Wiki source code of Mitsubishi

Version 52.1 by Devin Chen on 2023/09/14 17:54

Hide last authors
Hunter 2.1 1 = {{id name="HMitsubishi"/}}**Mitsubishi** =
2
3 == {{id name="HFX1S2C1N2C2NSeries"/}}**FX1S, 1N, 2N Series** ==
4
5 Supported Series: Mitsubishi FX1S, FX1N, FX2N series
6
7 **HMI Settings**
8
9 |**Item**|**Settings**|**Note**
10 |Protocol|Mitsubishi FX1S/FX1N/FX2N|
11 |Connection|RS422/RS485/RS232|
12 |Baud rate|9600~~115200|
13 |Data bit|7/8|
14 |Parity|EVEN/Odd/None|
15 |Stop bit|1/2|
16 |PLC station No.|1~~255|
17
18 **Address List**
19
20 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
21 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
22 |Y|Y|Y o|0~~303237|
23 |M|M|M d|0~~99999|
24 |T|T|T d|0~~99999|
25 |C|C|C d|0~~99999|
26 |S|S|S d|0~~99999|
27 |SM|SM|SM d|8000~~9999|
28 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
29 |Y|Y|Y o|0~~303237|
30 |M|M|M d|0~~99999|
31 |T|T|T d|0~~99999|
32 |C|C|C d|0~~199|
33 |D|D|D d|0~~7999|
34 |S|S|S d|0~~99999|
35 |SD|SD|SD d|8000~~9999|
36
37 **Cable Wiring**
38
39 * **RS485**
40
41 {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]]
42
43 {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]]
44
45 * **RS422**
46
47 {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]]
48
49 **✎Note:** COM3 only available in PI8000/PI9000 series.
50
51 == {{id name="HFX3U2F3G2F3GASerial"/}}**FX3U/3G/3GA Serial** ==
52
53 **HMI Settings**
54
55 |=**Item**|=**Settings**|=**Note**
56 |Protocol|Mitsubishi FX3U/3G/3GA|
57 |Connection|RS422|
58 |Baud rate|9600~~115200|
59 |Data bit|7/8|
60 |Parity|EVEN/Odd/None|
61 |Stop bit|1/2|
62 |PLC station No.|1~~255|
63
64 **Address List**
65
66 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
67 |(% rowspan="7" %)Bit|X|X|Xo|0~~303237|
68 |Y|Y|Y o|0~~303237|
69 |M|M|M d|0~~99999|
70 |T|T|T d|0~~99999|
71 |C|C|C d|0~~99999|
72 |S|S|S d|0~~99999|
73 |SM|SM|SM d|8000~~9999|
74 |(% rowspan="8" %)Word|X|X|Xo|0~~303237|
75 |Y|Y|Y o|0~~303237|
76 |M|M|M d|0~~99999|
77 |T|T|T d|0~~99999|
78 |C|C|C d|0~~199|
79 |D|D|D d|0~~7999|
80 |S|S|S d|0~~99999|
81 |SD|SD|SD d|8000~~9999|
82
83 **Configure the communication protocol**
84
85 {{id name="Iimage-20220831095222-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_87497ea9be28fa5.png||alt="image-20220831095222-1.png" height="735" width="616"]]
86
87 {{id name="Iimage-20220831095743-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_f1214e2436407de.png||alt="image-20220831095743-2.png" height="905" width="1038"]]
88
Devin Chen 48.1 89 **PLC Setting:**
90
91 ①Open GX Works2, create a new PLC project or open the project that has been created.
92 Create new project: [Project]→[New]→[Series] FXCPU→[Type] FX3G/FX3GC→[OK].
93
94 (% style="text-align:center" %)
95 [[image:1.2.png]]
96
97 ②PLC Default Parameters:
98 [Connection type]RS422;[Baud rate]9600, [Data bit]7, [Stop bit]1,[Parity]EVEN; [Station number]0
99 Note:The serial port parameters should be set depending on field requirements
100
101 ③PC and PLC connection:
102
103 [All connection]→[Connection 1]→[Transfer Setup Connection1]→[Serial USB]→RS-232C: PC and PLC are connected by USB to RS232 adapter,choose corresponding [COM Port]COM 5 →[Transmission speed]9.6Kbps→[setup] →[Parity]EVEN→[Data bits]7→[Stop bits]1→[OK]
104
105 (% style="text-align:center" %)
106 [[image:1.5.1.png]]
107
108 Connection test:when connection is OK,the GX Works2 prompts “Successfully connected with the FX3G/FX3GCCPU.”
109
110 (% style="text-align:center" %)
111 [[image:1.5.2.png]]
112
Hunter 2.1 113 **Wiring**
114
Devin Chen 50.1 115 {{id name="Iimage-20220831100314-6.png"/}}
Hunter 2.1 116
Devin Chen 50.1 117 (% style="text-align:center" %)
118 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_feac72c6266d5c9f.png||alt="image-20220831100314-6.png" height="240" width="381"]]
119
Hunter 2.1 120 == {{id name="HFXNOPROTOCOL"/}}**FX NOPROTOCOL** ==
121
122 Mitsubishi FX3G-RS232-BD
123
124 **HMI Settings**
125
126 |=**Item**|=**Settings**|=**Note**
127 |Protocol|Mitsubishi FX NOPROTOCOL|
128 |Connection|RS232|
129 |Baud rate|9600|
130 |Data bit|7|
131 |Parity|EVEN|
132 |Stop bit|1|
133 |PLC station No.|0|
134
135 **Address List**
136
137 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
138 |(% rowspan="8" %)Bit|X|X|X o|0~~303237|
139 |Y|Y|Y o|0~~303237|
140 |M|M|M d|0~~99999|
141 |T|T|T d|0~~99999|
142 |C|C|C d|0~~99999|
143 |S|S|S d|0~~99999|
144 |SM|SM|SM d|8000~~9999|
145 |Lamp|Lamp|Lamp d|0~~0|
146 |(% rowspan="8" %)Word|X|X|X o|0~~303237|
147 |Y|Y|Y o|0~~303237|
148 |M|M|M d|0~~99999|
149 |T|T|T d|0~~99999|
150 |C|C|C d|0~~199|
151 |D|D|D d|0~~7999|
152 |S|S|S d|0~~99999|
153 |SD|SD|SD d|8000~~9999|
154
155 **Configure the communication protocol**
156
157 {{id name="I1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_468060edf3e40542.png||alt="1.png" height="706" width="909"]]
158
159 {{id name="I2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d58ca6ee4453ebce.png||alt="2.png" height="706" width="909"]]
160
161 **Wiring**
162
163 {{id name="I3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1717efe8d969a43c.png||alt="3.png" height="246" width="401"]]
164
165 == {{id name="HFX3UEthernet"/}}**FX3U Ethernet** ==
166
167 Mitsubishi FX3U series PLC
168
169 **HMI Settings**
170
171 |Items|Settings|Note
172 |Protocol|Mitsubishi FX3U Ethernet|
173 |Connection|Ethernet|
174 |Port No.|5009|Must be the same as the PLC setting
175 |PLC station No.|0|
176
177 **Address List**
178
179 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
180 |(% rowspan="7" %)Bit|X|X|X OOO|0~~377|
181 |Y|Y|Y OOO|0~~377|
182 |M|M|M DDDD|0~~7679|
183 |SM|SM|SM DDDD|8000~~8511|
184 |S|S|S DDDD|0~~4095|
185 |TS|TS|TS DDD|0~~511|
186 |CS|CS|CS DDD|0~~255|
187 |(% rowspan="5" %)Word|CN|CN|CN DDD|0~~199|
188 |TN|TN|TN DDD|0~~511|
189 |D|D|D DDDD|0~~7999|
190 |SD|SD|SD DDDD|8000~~8511|
191 |R|R|R DDDDD|0~~32767|
192
193 **Ethernet Module Settings**
194
195 FX3U-ENET-L module configuration
196 Set up the FX3U-ENET-L Ethernet module settings as follows.
197 Select the module location, which in this document is Module 0.
198
199 {{id name="Iimage-20221115140802-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_949d5d77c1d9cf1e.png||alt="image-20221115140802-1.png" height="573" width="706"]]
200
201 Select "Operational setting" to enter the following screen.
202
203 The Ethernet module IP is set to 192.168.39.254 in this document, and other options are default.
204
205 {{id name="Iimage-20221115142728-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dfbfdd586c855c47.png||alt="image-20221115142728-4.png" height="573" width="706"]]
206
207 Select "Open setting" to enter the setting interface, the settings are as follows.
208
209 The third item "Protocol" selects TCP, and "Open system" selects MELSOFT connection, which allows the
210
211 Mitsubishi programming software GX works2 to communicate with the FX3U via the Ethernet module.
212
213 {{id name="Iimage-20221115142945-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7c01ac15090fcc5b.png||alt="image-20221115142945-5.png" height="549" width="706"]]
214
215 Click on "transter setup" - "PC side I/F setting", see the following figure.
216
217 After setting, the first download must use the programming cable, as shown in the figure; after that, can
218
219 use the IP set in the "Ethernet board" to communicate directly with the network cable.
220
221 {{id name="Iimage-20221115143341-6.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d6fd9ce3b96f99e2.png||alt="image-20221115143341-6.png" height="426" width="712"]]
222
223 Read and write data from the Ethernet module
224
225 {{id name="Iimage-20221115143703-7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_690b3e57b29cfd4b.png||alt="image-20221115143703-7.png" height="549" width="706"]]
226
227 Set "Transter setup" to COM communication, and read or write operation as shown below
228
229 {{id name="Iimage-20221115143809-8.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_b317253742f7151.png||alt="image-20221115143809-8.png" height="549" width="706"]]
230
231 **PLC Settings (GX Works 2)**
232
233 Create a blank FX5U project
234
235 Find Current Connection in the navigation
236
237 {{id name="Iimage-20221115144335-9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d2a46ba9c005cf38.png||alt="image-20221115144335-9.png" height="422" width="706"]]
238
239 Select Connection Channel List
240
241 Select Ethernet board communication
242
243 {{id name="Iimage-20221115144824-10.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8f49721a3e5b0ef9.png||alt="image-20221115144824-10.png" height="421" width="705"]]
244
245 Select Ethernet Module
246 Set the IP address of the PLC
247
248 {{id name="Iimage-20221115145228-11.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_1e9a9e29a46a1041.png||alt="image-20221115145228-11.png" height="674" width="708"]]
249
250 Read or write PLC data, in this document is read
251
252 {{id name="Iimage-20221115145553-12.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e3d629103727a423.png||alt="image-20221115145553-12.png" height="424" width="711"]]
253
254 {{id name="Iimage-20221115145559-13.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]]
255
256 **HMI Communication Setting**
257
258 {{id name="Iimage-20221115150003-14.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]]
259
260 {{id name="Iimage-20221115150235-15.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]]
261
262 {{id name="Iimage-20221115145559-13.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7f29923ebcb670d1.png||alt="image-20221115145559-13.png" height="424" width="711"]]
263
264 **HMI Communication Setting**
265
266 {{id name="Iimage-20221115150003-14.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_11364c6da9a4fd72.png||alt="image-20221115150003-14.png" height="425" width="712"]]
267
268 {{id name="Iimage-20221115150235-15.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4c73e8982af3231.png||alt="image-20221115150235-15.png" height="427" width="713"]]
269
270 == {{id name="HFX5USerial"/}}**FX5U Serial** ==
271
272 Mitsubishi FX5U series PLC
273
274 **HMI Settings**
275
276 |**Item**|**Settings**|**Note**
277 |Protocol|Mitsubishi FX5U|
278 |Connection|RS422/RS485|
279 |Baud rate|9600|
280 |Data bit|7|
281 |Parity|Odd|
282 |Stop bit|1|
Devin Chen 51.1 283 |PLC station No.|0~~255|Need to be the same as PLC settings
Hunter 2.1 284
285 **Address List**
286
287 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
288 |(% rowspan="15" %)Bit|X|X|X o|0~~303237|
289 |Y|Y|Y o|0~~303237|
290 |M|M|M d|0~~99999|
291 |B|B|B h|0~~7FFF|
292 |F|F|F d|0~~32767|
293 |SB|SB|SB h|0~~7FFF|
294 |TS|TS|TS d|0~~1023|
295 |TC|TC|TC d|0~~1023|
296 |STS|STS|STS d|0~~1023|
297 |STC|STC|STS d|0~~1023|
298 |CS|CS|CS d|0~~1023|
299 |CC|CC|CC d|0~~1023|
300 |SM|SM|SM d|0~~9999|
301 |L|L|L d|0~~32767|
302 |S|S|S d|0~~4095|
303 |(% rowspan="9" %)Word|W|W|W h|0~~3FF|
304 |TN|TN|TN d|0~~1023|
305 |STN|STN|STN d|0~~1023|
306 |CN|CN|CN d|0~~1023|
307 |R|R|R d|0~~32767|
308 |SW|SW|SW h|0~~7FFF|
309 |Z|Z|Z d|0~~23|
310 |D|D|D d|0~~7999|
311 |SD|SD|SD d|0~~11999|
312
313 **PLC Settings (GX Works 3)**
314
315 Create a blank FX5U project
316
317 Find the 485 serial port module in the system navigation bar and double click to enter the settings.
318
319 {{id name="I12.PLCProtocol_html_5c9cb13fac1e6c93.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a2437897f85ae78.png||alt="12.PLC Protocol_html_5c9cb13fac1e6c93.png" height="462" width="200"]]
320
321 Select protocol in the setting item, and set parameters.
322
323 {{id name="I12.PLCProtocol_html_de942589ca070228.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e13b2569bc879dc9.png||alt="12.PLC Protocol_html_de942589ca070228.png" height="324" width="600"]]
324
325 Set station number, and [Message Pattern] (Pattern 1 or Pattern 4)
326
327 {{id name="I12.PLCProtocol_html_387ec7d00b5feb59.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7a585c2e05785534.png||alt="12.PLC Protocol_html_387ec7d00b5feb59.png" height="323" width="600"]]
328
329 Click the [Apply] button to finish the setting.
330
331 Click download and select the items as below, then click [execute] to download the configuration to PLC.
332
333 {{id name="I12.PLCProtocol_html_cdef1c5ec8cc2105.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_24ac3c2c904fdd5a.png||alt="12.PLC Protocol_html_cdef1c5ec8cc2105.png" height="434" width="600"]]
334
335 As soon as download is completed, connect PLC with serial port, then configure it in the [Specify Connection Destination Connection].
336
337 Done.
338
339 **Cable Wiring**
340
341 * **RS485**
342
Devin Chen 52.1 343 {{id name="I12.PLCProtocol_html_d4012bdeb4ce4aae.png-1"/}}
Hunter 2.1 344
Devin Chen 52.1 345 (% style="text-align:center" %)
346 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ddcfa89a7e788c14.png||alt="12.PLC Protocol_html_d4012bdeb4ce4aae.png" height="244" width="394"]]
Hunter 2.1 347
Devin Chen 52.1 348 {{id name="I12.PLCProtocol_html_4bf57ad8d44eacc4.png-1"/}}
349
350 (% style="text-align:center" %)
351 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_64f32195c6a29424.png||alt="12.PLC Protocol_html_4bf57ad8d44eacc4.png" height="244" width="394"]]
352
Hunter 2.1 353 * **RS422**
354
Devin Chen 52.1 355 {{id name="I12.PLCProtocol_html_f8a6bebc5792960d.png-1"/}}
Hunter 2.1 356
Devin Chen 52.1 357 (% style="text-align:center" %)
358 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e27e979a8eaf8f17.png||alt="12.PLC Protocol_html_f8a6bebc5792960d.png" height="253" width="402"]]
359
360 (% style="text-align:center" %)
361 [[image:RS422.png]]
362
Hunter 2.1 363 **✎Note:** COM3 only available in PI8000/PI9000 series.
364
365 == {{id name="HL02CPUPort"/}}**L02 CPU Port** ==
366
367 Mitsubishi L02 series CPU built-in serial port.
368
369 **HMI Settings**
370
371 |=**Item**|=**Settings**|=**Note**
372 |Protocol|Mitsubishi L02 CPU Port|
373 |Connection|RS422|
374 |Baud rate|115200|
375 |Data bit|8|
376 |Parity|Odd|
377 |Stop bit|1|
378 |PLC station No.|1~~255|Need to be the same as PLC settings
379
380 **Address List**
381
382 |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
383 |Bit|X|X|X h|0~~FFFF|
384 |Bit|Y|Y|Y h|0~~FFFF|
385 |Bit|M|M|M d|0~~9999|
386 |Bit|L|L|L d|0~~9999|
387 |Bit|F|F|F d|0~~9999|
388 |Bit|B|B|B h|0~~FFFF|
389 |Bit|V|V|V d|0~~2047|
390 |Bit|TC|TC|TC d|0~~9999|
391 |Bit|SS|SS|SS d|0~~9999|
392 |Bit|SC|SC|SC d|0~~9999|
393 |Bit|CS|CS|CS d|0~~9999|
394 |Bit|CC|CC|CC d|0~~9999|
395 |Bit|SB|SB|SB h|0~~FFFF|
396 |Bit|SM|SM|SM d|0~~2047|
397 |Bit|STS|STS|STS d|0~~1023|
398 |Bit|S|S|S d|0~~9999|
399 |Bit|DX|DX|DX h|0~~FFFF|
400 |Bit|DY|DY|DY h|0~~FFFF|
401 |Bit|TS|TS|TS d|0~~9999|
402 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
403 |Word|W|W|W h|0~~FFFF|
404 |Word|TN|TN|TN d|0~~99999|
405 |Word|SN|SN|SN d|0~~99999|
406 |Word|CN|CN|CN d|0~~99999|
407 |Word|R|R|R d|0~~99999|
408 |Word|SW|SW|SW h|0~~FFFF|
409 |Word|Z|Z|Z d|0~~99999|
410 |Word|ZR|ZR|ZR h|0~~FFFF|
411 |Word|D|D|D d|0~~99999|
412
413 **Communication Settings**
414
415 {{id name="Iimage-20220831105732-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d08c69b880471768.png||alt="image-20220831105732-3.png" height="735" width="616"]]
416
417 {{id name="Iimage-20220831110004-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6479028a3958c09.png||alt="image-20220831110004-5.png" height="905" width="1038"]]
418
419 **Cable Wiring**
420
421 {{id name="Iimage-20220831105542-2.png"/}}{{id name="Iimage-20220831105529-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_183dee3a2f9d5a5a.png||alt="image-20220831105542-2.png" height="172" width="226"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_679c6b6b2dc84d90.png||alt="image-20220831105529-1.png" height="228" width="492"]]
422
423 Pin Definition Diagram
424
425 {{id name="Ihttps:2F2Fdocs.we-con.com.cn2Fbin2Fdownload2FV-BOX2FV-Net2FTraining2F12520Communication2FWebHome2Fimage-20220825160820-4.png3Frev3D1.1"/}}[[image:https://docs.we-con.com.cn/bin/download/V-BOX/V-Net/Training/1%20Communication/WebHome/image-20220825160820-4.png?rev=1.1||alt="image-20220825160820-4.png" height="38" width="76"]]
426
427 == {{id name="HL02CPUMELSEC28Ethernet29"/}}**L02 CPU MELSEC(Ethernet)** ==
428
429 Mitsubishi Q series CPU built-in Ethernet port.
430
431 **HMI Settings**
432
433 |**Items**|**Settings**|**Note**
434 |Protocol|MITSUBISHI L02 CPU MELSEC|
435 |Connection|Ethernet|
436 |Port No.|1025|Must be the same as the PLC setting
437 |PLC station No.|0|Must be the same as the PLC setting
438
439 **Address List**
440
441 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
442 |Bit|X|X|X h|0~~FFFF|
443 |Bit|Y|Y|Y h|0~~FFFF|
444 |Bit|M|M|M d|0~~9999|
445 |Bit|L|L|L d|0~~9999|
446 |Bit|F|F|F d|0~~9999|
447 |Bit|B|B|B h|0~~FFFF|
448 |Bit|V|V|V d|0~~2047|
449 |Bit|TC|TC|TC d|0~~9999|
450 |Bit|SS|SS|SS d|0~~9999|
451 |Bit|SC|SC|SC d|0~~9999|
452 |Bit|CS|CS|CS d|0~~9999|
453 |Bit|CC|CC|CC d|0~~9999|
454 |Bit|SB|SB|SB h|0~~FFFF|
455 |Bit|SM|SM|SM d|0~~2047|
456 |Bit|STS|STS|STS d|0~~1023|
457 |Bit|S|S|S d|0~~9999|
458 |Bit|DX|DX|DX h|0~~FFFF|
459 |Bit|DY|DY|DY h|0~~FFFF|
460 |Bit|TS|TS|TS d|0~~9999|
461 |Bit|Dbit|Dbit|Dbit d.d|0~~99999.0~~15|
462 |Word|W|W|W h|0~~FFFF|
463 |Word|TN|TN|TN d|0~~99999|
464 |Word|SN|SN|SN d|0~~99999|
465 |Word|CN|CN|CN d|0~~99999|
466 |Word|R|R|R d|0~~99999|
467 |Word|SW|SW|SW h|0~~FFFF|
468 |Word|Z|Z|Z d|0~~99999|
469 |Word|ZR|ZR|ZR h|0~~FFFF|
470 |Word|D|D|D d|0~~99999|
471
472 **Communication Settings**
473
474 Enable HMI Ethernet in [Project Settings];
475
476 {{id name="I12.PLCProtocol_html_43b671f18153910d.png-1"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
477
478 Set PLC IP in [Device IP] settings;
479
480 {{id name="I12.PLCProtocol_html_38189fae42f6caa7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_376def31824aaed1.png||alt="12.PLC Protocol_html_38189fae42f6caa7.png" height="206" width="600"]]
481
482 **PLC Settings (GX Works2 )**
483
484 Create a project
485
486 Set PLC IP, subnet mask and gateway;
487
488 Select [Binary Code] as communication data code;
489
490 {{id name="Iimage-20221108202109-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_8c67f9236cf3c782.png||alt="image-20221108202109-2.png" height="636" width="732"]]
491
492 Set PLC port number, for example 1025
493
494 {{id name="I12.PLCProtocol_html_8d0d1a22d388f70b.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4fafc6de7980df7a.png||alt="12.PLC Protocol_html_8d0d1a22d388f70b.png" height="524" width="600"]]
495
496 Save settings;
497
498 Download project into PLC device;
499
500 Restart PLC device;
501
502 **Cable Wiring**
503
504 {{id name="I12.PLCProtocol_html_2297240b57346b2a.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]
505
506 == {{id name="HQJ71C24NMELSEC"/}}**QJ71C24N MELSEC** ==
507
508 Mitsubishi QJ71C24N communication module built-in serial port;
509
510 **HMI Settings**
511
512 |**Items**|**Settings**|**Note**
513 |Protocol|MITSUBISHI QJ71 MELSEC|
514 |Connection|422|
515 |Baud rate|9600|
516 |Data bit|8|
517 |Parity|ODD|
518 |Stop bit|1|
519 |PLC station No.|1~~255|Need to be the same as PLC settings
520
521 **Address List**
522
523 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
524 |(% rowspan="19" %)Bit|X|X|X FFFF|0~~1FFF|
525 |Y|Y|Y FFFF|0~~1FFF|
526 |M|M|M DDDDD|0~~99999|
527 |L|L|L DDDD|0~~8191|
528 |F|F|F DDDD|0~~2047|
529 |V|V|V DDDD|0~~2047|
530 |B|B|B FFFF|0~~1FFF|
531 |TS|TS|TS DDDD|0~~2047|
532 |TC|TC|TC DDDD|0~~2047|
533 |SS|SS|SS DDDD|0~~2047|
534 |SC|SC|SC DDDD|0~~2047|
535 |CS|CS|CS DDDD|0~~1023|
536 |CC|CC|CC DDDD|0~~1023|
537 |SB|SB|SB FFF|0~~7FF|
538 |S|S|S D|0~~8191|
539 |DX|DX|DX FFFF|0~~1FFF|
540 |DY|DY|DY FFFF|0~~1FFF|
541 |SM_|SM_|SM_ DDDD|8000~~9999|
542 |SM|SM|SM DDDD|0~~2047|
543 |(% rowspan="10" %)Word|SD|SD|SD DDDD|0~~2047|
544 |D|D|D DDDDD|0~~12287|
545 |W|W|W FFFF|0~~1FFF|
546 |TN|TN|TN DDDD|0~~2047|
547 |SN|SN|SN DDDD|0~~2047|
548 |CN|CN|CN DDDD|0~~1023|
549 |R|R|R DDDDD|0~~32767|
550 |SW|SW|SW FFF|0~~7FF|
551 |Z|Z|Z D|0~~15|
552 |ZR|ZR|ZR FFFFF|0~~FE7FF|
553
554 **Communication Settings**
555
556 {{id name="Iimage-20221109135738-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6513d4083293f50e.png||alt="image-20221109135738-1.png" height="574" width="540"]]
557
558 {{id name="Iimage-20221109140016-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4856928ac03ccb79.png||alt="image-20221109140016-3.png" height="706" width="909"]]
559
560 Pin Definition Diagram
561
562 {{id name="Iimage-20221109140406-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_708b4368ae664f84.png||alt="image-20221109140406-4.png" height="247" width="397"]]
563
564 == {{id name="HQJ71E71MELSEC"/}}**QJ71E71 MELSEC** ==
565
566 Mitsubishi QJ71E71 Ethernet communication module;
567
568 **HMI Settings**
569
570 |**Items**|**Settings**|**Note**
571 |Protocol|MITSUBISHI QJ71E71 MELSEC|
572 |Connection|Ethernet|
573 |Port No.|1025|Must be the same as the PLC setting
574 |PLC station No.|0|Must be the same as the PLC setting
575
576 **Address List**
577
578 |**Type**|**Device registers**|**HMI registers**|**Format**|**Range**|**Note**
579 |(% rowspan="18" %)Bit|X|X|X h|0~~1FFF|
580 |Y|Y|Y h|0~~1FFF|
581 |M|M|M d|0~~99999|
582 |L|L|L d|0~~8191|
583 |F|F|F d|0~~2047|
584 |B|B|B h|0~~1FFF|
585 |V|V|V d|0~~2047|
586 |TS|TS|TS d|0~~2047|
587 |TC|TC|TC d|0~~2047|
588 |SS|SS|SS d|0~~2047|
589 |SC|SC|SC d|0~~2047|
590 |CS|CS|CS d|0~~1023|
591 |CC|CC|CC d|0~~1023|
592 |SB|SB|SB h|0~~7FF|
593 |S|S|S d|0~~8191|
594 |DX|DX|DX h|0~~1FFF|
595 |DY|DY|DY h|0~~1FFF|
596 |SM|SM|SM d|8000~~9999|
597 |(% rowspan="10" %)Word|SD|SD|SD d|0~~2047|
598 |D|D|D d|0~~12287|
599 |W|W|W h|0~~1FFF|
600 |TN|TN|TN d|0~~2047|
601 |SN|SN|SN d|0~~2047|
602 |CN|CN|CN d|0~~1023|
603 |R|R|R d|0~~32767|
604 |SW|SW|SW h|0~~7FF|
605 |Z|Z|Z d|0~~15|
606 |ZR|ZR|ZR h|0~~FE7FF|
607
608 **HMI Communication Settings**
609
610 1) Enable HMI Ethernet in [Project Settings];
611
612 {{id name="I12.PLCProtocol_html_43b671f18153910d.png-2"/}} [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="107" width="405"]]
613
614 2) Set PLC IP in [Device IP] settings
615
616 {{id name="Iimage-20221119164628-1.png"/}};[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a672b85489bc3ccf.png||alt="image-20221119164628-1.png" height="502" width="646"]]
617
618 **PLC Settings(GX Works2)**
619
620 * Click [Ethernet/CC IE/MELSECNET];
621 * Please select [Ethernet] as network type;
622 * Set station I/O number according to situation (For example, 0020 means that the module is connected to PLC CPU in first order);
623 * Select [Online] as Mode;
624 * {{id name="Iimage-20221119164958-2.png"/}}{{id name="I12.PLCProtocol_html_acd084d845da380e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_5299cbf3c8268344.png||alt="image-20221119164958-2.png" height="356" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_cca6d562ae3a78f7.png||alt="12.PLC Protocol_html_acd084d845da380e.png" height="300" width="554"]]
625 * Click [Operation setting] to set IP;
626 * Select [Binary Code] as [Communication Data Code];
627 * {{id name="Iimage-20221119165129-3.png"/}}{{id name="I12.PLCProtocol_html_a972e671d2bb9150.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ad7bac4c325df08d.png||alt="image-20221119165129-3.png" height="381" width="611"]] [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_bbfa45d44f415527.png||alt="12.PLC Protocol_html_a972e671d2bb9150.png" height="304" width="553"]]
628 * Click [Open setting]
629 * Set protocol: TCP;
630 * Set [unpassive] in [Open system];
631 * Set [receive] in [Fixed buffer];
632 * Set [procedure Exist] in [Fixed buffer communication];
633 * Disable [Pairing open];
634 * Set [No confirm] in [Existence confirmation];
635 * Host station port number: 5009;
636 * {{id name="I12.PLCProtocol_html_f2c432006cdd2f9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_9abc6f2f8ad89136.png||alt="12.PLC Protocol_html_f2c432006cdd2f9.png" height="220" width="553"]] Save settings;
637 * {{id name="Iimage-20221119165342-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_143120787717f1e3.png||alt="image-20221119165342-4.png" height="387" width="620"]]
638 * Download project into PLC and restart it
639
640 **Cable Wiring**
641
642 {{id name="I12.PLCProtocol_html_2297240b57346b2a.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="401"]]