 160px;" %)(((
845 +HSW1870
846 +)))|(% style="width:282px" %)(((
847 +Display or set the dynamic or static IP mode of Ethernet1
848 +)))|(% style="width:452px" %)(((
849 +HSX1870.0 = 0, Static IP mode
850 +
851 +HSX1870.0 = 1, dynamic IP mode
852 +)))
853 +|=(% style="width: 160px;" %)(((
854 +HSW1871
855 +)))|(% style="width:282px" %)(((
856 +Confirm the IP, subnet mask, gateway, DNS1, DNS2, and dynamic static IP settings for Ethernet1
857 +)))|(% style="width:452px" %)(((
858 +~= 1, confirm the setting (i.e., after modifying IP-related information, set this address to 1, representing confirmation of the modification, after which it will be reset to 0)
859 +)))
860 +|=(% style="width: 160px;" %)(((
861 +HSW1872
862 +)))|(% colspan="1" rowspan="8" style="width:282px" %)(((
863 +①Display and modify DNS1 and DNS2 of Ethernet1
864 +
865 +②Related registers can be read and written mode (only static IP mode can be written)
866 +)))|(% style="width:452px" %)(((
867 +Ethernet1 Local DNS1 address high byte 1
868 +)))
869 +|=(% style="width: 160px;" %)(((
870 +HSW1873
871 +)))|(% style="width:452px" %)Ethernet1 Local DNS1 address high byte 2
872 +|=(% style="width: 160px;" %)(((
873 +HSW1874
874 +)))|(% style="width:452px" %)Ethernet1 Local DNS1 address high byte 3
875 +|=(% style="width: 160px;" %)(((
876 +HSW1875
877 +)))|(% style="width:452px" %)Ethernet1 Local DNS1 address high byte 4
878 +|=(% style="width: 160px;" %)(((
879 +HSW1876
880 +)))|(% style="width:452px" %)Ethernet1 Local DNS2 address high byte 1
881 +|=(% style="width: 160px;" %)(((
882 +HSW1877
883 +)))|(% style="width:452px" %)Ethernet1 Local DNS2 address high byte 2
884 +|=(% style="width: 160px;" %)(((
885 +HSW1878
886 +)))|(% style="width:452px" %)Ethernet1 Local DNS2 address high byte 3
887 +|=(% style="width: 160px;" %)(((
888 +HSW1879
889 +)))|(% style="width:452px" %)Ethernet1 Local DNS2 address high byte 4
667 667  |=(% style="width: 160px;" %)HSW10000~~19999|(% style="width:282px" %)Power-down storage area|(% style="width:452px" %)After restart, the data remains
668 668  |=(% style="width: 160px;" %)HSW10035|(% rowspan="13" style="width:282px" %)(((
669 -**✎Note: **Only valid when the HMI is plugged into the Ethernet cable.
670 -
671 -1. If Ethernet settings is enabled in project parameters, this register displays the set value.
672 -1. If Ethernet settings is not enabled in project parameters, IP would automatically obtained IP.
673 -1. If HMI is not connected to the network, the register is displayed as 0 whether the engineering parameters are set.
674 -1. 4. All IP registers of HMI are read-only.
892 +Note: Valid when Ethernet1 of HMI is plugged into the network cable.
893 +①、When the Ethernet setting is enabled in the project parameters, this register displays the set value.
894 +②. When the Ethernet setting is not enabled in the engineering parameters, the register displays the Ethernet IP automatically acquired by the HMI.
895 +③. When the HMI is not plugged into the network cable, the register will show 0 whether the engineering parameters are set or not.
896 +④.IP related registers can be read and written (only static IP mode can be written).
675 675  )))|(% style="width:452px" %)Local IP address high byte 1
676 676  |=(% style="width: 160px;" %)HSW10036|(% style="width:452px" %)Local IP address high byte 2
677 677  |=(% style="width: 160px;" %)HSW10037|(% style="width:452px" %)Local IP address high byte 3
... ... @@ -686,9 +686,11 @@
686 686  |=(% style="width: 160px;" %)HSW10046|(% style="width:452px" %)Local gateway address high byte 4
687 687  |=(% style="width: 160px;" %)HSW10047|(% style="width:452px" %)Local port address
688 688  |=(% style="width: 160px;" %)HSW10048|(% rowspan="6" style="width:282px" %)(((
689 -Displays the MAC code of the current network card
911 +Display the MAC code of Ethernet1 NIC
690 690  
691 -(Hexadecimal display)
913 +(hexadecimal display)
914 +
915 +②Read-only mode, not modifiable
692 692  )))|(% style="width:452px" %)Local MAC code high word 1
693 693  |=(% style="width: 160px;" %)HSW10049|(% style="width:452px" %)Local MAC code high word 2
694 694  |=(% style="width: 160px;" %)HSW10050|(% style="width:452px" %)Local MAC code high word 3
... ... @@ -695,7 +695,7 @@
695 695  |=(% style="width: 160px;" %)HSW10051|(% style="width:452px" %)Local MAC code high word 4
696 696  |=(% style="width: 160px;" %)HSW10052|(% style="width:452px" %)Local MAC code high word 5
697 697  |=(% style="width: 160px;" %)HSW10053|(% style="width:452px" %)Local MAC code high word 6
698 -|=(% style="width: 160px;" %)HSW10118|(% colspan="1" rowspan="2" style="width:282px" %)TSAP settings for HMI in the Siemens logo! 8 protocol|(% style="width:452px" %)HMI local TSAP, which corresponds to the remote TSAP of PLC
922 +|=(% style="width: 160px;" %)HSW10118|(% colspan="1" rowspan="2" style="width:282px" %)TSAP settings for HMI in the Siemens LOGO! 8 protocol|(% style="width:452px" %)HMI local TSAP, which corresponds to the remote TSAP of PLC
699 699  |=(% style="width: 160px;" %)HSW10119|(% style="width:452px" %)HMI remote TSAP, which corresponds to the local TSAP of PLC
700 700  |=(% style="width: 160px;" %)HSW10461~~10493|(% style="width:282px" %)Remote access password|(% style="width:452px" %)8-character remote access password
701 701  |=(% style="width: 160px;" %)HSW10494~~10558|(% style="width:282px" %)Machine ID (Read only)|(% style="width:452px" %)Machine ID for remote access (read only 64-bit)
... ... @@ -777,7 +777,34 @@
777 777  )))
778 778  |=(% style="width: 160px;" %)HSW11760|(% style="width:282px" %)Screensaver countdown|(% style="width:452px" %)Display the countdown to enter the Screensaver, unit: second.
779 779  |=(% style="width: 160px;" %)HSW11761|(% style="width:282px" %)Screensaver screen number|(% style="width:452px" %)Set the screen number for Screensaver
1004 +|=(% style="width: 160px;" %)(((
1005 +HSW11762
1006 +)))|(% style="width:282px" %)(((
1007 +Dynamic screensaver control address
1008 +)))|(% style="width:452px" %)(((
1009 +HSX11762.0=0, initialize with project configuration;
780 780  
1011 +HSX11762.0=1, initialize with special register configuration;
1012 +
1013 +HSX11762.1=0, disable dynamic screensaver;
1014 +
1015 +HSX11762.1=1, enable dynamic screensaver
1016 +)))
1017 +|=(% style="width: 160px;" %)(((
1018 +HSW11763
1019 +)))|(% style="width:282px" %)(((
1020 +Waiting time to enter the dynamic screensaver
1021 +)))|(% style="width:452px" %)(((
1022 +Waiting time when the screen is not operated, range 1~~720 minutes
1023 +)))
1024 +|=(% style="width: 160px;" %)(((
1025 +HSW11764
1026 +)))|(% style="width:282px" %)(((
1027 +Animated screensaver animation type
1028 +)))|(% style="width:452px" %)(((
1029 +~=0: Raster,=1: Blinds,=2: Bubble
1030 +)))
1031 +
781 781  == Serial port communication configuration ==
782 782  
783 783  (% class="table-bordered" %)