Changes for page Rockwell

Last modified by Molly on 2024/11/04 18:13

From version 1.1
edited by Hunter
on 2023/08/24 18:12
Change comment: Changed document syntax from [XWiki 2.1] to [xwiki/2.1].
To version 17.1
edited by Molly
on 2024/09/21 16:29
Change comment: There is no comment for this version

Summary

Details

Page properties
Title
... ... @@ -1,0 +1,1 @@
1 +Rockwell
Parent
... ... @@ -1,0 +1,1 @@
1 +PIStudio.PLC Protocol.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.Hunter
1 +XWiki.Molly
Content
... ... @@ -1,0 +1,397 @@
1 += {{id name="HRockwell"/}}**Rockwell** =
2 +
3 +== {{id name="HDF1"/}}**DF1** ==
4 +
5 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
6 +
7 +**HMI Settings**
8 +
9 +|=Item|=Recommended |=Note
10 +|=Protocol|Rockwell DF1|
11 +|=Connection|RS232|
12 +|=Baud rate|19200|
13 +|=Stop bits|1|
14 +|=Data bits|8|
15 +|=Parity|None|
16 +|=PLC Station No.|1|
17 +|=HMI Station No.|0|
18 +
19 +**PLC Settings**
20 +
21 +DF1 Full Duplex protocol and CRC error check
22 +
23 +**Address List**
24 +
25 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
26 +|(% rowspan="5" %)Bit|I|I ddd.dd|0.0~~255.15|Only able to communicate with file number I1
27 +|O|O ddd.dd|0.0~~255.15|Only able to communicate with file number O0
28 +|B|B nnhh.dd|0.0~~ffff.15|Only able to communicate with file number B3
29 +|S|S ddd.dd|0.0~~255.15|Only able to communicate with file number S2
30 +|N|N nnhh.dd|0.0~~ffff.15|Only able to communicate with file number N7
31 +|(% rowspan="6" %)Word|S|S ddd|0~~255|Only able to communicate with file number S2
32 +|TS|TS nnhh|0~~ffff|Only able to communicate with file number T4 (Timer Preset Value)
33 +|TP|TP nnhh|0~~ffff|Only able to communicate with file number T4 (Timer Accumulator Value)
34 +|CS|CS nnhh|0~~ffff|Only able to communicate with file number C5 (Counter Preset Value)
35 +|CP|CP nnhh|0~~ffff|Only able to communicate with file number C5 (Counter Accumulator Value)
36 +|N|N nnhh|0~~ffff|Only able to communicate with file number N7
37 +
38 +**Cable Wiring**
39 +
40 +{{id name="IAB.gif"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c884ca361be80135.gif||alt="AB.gif" height="247" width="400"]]
41 +
42 +== {{id name="HDF1Advanced"/}}**DF1 Advanced** ==
43 +
44 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
45 +
46 +**HMI Settings**
47 +
48 +|=Item|=Recommended |=Note
49 +|=Protocol|Rockwell DF1 Advanced|
50 +|=Connection|RS232|
51 +|=Baud rate|19200|
52 +|=Stop bits|1|
53 +|=Data bits|8|
54 +|=Parity|None|
55 +|=PLC Station No.|1|
56 +|=HMI Station No.|0|
57 +
58 +**PLC Settings**
59 +
60 +DF1 Full Duplex protocol and CRC error check
61 +
62 +**Address List**
63 +
64 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
65 +|(% rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
66 +|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
67 +|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
68 +|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
69 +|BN|BNddddd.dd|0.0~~99255.15|(((
70 +Bit data file B0~~B99
71 +
72 +First two digits is for file number
73 +
74 +For example, BN13001.00 represents file number B13, address 001, the 0th bit.
75 +)))
76 +|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
77 +|NN|NNddddd.dd|0.0~~99255.15|(((
78 +Integer data file bit format N0~~N99
79 +
80 +First two digits is for file number
81 +
82 +For example, NN13001.00 represents file number N13, address 001, the 0th bit.
83 +)))
84 +|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
85 +|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
86 +|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
87 +|TNS|TNSddddd|0~~99255|(((
88 +Timer Preset Value
89 +
90 +First two digits is for file number
91 +
92 +For example, TNS99255 represents file number T99, address 255.
93 +)))
94 +|TNP|TNPddddd|0~~99255|(((
95 +Timer Accumulator Value
96 +
97 +First two digits is for file number
98 +
99 +For example, TNP99255 represents file number T99, address 255.
100 +)))
101 +|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
102 +|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
103 +|CNS|CNSddddd|0~~99255|(((
104 +Counter Preset Value
105 +
106 +First two digits is for file number
107 +
108 +For example, CNS99255 represents file number C99, address 255.
109 +)))
110 +|CNP|CNPddddd|0~~99255|(((
111 +Counter Accumulator Value
112 +
113 +First two digits is for file number
114 +
115 +For example, CNP99255 represents file number C99, address 255.
116 +)))
117 +|N7|N7ddd|0~~255|Only able to communicate with file number N7
118 +|NN|NNddd|0~~99255|(((
119 +Integer data file
120 +
121 +First two digits is for file number
122 +
123 +For example, NN99255 represents file number N99, address 255.
124 +)))
125 +|(% rowspan="3" %)Double Word|F8|F8ddd|0~~255|Only able to communicate with file number F8
126 +|FN|FNddddd|0~~99255|(((
127 +Floating point data file
128 +
129 +First two digits is for file number
130 +
131 +For example, FN99255 represents file number F99, address 255.
132 +)))
133 +|LN|LNddddd|0~~99255|Long
134 +
135 +**Cable Wiring**
136 +
137 +{{id name="IAB.gif-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c884ca361be80135.gif||alt="AB.gif" height="247" width="400"]]
138 +
139 +== {{id name="HMicroLogix"/}}**MicroLogix** ==
140 +
141 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
142 +
143 +**HMI Settings**
144 +
145 +|**Item**|**Settings**|**Note**
146 +|Protocol|Allen-Bradlley MicroLogix|
147 +|Connection|RS232|
148 +|Baud rate|19200|
149 +|Data bit|8|
150 +|Parity|None|
151 +|Stop bit|1|
152 +|PLC station No.|1|
153 +
154 +**Address List**
155 +
156 +|**Type**|**Device registers**|**Format**|**Range**|**Note**
157 +|(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
158 +|O|O d.d|0.0~~255.15|
159 +|B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
160 +|S|S d.d|0.0~~255.15|
161 +|N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
162 +|(% rowspan="9" %)Word|S|S d|0~~255|
163 +|TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
164 +|TP|TP nnhh|0~~ffff
165 +|CS|CS nnhh|0~~ffff
166 +|CP|CP nnhh|0~~ffff
167 +|N|N nnhh|0~~ffff
168 +|C|C nnhh|0~~ffff
169 +|T|T nnhh|0~~ffff
170 +|R|R nnhh|0~~ffff
171 +
172 +**Cable Wiring**
173 +
174 +{{id name="I12.PLCProtocol_html_58205bdf82c06d4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_32d8ab10ec374ea6.png||alt="12.PLC Protocol_html_58205bdf82c06d4.png" height="307" width="500"]]
175 +
176 +== {{id name="HEtherNet2FIP28CompactLogixSeries29"/}}**EtherNet/IP(CompactLogix Series)** ==
177 +
178 +Allen-Brandly Compact Logix Free Tag
179 +
180 +**HMI Settings**
181 +
182 +|**Items**|**Settings**|**Note**
183 +|Protocol|EtherNet/IP(CompactLogix Series)|
184 +|Connection|Ethernet|
185 +|Port No.|44818|
186 +
187 +**PLC Setting**
188 +
189 +Create new tags
190 +
191 +{{id name="I12.PLCProtocol_html_a748a27dcf7f1124.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_75d3f4097ac67d8e.png||alt="12.PLC Protocol_html_a748a27dcf7f1124.png" height="411" width="700"]]
192 +
193 +Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
194 +
195 +{{id name="I12.PLCProtocol_html_151379170bb8ff3e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_39bb299de26a0af0.png||alt="12.PLC Protocol_html_151379170bb8ff3e.png" height="352" width="700"]]
196 +
197 +Import labels, please open [Communication] window and click [Import label];
198 +
199 +Select csv file, all tags will be displayed as belows;
200 +
201 +{{id name="I12.PLCProtocol_html_af192e54dee96f38.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4216defdc24cba39.png||alt="12.PLC Protocol_html_af192e54dee96f38.png" height="586" width="700"]]
202 +
203 +**✎Note:**
204 +
205 +Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
206 +
207 +{{id name="I12.PLCProtocol_html_33df1d63ebe53726.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_24f4d658173f88a9.png||alt="12.PLC Protocol_html_33df1d63ebe53726.png" height="206" width="700"]]
208 +
209 +The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
210 +
211 +**Communication settings in HMI**
212 +
213 +Enable HMI Ethernet in [Project Settings];
214 +
215 +{{id name="I12.PLCProtocol_html_43b671f18153910d.png-5"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="106" width="400"]]
216 +
217 +Set PLC IP in [Device IP] settings;
218 +
219 +{{id name="I12.PLCProtocol_html_27870d373581892e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_10385ddd81c8baff.png||alt="12.PLC Protocol_html_27870d373581892e.png" height="206" width="600"]]
220 +
221 +**Cable Wiring**
222 +
223 +{{id name="I12.PLCProtocol_html_2297240b57346b2a.png-3"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="400"]]
224 +
225 +== {{id name="HMicroLogix1200"/}}**MicroLogix 1200** ==
226 +
227 +The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
228 +
229 +* **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
230 +* **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
231 +* **Word address S:** The word address ranges from 0 to 255 (decimal).
232 +* **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
233 +
234 +**✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
235 +
236 +|**PLC bit address type**|**Address format**|**Address range**
237 +|I|dd.dd|I 0.0 ~~ 255.15
238 +|O|dd.dd|O 0.0 ~~ 255.15
239 +|B|fff.dd|B 000.0 ~~ fff.15
240 +|S|dd.dd|S 0.0 ~~ 255.15
241 +|N|ffff.dd|N 000.0 ~~ fff.15
242 +|**PLC word address type**|**Address format**|**Address range**
243 +|S|ddd|S0 ~~ 255
244 +|TS|ffff|TS0 ~~ FFFF
245 +|TP|ffff|TP0 ~~ FFFF
246 +|CS|ffff|CS0 ~~ FFFF
247 +|CP|ffff|CP0 ~~ FFFF
248 +|N|ffff|N0 ~~ FFFF
249 +|F|ffff|F0 ~~ FFFF
250 +
251 +== **Ethernet/IP DF1** ==
252 +
253 +Supported Series: Rockwell MicroLogix 1100, 1400, SLC5/05 Ethernet port. MicroLogix1000,1200,1500,SLC 5/03, 5/04 with 1761-NET-ENI
254 +
255 +|**Items**|**Settings**|**Note**
256 +|Protocol|Rockwell Ethernet/IP DF1|
257 +|Connection|Ethernet|
258 +|Port No.|44818|
259 +|PLC station No.|1|
260 +
261 +**Address List**
262 +
263 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
264 +|(% rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
265 +|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
266 +|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
267 +|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
268 +|BN|BNddddd.dd|0.0~~99255.15|(((
269 +Bit data file B0~~B99
270 +
271 +First two digits is for file number
272 +
273 +For example, BN13001.00 represents file number B13, address 001, the 0th bit.
274 +)))
275 +|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
276 +|NN|NNddddd.dd|0.0~~99255.15|(((
277 +Integer data file bit format N0~~N99
278 +
279 +First two digits is for file number
280 +
281 +For example, NN13001.00 represents file number N13, address 001, the 0th bit.
282 +)))
283 +|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
284 +|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
285 +|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
286 +|TNS|TNSddddd|0~~99255|(((
287 +Timer Preset Value
288 +
289 +First two digits is for file number
290 +
291 +For example, TNS99255 represents file number T99, address 255.
292 +)))
293 +|TNP|TNPddddd|0~~99255|(((
294 +Timer Accumulator Value
295 +
296 +First two digits is for file number
297 +
298 +For example, TNP99255 represents file number T99, address 255.
299 +)))
300 +|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
301 +|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
302 +|CNS|CNSddddd|0~~99255|(((
303 +Counter Preset Value
304 +
305 +First two digits is for file number
306 +
307 +For example, CNS99255 represents file number C99, address 255.
308 +)))
309 +|CNP|CNPddddd|0~~99255|(((
310 +Counter Accumulator Value
311 +
312 +First two digits is for file number
313 +
314 +For example, CNP99255 represents file number C99, address 255.
315 +)))
316 +|N7|N7ddd|0~~255|Only able to communicate with file number N7
317 +|NN|NNddd|0~~99255|(((
318 +Integer data file
319 +
320 +First two digits is for file number
321 +
322 +For example, NN99255 represents file number N99, address 255.
323 +)))
324 +|(% rowspan="3" %)Double Word|F8|F8ddd|0~~255|Only able to communicate with file number F8
325 +|FN|FNddddd|0~~99255|(((
326 +Floating point data file
327 +
328 +First two digits is for file number
329 +
330 +For example, FN99255 represents file number F99, address 255.
331 +)))
332 +|LN|LNddddd|0~~99255|Long
333 +
334 +**PLC Setting:**
335 +
336 +1.Open the RSLinx Classic Lite software and click [Configure Drivers...] in [Communications].[[image:1.png]]
337 +
338 +2.Click the drop-down menu and select EtherNet/IP driver[[image:2.png]]
339 +
340 +3.Click Add New and a pop-up window will pop up. Name the driver and click [OK] in the pop-up window.[[image:3.png]]
341 +
342 +4.The configuration driver window pops up., click on the correct network adapter option (such as the ASIX USB to Fast Ethernet Family Adapter option in this picture), and click OK
343 +
344 +[[image:4.png]]
345 +
346 +5.Click the [Close] button.[[image:5.png]]
347 +
348 +6.Click the [RSWho] button.[[image:6.png]]
349 +
350 +7.Pop up the RS Who window, indicating that the driver has been added successfully.[[image:7.png]]
351 +
352 +8.Open the RSLogix 500Pro software and select [System Comms...] in the [Comms] option.[[image:8.jpg]]
353 +
354 +9.Select the driver you have created. All device nodes in the same LAN as the computer will be scanned. Select the PLC to be connected and click [OK].
355 +
356 +[[image:9.png]]
357 +
358 +10.Click Comms [Go Online].[[image:10.png]]
359 +
360 +11.Click [YES] in the pop-up window.[[image:11.png]]
361 +
362 +12.Enter online mode.[[image:14.jpg]]
363 +
364 +**Cable Wiring**
365 +
366 +(% style="text-align:center" %)
367 +[[image:Ethernet.png]]
368 +
369 +
370 += Rockwell EtherNet/IP(CompactLogix Series) =
371 +
372 +Supported Series: Rockwell CompactLogix Series Ethernet
373 +
374 +|**Items**|**Settings**|**Note**
375 +|Protocol|Rockwell EtherNet/IP (CompactLogix Series)|
376 +|Connection|Ethernet|
377 +|Port No.|44818|
378 +|PLC station No.|1|
379 +
380 +**Support Variable Type**
381 +
382 +|PLC data type|Bit/Word|PIStudio data format|Memo
383 +|BOOL|Boolean|Bit object|
384 +|BitArray| | |
385 +|SINT| | |-128-127
386 +|USINT| | |0~~255
387 +|INT|Integer|16-bit signed, ASCll|-32768~~32767
388 +|UINT| | |0~~65535
389 +|DINT|Double integer|32-bit signed|-2^31~~(2^31-1)
390 +|UDINT| | |0~~4294967295
391 +|REAL|Single Precision Float|32-bit floating|
392 +|LINT|Long integer|64-bit signed|
393 +|ULINT|Long integer|64-bit unsigned|
394 +|LREAL|Double Precision Float|64-bit double|
395 +|STRING| | |Enable Read DWord
396 +
397 +
1.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +22.0 KB
Content
10.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +112.1 KB
Content
11.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +68.6 KB
Content
14.jpg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +70.0 KB
Content
2.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +32.2 KB
Content
3.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +39.2 KB
Content
4.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +36.5 KB
Content
5.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +25.0 KB
Content
6.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +18.0 KB
Content
7.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +24.7 KB
Content
8.jpg
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +116.6 KB
Content
9.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +74.5 KB
Content
Ethernet.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Molly
Size
... ... @@ -1,0 +1,1 @@
1 +107.1 KB
Content
xwiki_PIStudio_12.PLC+protocols_WebHome_10385ddd81c8baff.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +17.5 KB
Content
xwiki_PIStudio_12.PLC+protocols_WebHome_24f4d658173f88a9.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +27.6 KB
Content
xwiki_PIStudio_12.PLC+protocols_WebHome_32d8ab10ec374ea6.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +37.7 KB
Content
xwiki_PIStudio_12.PLC+protocols_WebHome_39bb299de26a0af0.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +158.4 KB
Content
xwiki_PIStudio_12.PLC+protocols_WebHome_4216defdc24cba39.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +28.5 KB
Content
xwiki_PIStudio_12.PLC+protocols_WebHome_75d3f4097ac67d8e.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +195.6 KB
Content
xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +3.1 KB
Content
xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +107.1 KB
Content
xwiki_PIStudio_12.PLC+protocols_WebHome_c884ca361be80135.gif
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.Hunter
Size
... ... @@ -1,0 +1,1 @@
1 +8.0 KB
Content
XWiki.XWikiComments[0]
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.VZ
Comment
... ... @@ -1,0 +1,2 @@
1 +I have a 3070ig-O-RS v1.7 HMI panel.
2 +I tried it with an Allen-Bradley Micro820 2080-LC20-20QWB V12 PLC with Ethernet connection, with more different Rockwell protocols (for example Micro850 Ethernet (Free Tags) too). But when I am exporting the PLC TAGs (variables) from Connected Components Workbench (CCW) to a CSV or TXT files, and I am importing these into the PIStudio, an Error message comes in the PIStudio: "Wrong File Format". (???) Please, if anyone can help!
Date
... ... @@ -1,0 +1,1 @@
1 +2024-08-26 18:34:39.437
XWiki.XWikiComments[1]
Author
... ... @@ -1,0 +1,1 @@
1 +XWiki.VZ
Comment
... ... @@ -1,0 +1,4 @@
1 +I imported already successfully the Allen-Bradley Micro PLC's Tags CSV file into the PIStudio 3070ig project (I edited it manually). But on the 3070ig-O-RS V1.7 HMI comes the next message:
2 +"This model does not support Free Tags!" ???
3 +What could be the problem? This 3070ig type HMI doesn't support this? Maybe I should update the firmware?
4 +Please, if anyone can help!
Date
... ... @@ -1,0 +1,1 @@
1 +2024-09-06 21:58:06.713