Wiki source code of HollySys

Version 3.1 by Hunter on 2023/08/24 18:12

Hide last authors
Hunter 2.1 1 = {{id name="HHollySys"/}}**HollySys** =
2
3 == {{id name="HLKMODBUSRTU"/}}**LK MODBUS RTU** ==
4
5 Supported Series: HollySys LK series CPU
6
7 **HMI Settings**
8
9 |=Item|=Recommended|=Note
10 |=Protocol|HollySys LK MODBUS RTU|
11 |=Connection|RS485|
12 |=Baud rate|38400|
13 |=Stop bits|1|
14 |=Data bits|8|
15 |=Parity|NONE|
16 |=PLC Station No.|1|
17 |=HMI Station No.|0|
18
19 **Address List**
20
21 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
22 |Bit|QX|QXDDDDD.dd|0~~65535.15|
23 |Bit|IX|IXDDDDD.dd|0~~65535.15|
24 |Bit|MX|MXDDDDD.dd|0~~65535.15|
25 |Word|QW|QWDDDDD|0~~99999|
26 |Word|IW|IWDDDDD|0~~99999|
27 |Word|MW|MWDDDDD|0~~99999|
28 |Word|MD|MDDDDDD|0~~99999|
29
30 **Cable Wiring**
31
32 {{id name="IHollysys485.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_eded50dda1febf31.png||alt="Hollysys485.png" height="247" width="400"]]
33
34 == {{id name="HLMMODBUSRTU"/}}**LM MODBUS RTU** ==
35
36 Supported Series: HollySys LM3109/LM3107 PLC
37
38 **HMI Settings**
39
40 |=Item|=Recommended|=Optional|=Note
41 |=Protocol|HollySys LM MODBUS RTU|HollySys LM MODBUS RTU|
42 |=Connection|RS232|RS485|
43 |=Baud rate|38400|38400|
44 |=Stop bits|1|1|
45 |=Data bits|8|8|
46 |=Parity|NONE|NONE|
47 |=PLC Station No.|51|51|
48 |=HMI Station No.|0|0|
49
50 **Address List**
51
52 |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note**
53 |Bit|QX|QXDDDDD.oo|0~~65535.7|
54 |Bit|IX|IXDDDDD.oo|0~~65535.7|
55 |Bit|MX|MXDDDDD.oo|0~~65535.7|
56 |Word|QW|QWDDDDD|0~~99999|
57 |Word|IW|IWDDDDD|0~~99999|
58 |Word|MW|MWDDDDD|0~~99999|
59 |Word|MD|MDDDDDD|0~~99999|
60
61 **Cable Wiring**
62
63 RS232
64
65 {{id name="IHollySysLMModbusRTU.gif"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ab351b690cbc9a0d.gif||alt="HollySys LM Modbus RTU.gif" height="247" width="400"]]
66