Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
2.1 | 1 | = TwinCAT_PLC_Ethernet = |
2 | |||
3 | Supported series: Twincat | ||
4 | |||
5 | **HMI Settings** | ||
6 | |||
7 | |**Item**|**Settings**|**Note** | ||
8 | |Protocol|TwinCAT_PLC_Ethernet| | ||
9 | |Connection|Ethernet| | ||
10 | |Port NO.|48898| | ||
11 | |ADS port|801/811/821/831| | ||
12 | |PLC station No.|1 | ||
![]() |
3.1 | 13 | |
![]() |
3.2 | 14 | Choose protocol: TwinCAT_PLC_Ethernet |
15 | |||
16 | (% style="text-align:center" %) | ||
17 | [[image:0rPAMOoxzH.png]] | ||
18 | |||
19 | setting→PLC IP Address→AMS NetId | ||
20 | |||
21 | (% style="text-align:center" %) | ||
22 | [[image:RVUyBW3DPV.png]] | ||
23 | |||
24 | **PLC Settings** | ||
25 | |||
26 | Choose Target System→ Search→ Broadcast Search→ choose PLC → Add router→ choose CPU → OK | ||
27 | |||
28 | (% style="text-align:center" %) | ||
29 | [[image:lTAhpgCBWJ.png]] | ||
30 | |||
![]() |
3.3 | 31 | Route Settings**→Add Route Dialog→** Broadcast Search→ choose PLC→ modify HMI name → change AmsNetId as 192.168.50.154.1.1 **(HMI IP + .1.1) **→ select the option of IP Address→ set HMI IP in Address info→ Add route |
![]() |
3.2 | 32 | |
33 | (% style="text-align:center" %) | ||
34 | [[image:gfF9dtMLW7.png]] | ||
35 | |||
![]() |
3.4 | 36 | **how to import the tags** |
37 | |||
38 | Open TwinCAT PLC Control→ edit program→ save the program in a path → Project → Rebuild all | ||
39 | |||
40 | (% style="text-align:center" %) | ||
41 | [[image:f925vKrK47.png]] | ||
42 | |||
43 | (% style="text-align:center" %) | ||
44 | [[image:FITLTJJfLP.png]] | ||
45 | |||
46 | (% class="box infomessage" %) | ||
47 | ((( | ||
48 | Note: After "Rebuild all", there will be a file whose format is "tpy". | ||
49 | ))) | ||
50 | |||
51 | Labels mange→ Import Tag From File→ choose the file whose format is "tpy" in the path →Save | ||
52 | |||
53 | (% style="text-align:center" %) | ||
54 | [[image:qaOxmsAR2S.png]] | ||