1 = {{id name="HPanasonic"/}}Panasonic =
2
3 == {{id name="HFPMEWTOCOL"/}}**FP Series Serial** ==
4
5 **1)HMI Settings**
6
7 |**Item**|**Settings**|**Note**
8 |Protocol|Panasonic FP MEWTOCOL|
9 |Connection|RS232|
10 |Baud rate|9600|
11 |Data bit|8|
12 |Parity|ODD|
13 |Stop bit|1|
14 |PLC station No.|1|
15
16 **2)Address List**
17
18 |**Type**|(% style="width:332px" %)**Device registers**|(% style="width:283px" %)**Format**|(% style="width:314px" %)**Range**|**Note**
19 |Bit|(% style="width:332px" %)X|(% style="width:283px" %)X d|(% style="width:314px" %)0~~9999|
20 |Bit|(% style="width:332px" %)Y|(% style="width:283px" %)Y d|(% style="width:314px" %)0~~9999|
21 |Bit|(% style="width:332px" %)R|(% style="width:283px" %)R d|(% style="width:314px" %)0~~9999|
22 |Bit|(% style="width:332px" %)T|(% style="width:283px" %)T d|(% style="width:314px" %)0~~9999|
23 |Bit|(% style="width:332px" %)C|(% style="width:283px" %)C d|(% style="width:314px" %)0~~9999|
24 |Bit|(% style="width:332px" %)L|(% style="width:283px" %)L d|(% style="width:314px" %)0~~9999|
25 |Word|(% style="width:332px" %)WX|(% style="width:283px" %)WX d|(% style="width:314px" %)0~~9999|
26 |Word|(% style="width:332px" %)WY|(% style="width:283px" %)WY d|(% style="width:314px" %)0~~9999|
27 |Word|(% style="width:332px" %)WR|(% style="width:283px" %)WR d|(% style="width:314px" %)0~~9999|
28 |Word|(% style="width:332px" %)WL|(% style="width:283px" %)WL d|(% style="width:314px" %)0~~9999|
29 |Word|(% style="width:332px" %)LD|(% style="width:283px" %)LD d|(% style="width:314px" %)0~~9999|
30 |Word|(% style="width:332px" %)DT|(% style="width:283px" %)DT d|(% style="width:314px" %)0~~65535|
31 |Word|(% style="width:332px" %)FL|(% style="width:283px" %)FL d|(% style="width:314px" %)0~~9999|
32 |Word|(% style="width:332px" %)EV|(% style="width:283px" %)EV d|(% style="width:314px" %)0~~9999|
33 |Word|(% style="width:332px" %)SV|(% style="width:283px" %)SV d|(% style="width:314px" %)0~~9999|
34
35 **3)Configure the communication protocol**
36
37 {{id name="Iimage-20220830171050-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_61c95ff9892a9bf0.png||alt="image-20220830171050-1.png" height="735" width="616"]]
38
39 {{id name="Iimage-20220830171126-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dd56d3061f9486e6.png||alt="image-20220830171126-2.png" height="905" width="1038"]]
40
41 **5)PLC Setting:**
42
43 ①PLC Default Parameters:
44 1.[Option]→[System register settings]→[COM0 Port]→[Unit No.]1→[Communication Mode]Computer Link → [Baud Rate]9600bps → [Communication Format]char.bit:8bits;Parity:Odd;Stop Bit:1→[OK].
45
46 (% style="text-align:center" %)
47 [[image:1.3.png]]
48
49 ②[Online]→[Communication Settings]→[Port to use]COM(USB)→[Port to use (No.)]PIDSX PLC USB-COM(COM12)→[Communications condition settings] Communications speed:9600bps;Data
50 length:8bits;Stop bits:1bit;Parity:Odd;Timeout (sec):5→[Automatic search items in communications conditions]:check the option[Communications speed],[ Data length],[ Parity]→[OK]
51 Please select according to the actual connection between PC and PLC.
52
53 (% style="text-align:center" %)
54 [[image:1.5.png]]
55
56 **5)Cable Wiring**
57
58 Figure
59
60 {{id name="Iimage-20220830171328-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ce9891ae062a7b5c.png||alt="image-20220830171328-4.png" height="201" width="664"]]
61
62 Pin Definition Diagram
63
64 {{id name="Iimage-20220830171146-3.png"/}}
65
66 (% style="text-align:center" %)
67 [[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e97b603d4f88a93a.png||alt="image-20220830171146-3.png" height="231" width="377"]]
68
69 (% style="text-align:center" %)
70 [[image:Picture2.jpg||height="231" width="446"]]
71
72 == (% id="cke_bm_580S" style="display:none" %) {{id name="HFPMEWTOCOL"/}}(%%)**FP Series Ethernet** ==
73
74 **HMI Settings**
75
76
77 |**Item**|**Settings**|**Note**
78 |Protocol|Panasonic FP MEWTOCOL(Ethernet)|
79 |Connection|Ethernet|
80 |Port No.|32769|
81 |Network|TCP_Client_2N|
82 |PLC station No.|1|
83
84 **Address List**
85
86 |**Type**|**Device registers**|**Format**|**Range**|**Note**
87 |Bit|X|X d|0~~9999|
88 |Bit|Y|Y d|0~~9999|
89 |Bit|R|R d|0~~9999|
90 |Bit|T|T d|0~~9999|
91 |Bit|C|C d|0~~9999|
92 |Bit|L|L d|0~~9999|
93 |Word|WX|WX d|0~~9999|
94 |Word|WY|WY d|0~~9999|
95 |Word|WR|WR d|0~~9999|
96 |Word|WL|WL d|0~~9999|
97 |Word|LD|LD d|0~~9999|
98 |Word|DT|DT d|0~~65535|
99 |Word|FL|FL d|0~~9999|
100 |Word|EV|EV d|0~~9999|
101 |Word|SV|SV d|0~~9999|
102
103 **Configure the communication protocol**
104
105 (% style="text-align:center" %)
106 [[image:Picture1.png]]
107
108 (% style="text-align:center" %)
109 [[image:Picture2.png]]
110
111 **PLC Setting:**
112
113 1.[Option]→[Ethernet settings]→[Basic communications information]→[IPv4 address autonatic acquisition]No → [Home IP address]192.168.40.11 → [Subnet mask]255.255.255.0 → [Default gateway]192.168.40.1
114
115 (% style="text-align:center" %)
116 [[image:1.3.1.png]]
117
118 2.[ System connecton settings] →[Home port nunber]32769→[OK].
119
120 (% style="text-align:center" %)
121 [[image:1.3.2.png]]
122
123 Note: Please configure the IP parameters of PLC according to the field needs
124
125 **Cable Wiring**
126
127 (% style="text-align:center" %)
128 [[image:WeCom Screenshot_20230926104300.png]]
129
130 Pin Definition Diagram