Wiki source code of BECKHOFF

Version 3.4 by Joe on 2024/08/26 17:55

Show last authors
1 = TwinCAT_PLC_Ethernet =
2
3 Supported series: Twincat
4
5 **HMI Settings**
6
7 |**Item**|**Settings**|**Note**
8 |Protocol|TwinCAT_PLC_Ethernet|
9 |Connection|Ethernet|
10 |Port NO.|48898|
11 |ADS port|801/811/821/831|
12 |PLC station No.|1
13
14 Choose protocol: TwinCAT_PLC_Ethernet
15
16 (% style="text-align:center" %)
17 [[image:0rPAMOoxzH.png]]
18
19 setting→PLC IP Address→AMS NetId
20
21 (% style="text-align:center" %)
22 [[image:RVUyBW3DPV.png]]
23
24 **PLC Settings**
25
26 Choose Target System→ Search→ Broadcast Search→ choose PLC → Add router→ choose CPU → OK
27
28 (% style="text-align:center" %)
29 [[image:lTAhpgCBWJ.png]]
30
31 Route Settings**→Add Route Dialog→** Broadcast Search→ choose PLC→ modify HMI name → change AmsNetId as 192.168.50.154.1.1 **(HMI IP + .1.1) **→  select the option of IP Address→ set HMI IP in Address info→ Add route
32
33 (% style="text-align:center" %)
34 [[image:gfF9dtMLW7.png]]
35
36 **how to import the tags**
37
38 Open TwinCAT PLC Control→ edit program→ save the program in a path → Project → Rebuild all
39
40 (% style="text-align:center" %)
41 [[image:f925vKrK47.png]]
42
43 (% style="text-align:center" %)
44 [[image:FITLTJJfLP.png]]
45
46 (% class="box infomessage" %)
47 (((
48 Note: After "Rebuild all", there will be a file whose format is "tpy".
49 )))
50
51 Labels mange→ Import Tag From File→ choose the file whose format is "tpy" in the path →Save
52