Wiki source code of Mitsubishi

Version 47.2 by Hunter on 2023/08/24 18:14

Hide last authors
Hunter 2.1 1 = {{id name="HMitsubishi"/}}**Mitsubishi** =
2
3 == {{id name="HFX1S2C1N2C2NSeries"/}}**FX1S, 1N, 2N Series** ==
4
5 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
6
7 **HMI Settings**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
11 |Connection|RS422/RS485/RS232|
12 |Baud rate|9600~~115200|
13 |Data bit|7/8|
14 |Parity|EVEN/Odd/None|
15 |Stop bit|1/2|
16 |PLC station No.|1~~255|
17
18 **Address List**
19
20 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
21 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
22 |Y|Y|Y o|0~~303237|
23 |M|M|M d|0~~99999|
24 |T|T|T d|0~~99999|
25 |C|C|C d|0~~99999|
26 |S|S|S d|0~~99999|
27 |SM|SM|SM d|8000~~9999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **Cable Wiring**
38
39 * **RS485**
40
41 {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]]
42
43 {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]]
44
45 * **RS422**
46
47 {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]]
48
49 **✎Note:** COM3 only available in PI8000/PI9000 series.
50
51 == {{id name="HFX3U2F3G2F3GASerial"/}}**FX3U/3G/3GA Serial** ==
52
53 **HMI Settings**
54
55 |=**Item**|=**Settings**|=**Note**
56 |Protocol|Mitsubishi FX3U/3G/3GA|
57 |Connection|RS422|
58 |Baud rate|9600~~115200|
59 |Data bit|7/8|
60 |Parity|EVEN/Odd/None|
61 |Stop bit|1/2|
62 |PLC station No.|1~~255|
63
64 **Address List**
65
66 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
67 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
68 |Y|Y|Y o|0~~303237|
69 |M|M|M d|0~~99999|
70 |T|T|T d|0~~99999|
71 |C|C|C d|0~~99999|
72 |S|S|S d|0~~99999|
73 |SM|SM|SM d|8000~~9999|
74 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
75 |Y|Y|Y o|0~~303237|
76 |M|M|M d|0~~99999|
77 |T|T|T d|0~~99999|
78 |C|C|C d|0~~199|
79 |D|D|D d|0~~7999|
80 |S|S|S d|0~~99999|
81 |SD|SD|SD d|8000~~9999|
82
83 **Configure the communication protocol**
84
85 {{id name="Iimage-20220831095222-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_87497ea9be28fa5.png||alt="image-20220831095222-1.png" height="735" width="616"]]
86
87 {{id name="Iimage-20220831095743-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_f1214e2436407de.png||alt="image-20220831095743-2.png" height="905" width="1038"]]
88
89 **Wiring**
90
91 {{id name="Iimage-20220831100314-6.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_feac72c6266d5c9f.png||alt="image-20220831100314-6.png" height="240" width="381"]]
92
93 == {{id name="HFXNOPROTOCOL"/}}**FX NOPROTOCOL** ==
94
95 Mitsubishi FX3G-RS232-BD
96
97 **HMI Settings**
98
99 |=**Item**|=**Settings**|=**Note**
100 |Protocol|Mitsubishi FX NOPROTOCOL|
101 |Connection|RS232|
102 |Baud rate|9600|
103 |Data bit|7|
104 |Parity|EVEN|
105 |Stop bit|1|
106 |PLC station No.|0|
107
108 **Address List**
109
110 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
111 |(% rowspan="8" %)Bit|X|X|X o|0~~303237|
112 |Y|Y|Y o|0~~303237|
113 |M|M|M d|0~~99999|
114 |T|T|T d|0~~99999|
115 |C|C|C d|0~~99999|
116 |S|S|S d|0~~99999|
117 |SM|SM|SM d|8000~~9999|
118 |Lamp|Lamp|Lamp d|0~~0|
119 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
120 |Y|Y|Y o|0~~303237|
121 |M|M|M d|0~~99999|
122 |T|T|T d|0~~99999|
123 |C|C|C d|0~~199|
124 |D|D|D d|0~~7999|
125 |S|S|S d|0~~99999|
126 |SD|SD|SD d|8000~~9999|
127
128 **Configure the communication protocol**
129
130 {{id name="I1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_468060edf3e40542.png||alt="1.png" height="706" width="909"]]
131
132 {{id name="I2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d58ca6ee4453ebce.png||alt="2.png" height="706" width="909"]]
133
134 **Wiring**
135
136 {{id name="I3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1717efe8d969a43c.png||alt="3.png" height="246" width="401"]]
137
138 == {{id name="HFX3UEthernet"/}}**FX3U Ethernet** ==
139
140 Mitsubishi FX3U series PLC
141
142 **HMI Settings**
143
144 |Items|Settings|Note
145 |Protocol|Mitsubishi FX3U Ethernet|
146 |Connection|Ethernet|
147 |Port No.|5009|Must be the same as the PLC setting
148 |PLC station No.|0|
149
150 **Address List**
151
152 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
153 |(% rowspan="7" %)Bit|X|X|X OOO|0~~377|
154 |Y|Y|Y OOO|0~~377|
155 |M|M|M DDDD|0~~7679|
156 |SM|SM|SM DDDD|8000~~8511|
157 |S|S|S DDDD|0~~4095|
158 |TS|TS|TS DDD|0~~511|
159 |CS|CS|CS DDD|0~~255|
160 |(% rowspan="5" %)Word|CN|CN|CN DDD|0~~199|
161 |TN|TN|TN DDD|0~~511|
162 |D|D|D DDDD|0~~7999|
163 |SD|SD|SD DDDD|8000~~8511|
164 |R|R|R DDDDD|0~~32767|
165
166 **Ethernet Module Settings**
167
168 FX3U-ENET-L module configuration
169 Set up the FX3U-ENET-L Ethernet module settings as follows.
170 Select the module location, which in this document is Module 0.
171
172 {{id name="Iimage-20221115140802-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_949d5d77c1d9cf1e.png||alt="image-20221115140802-1.png" height="573" width="706"]]
173
174 Select "Operational setting" to enter the following screen.
175
176 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
177
178 {{id name="Iimage-20221115142728-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dfbfdd586c855c47.png||alt="image-20221115142728-4.png" height="573" width="706"]]
179
180 Select "Open setting" to enter the setting interface, the settings are as follows.
181
182 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
183
184 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
185
186 {{id name="Iimage-20221115142945-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7c01ac15090fcc5b.png||alt="image-20221115142945-5.png" height="549" width="706"]]
187
188 Click on "transter setup" - "PC side I/F setting", see the following figure.
189
190 After setting, the first download must use the programming cable, as shown in the figure; after that, can
191
192 use the IP set in the "Ethernet board" to communicate directly with the network cable.
193
194 {{id name="Iimage-20221115143341-6.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d6fd9ce3b96f99e2.png||alt="image-20221115143341-6.png" height="426" width="712"]]
195
196 Read and write data from the Ethernet module
197
198 {{id name="Iimage-20221115143703-7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_690b3e57b29cfd4b.png||alt="image-20221115143703-7.png" height="549" width="706"]]
199
200 Set "Transter setup" to COM communication, and read or write operation as shown below
201
202 {{id name="Iimage-20221115143809-8.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_b317253742f7151.png||alt="image-20221115143809-8.png" height="549" width="706"]]
203
204 **PLC Settings (GX Works 2)**
205
206 Create a blank FX5U project
207
208 Find Current Connection in the navigation
209
210 {{id name="Iimage-20221115144335-9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d2a46ba9c005cf38.png||alt="image-20221115144335-9.png" height="422" width="706"]]
211
212 Select Connection Channel List
213
214 Select Ethernet board communication
215
216 {{id name="Iimage-20221115144824-10.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8f49721a3e5b0ef9.png||alt="image-20221115144824-10.png" height="421" width="705"]]
217
218 Select Ethernet Module
219 Set the IP address of the PLC
220
221 {{id name="Iimage-20221115145228-11.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1e9a9e29a46a1041.png||alt="image-20221115145228-11.png" height="674" width="708"]]
222
223 Read or write PLC data, in this document is read
224
225 {{id name="Iimage-20221115145553-12.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e3d629103727a423.png||alt="image-20221115145553-12.png" height="424" width="711"]]
226
227 {{id name="Iimage-20221115145559-13.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]]
228
229 **HMI Communication Setting**
230
231 {{id name="Iimage-20221115150003-14.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]]
232
233 {{id name="Iimage-20221115150235-15.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]]
234
235 {{id name="Iimage-20221115145559-13.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]]
236
237 **HMI Communication Setting**
238
239 {{id name="Iimage-20221115150003-14.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]]
240
241 {{id name="Iimage-20221115150235-15.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]]
242
243 == {{id name="HFX5USerial"/}}**FX5U Serial** ==
244
245 Mitsubishi FX5U series PLC
246
247 **HMI Settings**
248
249 |**Item**|**Settings**|**Note**
250 |Protocol|Mitsubishi FX5U|
251 |Connection|RS422/RS485|
252 |Baud rate|9600|
253 |Data bit|7|
254 |Parity|Odd|
255 |Stop bit|1|
256 |PLC station No.|1~~255|Need to be the same as PLC settings
257
258 **Address List**
259
260 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
261 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
262 |Y|Y|Y o|0~~303237|
263 |M|M|M d|0~~99999|
264 |B|B|B h|0~~7FFF|
265 |F|F|F d|0~~32767|
266 |SB|SB|SB h|0~~7FFF|
267 |TS|TS|TS d|0~~1023|
268 |TC|TC|TC d|0~~1023|
269 |STS|STS|STS d|0~~1023|
270 |STC|STC|STS d|0~~1023|
271 |CS|CS|CS d|0~~1023|
272 |CC|CC|CC d|0~~1023|
273 |SM|SM|SM d|0~~9999|
274 |L|L|L d|0~~32767|
275 |S|S|S d|0~~4095|
276 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
277 |TN|TN|TN d|0~~1023|
278 |STN|STN|STN d|0~~1023|
279 |CN|CN|CN d|0~~1023|
280 |R|R|R d|0~~32767|
281 |SW|SW|SW h|0~~7FFF|
282 |Z|Z|Z d|0~~23|
283 |D|D|D d|0~~7999|
284 |SD|SD|SD d|0~~11999|
285
286 **PLC Settings (GX Works 3)**
287
288 Create a blank FX5U project
289
290 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
291
292 {{id name="I12.PLCProtocol_html_5c9cb13fac1e6c93.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a2437897f85ae78.png||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
293
294 Select protocol in the setting item, and set parameters.
295
296 {{id name="I12.PLCProtocol_html_de942589ca070228.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e13b2569bc879dc9.png||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
297
298 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
299
300 {{id name="I12.PLCProtocol_html_387ec7d00b5feb59.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7a585c2e05785534.png||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
301
302 Click the [Apply] button to finish the setting.
303
304 Click download and select the items as below, then click [execute] to download the configuration to PLC.
305
306 {{id name="I12.PLCProtocol_html_cdef1c5ec8cc2105.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_24ac3c2c904fdd5a.png||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
307
308 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
309
310 Done.
311
312 **Cable Wiring**
313
314 * **RS485**
315
316 {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]]
317
318 {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]]
319
320 * **RS422**
321
322 {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]]
323
324 **✎Note:** COM3 only available in PI8000/PI9000 series.
325
326 == {{id name="HL02CPUPort"/}}**L02 CPU Port** ==
327
328 Mitsubishi L02 series CPU built-in serial port.
329
330 **HMI Settings**
331
332 |=**Item**|=**Settings**|=**Note**
333 |Protocol|Mitsubishi L02 CPU Port|
334 |Connection|RS422|
335 |Baud rate|115200|
336 |Data bit|8|
337 |Parity|Odd|
338 |Stop bit|1|
339 |PLC station No.|1~~255|Need to be the same as PLC settings
340
341 **Address List**
342
343 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
344 |Bit|X|X|X h|0~~FFFF|
345 |Bit|Y|Y|Y h|0~~FFFF|
346 |Bit|M|M|M d|0~~9999|
347 |Bit|L|L|L d|0~~9999|
348 |Bit|F|F|F d|0~~9999|
349 |Bit|B|B|B h|0~~FFFF|
350 |Bit|V|V|V d|0~~2047|
351 |Bit|TC|TC|TC d|0~~9999|
352 |Bit|SS|SS|SS d|0~~9999|
353 |Bit|SC|SC|SC d|0~~9999|
354 |Bit|CS|CS|CS d|0~~9999|
355 |Bit|CC|CC|CC d|0~~9999|
356 |Bit|SB|SB|SB h|0~~FFFF|
357 |Bit|SM|SM|SM d|0~~2047|
358 |Bit|STS|STS|STS d|0~~1023|
359 |Bit|S|S|S d|0~~9999|
360 |Bit|DX|DX|DX h|0~~FFFF|
361 |Bit|DY|DY|DY h|0~~FFFF|
362 |Bit|TS|TS|TS d|0~~9999|
363 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
364 |Word|W|W|W h|0~~FFFF|
365 |Word|TN|TN|TN d|0~~99999|
366 |Word|SN|SN|SN d|0~~99999|
367 |Word|CN|CN|CN d|0~~99999|
368 |Word|R|R|R d|0~~99999|
369 |Word|SW|SW|SW h|0~~FFFF|
370 |Word|Z|Z|Z d|0~~99999|
371 |Word|ZR|ZR|ZR h|0~~FFFF|
372 |Word|D|D|D d|0~~99999|
373
374 **Communication Settings**
375
376 {{id name="Iimage-20220831105732-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d08c69b880471768.png||alt="image-20220831105732-3.png" height="735" width="616"]]
377
378 {{id name="Iimage-20220831110004-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6479028a3958c09.png||alt="image-20220831110004-5.png" height="905" width="1038"]]
379
380 **Cable Wiring**
381
382 {{id name="Iimage-20220831105542-2.png"/}}{{id name="Iimage-20220831105529-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_183dee3a2f9d5a5a.png||alt="image-20220831105542-2.png" height="172" width="226"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_679c6b6b2dc84d90.png||alt="image-20220831105529-1.png" height="228" width="492"]]
383
384 Pin Definition Diagram
385
386 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FV-BOX2FV-Net2FTraining2F12520Communication2FWebHome2Fimage-20220825160820-4.png3Frev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png" height="38" width="76"]]
387
388 == {{id name="HL02CPUMELSEC28Ethernet29"/}}**L02 CPU MELSEC(Ethernet)** ==
389
390 Mitsubishi Q series CPU built-in Ethernet port.
391
392 **HMI Settings**
393
394 |**Items**|**Settings**|**Note**
395 |Protocol|MITSUBISHI L02 CPU MELSEC|
396 |Connection|Ethernet|
397 |Port No.|1025|Must be the same as the PLC setting
398 |PLC station No.|0|Must be the same as the PLC setting
399
400 **Address List**
401
402 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
403 |Bit|X|X|X h|0~~FFFF|
404 |Bit|Y|Y|Y h|0~~FFFF|
405 |Bit|M|M|M d|0~~9999|
406 |Bit|L|L|L d|0~~9999|
407 |Bit|F|F|F d|0~~9999|
408 |Bit|B|B|B h|0~~FFFF|
409 |Bit|V|V|V d|0~~2047|
410 |Bit|TC|TC|TC d|0~~9999|
411 |Bit|SS|SS|SS d|0~~9999|
412 |Bit|SC|SC|SC d|0~~9999|
413 |Bit|CS|CS|CS d|0~~9999|
414 |Bit|CC|CC|CC d|0~~9999|
415 |Bit|SB|SB|SB h|0~~FFFF|
416 |Bit|SM|SM|SM d|0~~2047|
417 |Bit|STS|STS|STS d|0~~1023|
418 |Bit|S|S|S d|0~~9999|
419 |Bit|DX|DX|DX h|0~~FFFF|
420 |Bit|DY|DY|DY h|0~~FFFF|
421 |Bit|TS|TS|TS d|0~~9999|
422 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
423 |Word|W|W|W h|0~~FFFF|
424 |Word|TN|TN|TN d|0~~99999|
425 |Word|SN|SN|SN d|0~~99999|
426 |Word|CN|CN|CN d|0~~99999|
427 |Word|R|R|R d|0~~99999|
428 |Word|SW|SW|SW h|0~~FFFF|
429 |Word|Z|Z|Z d|0~~99999|
430 |Word|ZR|ZR|ZR h|0~~FFFF|
431 |Word|D|D|D d|0~~99999|
432
433 **Communication Settings**
434
435 Enable HMI Ethernet in [Project Settings];
436
437 {{id name="I12.PLCProtocol_html_43b671f18153910d.png-1"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
438
439 Set PLC IP in [Device IP] settings;
440
441 {{id name="I12.PLCProtocol_html_38189fae42f6caa7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_376def31824aaed1.png||alt="12.PLC Protocol_html_38189fae42f6caa7.png" height="206" width="600"]]
442
443 **PLC Settings (GX Works2 )**
444
445 Create a project
446
447 Set PLC IP, subnet mask and gateway;
448
449 Select [Binary Code] as communication data code;
450
451 {{id name="Iimage-20221108202109-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8c67f9236cf3c782.png||alt="image-20221108202109-2.png" height="636" width="732"]]
452
453 Set PLC port number, for example 1025
454
455 {{id name="I12.PLCProtocol_html_8d0d1a22d388f70b.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4fafc6de7980df7a.png||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
456
457 Save settings;
458
459 Download project into PLC device;
460
461 Restart PLC device;
462
463 **Cable Wiring**
464
465 {{id name="I12.PLCProtocol_html_2297240b57346b2a.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
466
467 == {{id name="HQJ71C24NMELSEC"/}}**QJ71C24N MELSEC** ==
468
469 Mitsubishi QJ71C24N communication module built-in serial port;
470
471 **HMI Settings**
472
473 |**Items**|**Settings**|**Note**
474 |Protocol|MITSUBISHI QJ71 MELSEC|
475 |Connection|422|
476 |Baud rate|9600|
477 |Data bit|8|
478 |Parity|ODD|
479 |Stop bit|1|
480 |PLC station No.|1~~255|Need to be the same as PLC settings
481
482 **Address List**
483
484 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
485 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
486 |Y|Y|Y FFFF|0~~1FFF|
487 |M|M|M DDDDD|0~~99999|
488 |L|L|L DDDD|0~~8191|
489 |F|F|F DDDD|0~~2047|
490 |V|V|V DDDD|0~~2047|
491 |B|B|B FFFF|0~~1FFF|
492 |TS|TS|TS DDDD|0~~2047|
493 |TC|TC|TC DDDD|0~~2047|
494 |SS|SS|SS DDDD|0~~2047|
495 |SC|SC|SC DDDD|0~~2047|
496 |CS|CS|CS DDDD|0~~1023|
497 |CC|CC|CC DDDD|0~~1023|
498 |SB|SB|SB FFF|0~~7FF|
499 |S|S|S D|0~~8191|
500 |DX|DX|DX FFFF|0~~1FFF|
501 |DY|DY|DY FFFF|0~~1FFF|
502 |SM_|SM_|SM_ DDDD|8000~~9999|
503 |SM|SM|SM DDDD|0~~2047|
504 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
505 |D|D|D DDDDD|0~~12287|
506 |W|W|W FFFF|0~~1FFF|
507 |TN|TN|TN DDDD|0~~2047|
508 |SN|SN|SN DDDD|0~~2047|
509 |CN|CN|CN DDDD|0~~1023|
510 |R|R|R DDDDD|0~~32767|
511 |SW|SW|SW FFF|0~~7FF|
512 |Z|Z|Z D|0~~15|
513 |ZR|ZR|ZR FFFFF|0~~FE7FF|
514
515 **Communication Settings**
516
517 {{id name="Iimage-20221109135738-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6513d4083293f50e.png||alt="image-20221109135738-1.png" height="574" width="540"]]
518
519 {{id name="Iimage-20221109140016-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4856928ac03ccb79.png||alt="image-20221109140016-3.png" height="706" width="909"]]
520
521 Pin Definition Diagram
522
523 {{id name="Iimage-20221109140406-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_708b4368ae664f84.png||alt="image-20221109140406-4.png" height="247" width="397"]]
524
525 == {{id name="HQJ71E71MELSEC"/}}**QJ71E71 MELSEC** ==
526
527 Mitsubishi QJ71E71 Ethernet communication module;
528
529 **HMI Settings**
530
531 |**Items**|**Settings**|**Note**
532 |Protocol|MITSUBISHI QJ71E71 MELSEC|
533 |Connection|Ethernet|
534 |Port No.|1025|Must be the same as the PLC setting
535 |PLC station No.|0|Must be the same as the PLC setting
536
537 **Address List**
538
539 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
540 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
541 |Y|Y|Y h|0~~1FFF|
542 |M|M|M d|0~~99999|
543 |L|L|L d|0~~8191|
544 |F|F|F d|0~~2047|
545 |B|B|B h|0~~1FFF|
546 |V|V|V d|0~~2047|
547 |TS|TS|TS d|0~~2047|
548 |TC|TC|TC d|0~~2047|
549 |SS|SS|SS d|0~~2047|
550 |SC|SC|SC d|0~~2047|
551 |CS|CS|CS d|0~~1023|
552 |CC|CC|CC d|0~~1023|
553 |SB|SB|SB h|0~~7FF|
554 |S|S|S d|0~~8191|
555 |DX|DX|DX h|0~~1FFF|
556 |DY|DY|DY h|0~~1FFF|
557 |SM|SM|SM d|8000~~9999|
558 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
559 |D|D|D d|0~~12287|
560 |W|W|W h|0~~1FFF|
561 |TN|TN|TN d|0~~2047|
562 |SN|SN|SN d|0~~2047|
563 |CN|CN|CN d|0~~1023|
564 |R|R|R d|0~~32767|
565 |SW|SW|SW h|0~~7FF|
566 |Z|Z|Z d|0~~15|
567 |ZR|ZR|ZR h|0~~FE7FF|
568
569 **HMI Communication Settings**
570
571 1) Enable HMI Ethernet in [Project Settings];
572
573 {{id name="I12.PLCProtocol_html_43b671f18153910d.png-2"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
574
575 2) Set PLC IP in [Device IP] settings
576
577 {{id name="Iimage-20221119164628-1.png"/}};[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a672b85489bc3ccf.png||alt="image-20221119164628-1.png" height="502" width="646"]]
578
579 **PLC Settings(GX Works2)**
580
581 * Click [Ethernet/CC IE/MELSECNET];
582 * Please select [Ethernet] as network type;
583 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
584 * Select [Online] as Mode;
585 * {{id name="Iimage-20221119164958-2.png"/}}{{id name="I12.PLCProtocol_html_acd084d845da380e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_5299cbf3c8268344.png||alt="image-20221119164958-2.png" height="356" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_cca6d562ae3a78f7.png||alt="12.PLC Protocol_html_acd084d845da380e.png" height="300" width="554"]]
586 * Click [Operation setting] to set IP;
587 * Select [Binary Code] as [Communication Data Code];
588 * {{id name="Iimage-20221119165129-3.png"/}}{{id name="I12.PLCProtocol_html_a972e671d2bb9150.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad7bac4c325df08d.png||alt="image-20221119165129-3.png" height="381" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_bbfa45d44f415527.png||alt="12.PLC Protocol_html_a972e671d2bb9150.png" height="304" width="553"]]
589 * Click [Open setting]
590 * Set protocol: TCP;
591 * Set [unpassive] in [Open system];
592 * Set [receive] in [Fixed buffer];
593 * Set [procedure Exist] in [Fixed buffer communication];
594 * Disable [Pairing open];
595 * Set [No confirm] in [Existence confirmation];
596 * Host station port number: 5009;
597 * {{id name="I12.PLCProtocol_html_f2c432006cdd2f9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_9abc6f2f8ad89136.png||alt="12.PLC Protocol_html_f2c432006cdd2f9.png" height="220" width="553"]] Save settings;
598 * {{id name="Iimage-20221119165342-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_143120787717f1e3.png||alt="image-20221119165342-4.png" height="387" width="620"]]
599 * Download project into PLC and restart it
600
601 **Cable Wiring**
602
603 {{id name="I12.PLCProtocol_html_2297240b57346b2a.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]