+Supported Series: Rockwell MicroLogix 1100, 1400, SLC5/05 Ethernet port. MicroLogix1000,1200,1500,SLC 5/03, 5/04 with 1761-NET-ENI |
|
254 |
+ |
|
255 |
+|**Items**|**Settings**|**Note** |
|
256 |
+|Protocol|Rock well Ethernet/IP DF1| |
|
257 |
+|Connection|Ethernet| |
|
258 |
+|Port No.|44818| |
|
259 |
+|PLC station No.|1| |
|
260 |
+ |
|
261 |
+**Address List** |
|
262 |
+ |
|
263 |
+|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note |
|
264 |
+|(% rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1 |
|
265 |
+|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0 |
|
266 |
+|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2 |
|
267 |
+|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3 |
|
268 |
+|BN|BNddddd.dd|0.0~~99255.15|((( |
|
269 |
+Bit data file B0~~B99 |
|
270 |
+ |
|
271 |
+First two digits is for file number |
|
272 |
+ |
|
273 |
+For example, BN13001.00 represents file number B13, address 001, the 0th bit. |
|
274 |
+))) |
|
275 |
+|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7 |
|
276 |
+|NN|NNddddd.dd|0.0~~99255.15|((( |
|
277 |
+Integer data file bit format N0~~N99 |
|
278 |
+ |
|
279 |
+First two digits is for file number |
|
280 |
+ |
|
281 |
+For example, NN13001.00 represents file number N13, address 001, the 0th bit. |
|
282 |
+))) |
|
283 |
+|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2 |
|
284 |
+|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value) |
|
285 |
+|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value) |
|
286 |
+|TNS|TNSddddd|0~~99255|((( |
|
287 |
+Timer Preset Value |
|
288 |
+ |
|
289 |
+First two digits is for file number |
|
290 |
+ |
|
291 |
+For example, TNS99255 represents file number T99, address 255. |
|
292 |
+))) |
|
293 |
+|TNP|TNPddddd|0~~99255|((( |
|
294 |
+Timer Accumulator Value |
|
295 |
+ |
|
296 |
+First two digits is for file number |
|
297 |
+ |
|
298 |
+For example, TNP99255 represents file number T99, address 255. |
|
299 |
+))) |
|
300 |
+|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value) |
|
301 |
+|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value) |
|
302 |
+|CNS|CNSddddd|0~~99255|((( |
|
303 |
+Counter Preset Value |
|
304 |
+ |
|
305 |
+First two digits is for file number |
|
306 |
+ |
|
307 |
+For example, CNS99255 represents file number C99, address 255. |
|
308 |
+))) |
|
309 |
+|CNP|CNPddddd|0~~99255|((( |
|
310 |
+Counter Accumulator Value |
|
311 |
+ |
|
312 |
+First two digits is for file number |
|
313 |
+ |
|
314 |
+For example, CNP99255 represents file number C99, address 255. |
|
315 |
+))) |
|
316 |
+|N7|N7ddd|0~~255|Only able to communicate with file number N7 |
|
317 |
+|NN|NNddd|0~~99255|((( |
|
318 |
+Integer data file |
|
319 |
+ |
|
320 |
+First two digits is for file number |
|
321 |
+ |
|
322 |
+For example, NN99255 represents file number N99, address 255. |
|
323 |
+))) |
|
324 |
+|(% rowspan="3" %)Double Word|F8|F8ddd|0~~255|Only able to communicate with file number F8 |
|
325 |
+|FN|FNddddd|0~~99255|((( |
|
326 |
+Floating point data file |
|
327 |
+ |
|
328 |
+First two digits is for file number |
|
329 |
+ |
|
330 |
+For example, FN99255 represents file number F99, address 255. |
|
331 |
+))) |
|
332 |
+|LN|LNddddd|0~~99255|Long |
|
333 |
+ |
|
334 |
+**Cable Wiring** |
|
335 |
+ |
|
336 |
+[[image:Ethernet.png]] |
|
337 |
+ |
|
338 |
+**PLC Setting:** |
|
339 |
+ |
|
340 |
+1.Open the RSLinx Classic Lite software and click [Configure Drivers...] in [Communications].[[image:1.png]] |
|
341 |
+ |
|
342 |
+2.Click the drop-down menu and select EtherNet/IP driver[[image:2.png]] |
|
343 |
+ |
|
344 |
+3.Click Add New and a pop-up window will pop up. Name the driver and click [OK] in the pop-up window.[[image:3.png]] |
|
345 |
+ |
|
346 |
+4.The configuration driver window pops up., click on the correct network adapter option (such as the ASIX USB to Fast Ethernet Family Adapter option in this picture), and click OK[[image:4.png]] |
|
347 |
+ |
|
348 |
+5.Click the [Close] button.[[image:5.png]] |
|
349 |
+ |
|
350 |
+6.Click the [RSWho] button.[[image:6.png]] |
|
351 |
+ |
|
352 |
+7.Pop up the RS Who window, indicating that the driver has been added successfully.[[image:7.png]] |
|
353 |
+ |
|
354 |
+8.Open the RSLogix 500Pro software and select [System Comms...] in the [Comms option].[[image:8.jpg]] |
|
355 |
+ |
|
356 |
+9.Select the driver you have created. All device nodes in the same LAN as the computer will be scanned. Select the PLC to be connected and click [OK]. |
|
357 |
+ |
|
358 |
+[[image:9.png]] |
|
359 |
+ |
|
360 |
+10.Click Comms [Go Online].[[image:10.png]] |
|
361 |
+ |
|
362 |
+11.Click [YES] in the pop-up window.[[image:11.png]] |
|
363 |
+ |
|
364 |
+12.Enter online mode.[[image:14.jpg]] |