1 += {{id name="HRockwell"/}}**Rockwell** =
2 +
3 +== {{id name="HDF1"/}}**DF1** ==
4 +
5 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
6 +
7 +**HMI Settings**
8 +
9 +|=Item|=Recommended |=Note
10 +|=Protocol|Rockwell DF1|
11 +|=Connection|RS232|
12 +|=Baud rate|19200|
13 +|=Stop bits|1|
14 +|=Data bits|8|
15 +|=Parity|None|
16 +|=PLC Station No.|1|
17 +|=HMI Station No.|0|
18 +
19 +**PLC Settings**
20 +
21 +DF1 Full Duplex protocol and CRC error check
22 +
23 +**Address List**
24 +
25 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
26 +|(% rowspan="5" %)Bit|I|I ddd.dd|0.0~~255.15|Only able to communicate with file number I1
27 +|O|O ddd.dd|0.0~~255.15|Only able to communicate with file number O0
28 +|B|B nnhh.dd|0.0~~ffff.15|Only able to communicate with file number B3
29 +|S|S ddd.dd|0.0~~255.15|Only able to communicate with file number S2
30 +|N|N nnhh.dd|0.0~~ffff.15|Only able to communicate with file number N7
31 +|(% rowspan="6" %)Word|S|S ddd|0~~255|Only able to communicate with file number S2
32 +|TS|TS nnhh|0~~ffff|Only able to communicate with file number T4 (Timer Preset Value)
33 +|TP|TP nnhh|0~~ffff|Only able to communicate with file number T4 (Timer Accumulator Value)
34 +|CS|CS nnhh|0~~ffff|Only able to communicate with file number C5 (Counter Preset Value)
35 +|CP|CP nnhh|0~~ffff|Only able to communicate with file number C5 (Counter Accumulator Value)
36 +|N|N nnhh|0~~ffff|Only able to communicate with file number N7
37 +
38 +**Cable Wiring**
39 +
40 +{{id name="IAB.gif"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c884ca361be80135.gif||alt="AB.gif" height="247" width="400"]]
41 +
42 +== {{id name="HDF1Advanced"/}}**DF1 Advanced** ==
43 +
44 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5
45 +
46 +**HMI Settings**
47 +
48 +|=Item|=Recommended |=Note
49 +|=Protocol|Rockwell DF1 Advanced|
50 +|=Connection|RS232|
51 +|=Baud rate|19200|
52 +|=Stop bits|1|
53 +|=Data bits|8|
54 +|=Parity|None|
55 +|=PLC Station No.|1|
56 +|=HMI Station No.|0|
57 +
58 +**PLC Settings**
59 +
60 +DF1 Full Duplex protocol and CRC error check
61 +
62 +**Address List**
63 +
64 +|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note
65 +|(% rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1
66 +|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0
67 +|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2
68 +|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3
69 +|BN|BNddddd.dd|0.0~~99255.15|(((
70 +Bit data file B0~~B99
71 +
72 +First two digits is for file number
73 +
74 +For example, BN13001.00 represents file number B13, address 001, the 0th bit.
75 +)))
76 +|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7
77 +|NN|NNddddd.dd|0.0~~99255.15|(((
78 +Integer data file bit format N0~~N99
79 +
80 +First two digits is for file number
81 +
82 +For example, NN13001.00 represents file number N13, address 001, the 0th bit.
83 +)))
84 +|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2
85 +|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value)
86 +|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value)
87 +|TNS|TNSddddd|0~~99255|(((
88 +Timer Preset Value
89 +
90 +First two digits is for file number
91 +
92 +For example, TNS99255 represents file number T99, address 255.
93 +)))
94 +|TNP|TNPddddd|0~~99255|(((
95 +Timer Accumulator Value
96 +
97 +First two digits is for file number
98 +
99 +For example, TNP99255 represents file number T99, address 255.
100 +)))
101 +|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value)
102 +|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value)
103 +|CNS|CNSddddd|0~~99255|(((
104 +Counter Preset Value
105 +
106 +First two digits is for file number
107 +
108 +For example, CNS99255 represents file number C99, address 255.
109 +)))
110 +|CNP|CNPddddd|0~~99255|(((
111 +Counter Accumulator Value
112 +
113 +First two digits is for file number
114 +
115 +For example, CNP99255 represents file number C99, address 255.
116 +)))
117 +|N7|N7ddd|0~~255|Only able to communicate with file number N7
118 +|NN|NNddd|0~~99255|(((
119 +Integer data file
120 +
121 +First two digits is for file number
122 +
123 +For example, NN99255 represents file number N99, address 255.
124 +)))
125 +|(% rowspan="3" %)Double Word|F8|F8ddd|0~~255|Only able to communicate with file number F8
126 +|FN|FNddddd|0~~99255|(((
127 +Floating point data file
128 +
129 +First two digits is for file number
130 +
131 +For example, FN99255 represents file number F99, address 255.
132 +)))
133 +|LN|LNddddd|0~~99255|Long
134 +
135 +**Cable Wiring**
136 +
137 +{{id name="IAB.gif-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c884ca361be80135.gif||alt="AB.gif" height="247" width="400"]]
138 +
139 +== {{id name="HMicroLogix"/}}**MicroLogix** ==
140 +
141 +MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5
142 +
143 +**HMI Settings**
144 +
145 +|**Item**|**Settings**|**Note**
146 +|Protocol|Allen-Bradlley MicroLogix|
147 +|Connection|RS232|
148 +|Baud rate|19200|
149 +|Data bit|8|
150 +|Parity|None|
151 +|Stop bit|1|
152 +|PLC station No.|1|
153 +
154 +**Address List**
155 +
156 +|**Type**|**Device registers**|**Format**|**Range**|**Note**
157 +|(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15|
158 +|O|O d.d|0.0~~255.15|
159 +|B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex)
160 +|S|S d.d|0.0~~255.15|
161 +|N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex)
162 +|(% rowspan="9" %)Word|S|S d|0~~255|
163 +|TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex)
164 +|TP|TP nnhh|0~~ffff
165 +|CS|CS nnhh|0~~ffff
166 +|CP|CP nnhh|0~~ffff
167 +|N|N nnhh|0~~ffff
168 +|C|C nnhh|0~~ffff
169 +|T|T nnhh|0~~ffff
170 +|R|R nnhh|0~~ffff
171 +
172 +**Cable Wiring**
173 +
174 +{{id name="I12.PLCProtocol_html_58205bdf82c06d4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_32d8ab10ec374ea6.png||alt="12.PLC Protocol_html_58205bdf82c06d4.png" height="307" width="500"]]
175 +
176 +== {{id name="HEtherNet2FIP28CompactLogixSeries29"/}}**EtherNet/IP(CompactLogix Series)** ==
177 +
178 +Allen-Brandly Compact Logix Free Tag
179 +
180 +**HMI Settings**
181 +
182 +|**Items**|**Settings**|**Note**
183 +|Protocol|EtherNet/IP(CompactLogix Series)|
184 +|Connection|Ethernet|
185 +|Port No.|44818|
186 +
187 +**PLC Setting**
188 +
189 +Create new tags
190 +
191 +{{id name="I12.PLCProtocol_html_a748a27dcf7f1124.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_75d3f4097ac67d8e.png||alt="12.PLC Protocol_html_a748a27dcf7f1124.png" height="411" width="700"]]
192 +
193 +Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments])
194 +
195 +{{id name="I12.PLCProtocol_html_151379170bb8ff3e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_39bb299de26a0af0.png||alt="12.PLC Protocol_html_151379170bb8ff3e.png" height="352" width="700"]]
196 +
197 +Import labels, please open [Communication] window and click [Import label];
198 +
199 +Select csv file, all tags will be displayed as belows;
200 +
201 +{{id name="I12.PLCProtocol_html_af192e54dee96f38.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4216defdc24cba39.png||alt="12.PLC Protocol_html_af192e54dee96f38.png" height="586" width="700"]]
202 +
203 +**✎Note:**
204 +
205 +Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format.
206 +
207 +{{id name="I12.PLCProtocol_html_33df1d63ebe53726.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_24f4d658173f88a9.png||alt="12.PLC Protocol_html_33df1d63ebe53726.png" height="206" width="700"]]
208 +
209 +The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting.
210 +
211 +**Communication settings in HMI**
212 +
213 +Enable HMI Ethernet in [Project Settings];
214 +
215 +{{id name="I12.PLCProtocol_html_43b671f18153910d.png-5"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="106" width="400"]]
216 +
217 +Set PLC IP in [Device IP] settings;
218 +
219 +{{id name="I12.PLCProtocol_html_27870d373581892e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_10385ddd81c8baff.png||alt="12.PLC Protocol_html_27870d373581892e.png" height="206" width="600"]]
220 +
221 +**Cable Wiring**
222 +
223 +{{id name="I12.PLCProtocol_html_2297240b57346b2a.png-3"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="400"]]
224 +
225 +== {{id name="HMicroLogix1200"/}}**MicroLogix 1200** ==
226 +
227 +The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200.
228 +
229 +* **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal).
230 +* **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal).
231 +* **Word address S:** The word address ranges from 0 to 255 (decimal).
232 +* **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal).
233 +
234 +**✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table.
235 +
236 +|**PLC bit address type**|**Address format**|**Address range**
237 +|I|dd.dd|I 0.0 ~~ 255.15
238 +|O|dd.dd|O 0.0 ~~ 255.15
239 +|B|fff.dd|B 000.0 ~~ fff.15
240 +|S|dd.dd|S 0.0 ~~ 255.15
241 +|N|ffff.dd|N 000.0 ~~ fff.15
242 +|**PLC word address type**|**Address format**|**Address range**
243 +|S|ddd|S0 ~~ 255
244 +|TS|ffff|TS0 ~~ FFFF
245 +|TP|ffff|TP0 ~~ FFFF
246 +|CS|ffff|CS0 ~~ FFFF
247 +|CP|ffff|CP0 ~~ FFFF
248 +|N|ffff|N0 ~~ FFFF
249 +|F|ffff|F0 ~~ FFFF