Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
2.1 | 1 | = {{id name="HHollySys"/}}**HollySys** = |
2 | |||
3 | == {{id name="HLKMODBUSRTU"/}}**LK MODBUS RTU** == | ||
4 | |||
5 | Supported Series: HollySys LK series CPU | ||
6 | |||
7 | **HMI Settings** | ||
8 | |||
9 | |=Item|=Recommended|=Note | ||
10 | |=Protocol|HollySys LK MODBUS RTU| | ||
11 | |=Connection|RS485| | ||
12 | |=Baud rate|38400| | ||
13 | |=Stop bits|1| | ||
14 | |=Data bits|8| | ||
15 | |=Parity|NONE| | ||
16 | |=PLC Station No.|1| | ||
17 | |=HMI Station No.|0| | ||
18 | |||
19 | **Address List** | ||
20 | |||
21 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
22 | |Bit|QX|QXDDDDD.dd|0~~65535.15| | ||
23 | |Bit|IX|IXDDDDD.dd|0~~65535.15| | ||
24 | |Bit|MX|MXDDDDD.dd|0~~65535.15| | ||
25 | |Word|QW|QWDDDDD|0~~99999| | ||
26 | |Word|IW|IWDDDDD|0~~99999| | ||
27 | |Word|MW|MWDDDDD|0~~99999| | ||
28 | |Word|MD|MDDDDDD|0~~99999| | ||
29 | |||
30 | **Cable Wiring** | ||
31 | |||
32 | {{id name="IHollysys485.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_eded50dda1febf31.png||alt="Hollysys485.png" height="247" width="400"]] | ||
33 | |||
34 | == {{id name="HLMMODBUSRTU"/}}**LM MODBUS RTU** == | ||
35 | |||
36 | Supported Series: HollySys LM3109/LM3107 PLC | ||
37 | |||
38 | **HMI Settings** | ||
39 | |||
40 | |=Item|=Recommended|=Optional|=Note | ||
41 | |=Protocol|HollySys LM MODBUS RTU|HollySys LM MODBUS RTU| | ||
42 | |=Connection|RS232|RS485| | ||
43 | |=Baud rate|38400|38400| | ||
44 | |=Stop bits|1|1| | ||
45 | |=Data bits|8|8| | ||
46 | |=Parity|NONE|NONE| | ||
47 | |=PLC Station No.|51|51| | ||
48 | |=HMI Station No.|0|0| | ||
49 | |||
50 | **Address List** | ||
51 | |||
52 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=**Note** | ||
53 | |Bit|QX|QXDDDDD.oo|0~~65535.7| | ||
54 | |Bit|IX|IXDDDDD.oo|0~~65535.7| | ||
55 | |Bit|MX|MXDDDDD.oo|0~~65535.7| | ||
56 | |Word|QW|QWDDDDD|0~~99999| | ||
57 | |Word|IW|IWDDDDD|0~~99999| | ||
58 | |Word|MW|MWDDDDD|0~~99999| | ||
59 | |Word|MD|MDDDDDD|0~~99999| | ||
60 | |||
61 | **Cable Wiring** | ||
62 | |||
63 | RS232 | ||
64 | |||
65 | {{id name="IHollySysLMModbusRTU.gif"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ab351b690cbc9a0d.gif||alt="HollySys LM Modbus RTU.gif" height="247" width="400"]] | ||
66 | |||
67 | RS485 | ||