Changes for page BECKHOFF

Last modified by Devin Chen on 2025/04/07 17:26

From version 9.1
edited by Devin Chen
on 2025/03/22 11:40
Change comment: There is no comment for this version
To version 5.1
edited by Joe
on 2024/08/26 18:20
Change comment: There is no comment for this version

Summary

Details

Page properties
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.DevinChen
1 +XWiki.joe
Content
... ... @@ -1,8 +1,24 @@
1 1  = TwinCAT_PLC_Ethernet =
2 2  
3 -Supported series: Twincat
3 +Supported series: Twincat
4 4  
5 +**HMI Settings**
6 +
7 +|**Item**|**Settings**|**Note**
8 +|Protocol|TwinCAT_PLC_Ethernet|
9 +|Connection|Ethernet|
10 +|Port NO.|48898|
11 +|ADS port|801/811/821/831|
12 +|PLC station No.|1
13 +
14 + Choose protocol: TwinCAT_PLC_Ethernet
15 +
5 5  (% style="text-align:center" %)
17 +[[image:0rPAMOoxzH.png]]
18 +
19 +Setting→PLC IP Address→AMS NetId
20 +
21 +(% style="text-align:center" %)
6 6  [[image:RVUyBW3DPV.png]]
7 7  
8 8  **PLC Settings**
... ... @@ -12,7 +12,7 @@
12 12  (% style="text-align:center" %)
13 13  [[image:lTAhpgCBWJ.png]]
14 14  
15 -Route Settings→Add Route Dialog→ Broadcast Search→ choose PLC→ modify Route Name as HMI name → modify AmsNetId as HMI AmsNetId: 192.168.50.154.1.1 **(HMI IP + .1.1) **→  select the option of IP Address→ set HMI IP in Address info→ Add Route
31 +Route Settings→Add Route Dialog→ Broadcast Search→ choose PLC→ modify HMI name → change AmsNetId as HMI AmsNetId: 192.168.50.154.1.1 **(HMI IP + .1.1) **→  select the option of IP Address→ set HMI IP in Address info→ Add Route
16 16  
17 17  (% style="text-align:center" %)
18 18  [[image:gfF9dtMLW7.png]]
... ... @@ -22,22 +22,6 @@
22 22  (% style="text-align:center" %)
23 23  [[image:0bvTefCtCv.png]]
24 24  
25 -(% id="cke_bm_680S" style="display:none" %)** **(%%)**HMI Settings**
26 -
27 -|**Item**|**Settings**|**Note**
28 -|Protocol|TwinCAT_PLC_Ethernet|
29 -|Connection|Ethernet|
30 -|Port NO.|48898|
31 -|ADS port|801/811/821/831|
32 -|PLC station No.|1
33 -
34 - Choose protocol: TwinCAT_PLC_Ethernet
35 -
36 -(% style="text-align:center" %)
37 -[[image:0rPAMOoxzH.png]]
38 -
39 -Setting→PLC IP Address→AMS NetId (Fill in according to the actual AMS NetId search by PLC)
40 -
41 41  **How to import the tags**
42 42  
43 43  Open TwinCAT PLC Control→ edit program→ save the program in a file → Project → Rebuild all