FATEK
Last modified by Hunter on 2023/09/19 15:05
FATEK ASCII
Supported Series: FATEK FBS Series, B1 Series, B1Z Series.
HMI Settings
Item | Settings | Note |
---|---|---|
Protocol | FATEK ASCII | |
Connection | RS232 | |
Baud rate | 9600 | |
Data bit | 7 | |
Parity | Even | |
Stop bit | 1 | |
PLC station No. | 0 |
Address List
Type | Device registers | Format | Range | Note |
---|---|---|---|---|
Bit | X | XDDDDDD | 0~999999 | Input Contact |
Y | YDDDDDD | 0~999999 | Output Relay | |
M | MDDDDDD | 0~999999 | Internal Relay | |
S | SDDDDDD | 0~999999 | Step Relay | |
T | TDDDDDD | 0~999999 | Timer "Time-Up" Status Contact | |
C | CDDDDDD | 0~999999 | Counter "Count-Up" Status Contact | |
Z | ZD | 0 | ||
Word | D | DDDDDDD | 0~999999 | Data Register |
R | RDDDDDD | 0~999999 | ||
WX | WXDDDDDD | 0~999999 | Input Register(IR) | |
WY | WYDDDDDD | 0~999999 | Output Register(OR) | |
WM | WMDDDDDD | 0~999999 | ||
WS | WSDDDDDD | 0~999999 | ||
RT | RTDDDDDD | 0~999999 | Timer Register | |
RC | RCDDDDDD | 0~999999 | Counter Register | |
DRT | DRTDDDDDD | 0~999999 | Double Word Timer Register | |
DRC | DRCDDDDDD | 0~999999 | Double Word Counter Register |
PLC Settings
Create new project, and naming the project, select the specific model according to the actual PLC.
Program the PLC
Connect the PLC to PC by RS232-USB converter cable, and online PLC by using the Auto Check function.
If there is some PLC detected by WinProLadder, it will prompt like the following window, and click [Yes] to go on.
If the current program is not consistent with the program inside the PLC, it will prompt like the following window, click [Yes] to rewrite the PLC.
After download successfully, it will show the window below, click [OK] to close it.
Cable Wiring