@@ -250,148 +250,4 @@ |
250 |
250 |
|
251 |
251 |
== **Ethernet/IP DF1** == |
252 |
252 |
|
253 |
|
-Supported Series: Rockwell MicroLogix 1100, 1400, SLC5/05 Ethernet port. MicroLogix1000,1200,1500,SLC 5/03, 5/04 with 1761-NET-ENI |
254 |
|
- |
255 |
|
-|**Items**|**Settings**|**Note** |
256 |
|
-|Protocol|Rockwell Ethernet/IP DF1| |
257 |
|
-|Connection|Ethernet| |
258 |
|
-|Port No.|44818| |
259 |
|
-|PLC station No.|1| |
260 |
|
- |
261 |
|
-**Address List** |
262 |
|
- |
263 |
|
-|=**Type**|=**Device registers**|=**Format**|=**Range**|=Note |
264 |
|
-|(% rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1 |
265 |
|
-|O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0 |
266 |
|
-|S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2 |
267 |
|
-|B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3 |
268 |
|
-|BN|BNddddd.dd|0.0~~99255.15|((( |
269 |
|
-Bit data file B0~~B99 |
270 |
|
- |
271 |
|
-First two digits is for file number |
272 |
|
- |
273 |
|
-For example, BN13001.00 represents file number B13, address 001, the 0th bit. |
274 |
|
-))) |
275 |
|
-|N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7 |
276 |
|
-|NN|NNddddd.dd|0.0~~99255.15|((( |
277 |
|
-Integer data file bit format N0~~N99 |
278 |
|
- |
279 |
|
-First two digits is for file number |
280 |
|
- |
281 |
|
-For example, NN13001.00 represents file number N13, address 001, the 0th bit. |
282 |
|
-))) |
283 |
|
-|(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2 |
284 |
|
-|T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value) |
285 |
|
-|T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value) |
286 |
|
-|TNS|TNSddddd|0~~99255|((( |
287 |
|
-Timer Preset Value |
288 |
|
- |
289 |
|
-First two digits is for file number |
290 |
|
- |
291 |
|
-For example, TNS99255 represents file number T99, address 255. |
292 |
|
-))) |
293 |
|
-|TNP|TNPddddd|0~~99255|((( |
294 |
|
-Timer Accumulator Value |
295 |
|
- |
296 |
|
-First two digits is for file number |
297 |
|
- |
298 |
|
-For example, TNP99255 represents file number T99, address 255. |
299 |
|
-))) |
300 |
|
-|C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value) |
301 |
|
-|C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value) |
302 |
|
-|CNS|CNSddddd|0~~99255|((( |
303 |
|
-Counter Preset Value |
304 |
|
- |
305 |
|
-First two digits is for file number |
306 |
|
- |
307 |
|
-For example, CNS99255 represents file number C99, address 255. |
308 |
|
-))) |
309 |
|
-|CNP|CNPddddd|0~~99255|((( |
310 |
|
-Counter Accumulator Value |
311 |
|
- |
312 |
|
-First two digits is for file number |
313 |
|
- |
314 |
|
-For example, CNP99255 represents file number C99, address 255. |
315 |
|
-))) |
316 |
|
-|N7|N7ddd|0~~255|Only able to communicate with file number N7 |
317 |
|
-|NN|NNddd|0~~99255|((( |
318 |
|
-Integer data file |
319 |
|
- |
320 |
|
-First two digits is for file number |
321 |
|
- |
322 |
|
-For example, NN99255 represents file number N99, address 255. |
323 |
|
-))) |
324 |
|
-|(% rowspan="3" %)Double Word|F8|F8ddd|0~~255|Only able to communicate with file number F8 |
325 |
|
-|FN|FNddddd|0~~99255|((( |
326 |
|
-Floating point data file |
327 |
|
- |
328 |
|
-First two digits is for file number |
329 |
|
- |
330 |
|
-For example, FN99255 represents file number F99, address 255. |
331 |
|
-))) |
332 |
|
-|LN|LNddddd|0~~99255|Long |
333 |
|
- |
334 |
|
-**PLC Setting:** |
335 |
|
- |
336 |
|
-1.Open the RSLinx Classic Lite software and click [Configure Drivers...] in [Communications].[[image:1.png]] |
337 |
|
- |
338 |
|
-2.Click the drop-down menu and select EtherNet/IP driver[[image:2.png]] |
339 |
|
- |
340 |
|
-3.Click Add New and a pop-up window will pop up. Name the driver and click [OK] in the pop-up window.[[image:3.png]] |
341 |
|
- |
342 |
|
-4.The configuration driver window pops up., click on the correct network adapter option (such as the ASIX USB to Fast Ethernet Family Adapter option in this picture), and click OK |
343 |
|
- |
344 |
|
-[[image:4.png]] |
345 |
|
- |
346 |
|
-5.Click the [Close] button.[[image:5.png]] |
347 |
|
- |
348 |
|
-6.Click the [RSWho] button.[[image:6.png]] |
349 |
|
- |
350 |
|
-7.Pop up the RS Who window, indicating that the driver has been added successfully.[[image:7.png]] |
351 |
|
- |
352 |
|
-8.Open the RSLogix 500Pro software and select [System Comms...] in the [Comms] option.[[image:8.jpg]] |
353 |
|
- |
354 |
|
-9.Select the driver you have created. All device nodes in the same LAN as the computer will be scanned. Select the PLC to be connected and click [OK]. |
355 |
|
- |
356 |
|
-[[image:9.png]] |
357 |
|
- |
358 |
|
-10.Click Comms [Go Online].[[image:10.png]] |
359 |
|
- |
360 |
|
-11.Click [YES] in the pop-up window.[[image:11.png]] |
361 |
|
- |
362 |
|
-12.Enter online mode.[[image:14.jpg]] |
363 |
|
- |
364 |
|
-**Cable Wiring** |
365 |
|
- |
366 |
|
-(% style="text-align:center" %) |
367 |
|
-[[image:Ethernet.png]] |
368 |
|
- |
369 |
|
- |
370 |
|
-= Rockwell EtherNet/IP(CompactLogix Series) = |
371 |
|
- |
372 |
|
-Supported Series: Rockwell CompactLogix Series Ethernet |
373 |
|
- |
374 |
|
-|**Items**|**Settings**|**Note** |
375 |
|
-|Protocol|Rockwell EtherNet/IP (CompactLogix Series)| |
376 |
|
-|Connection|Ethernet| |
377 |
|
-|Port No.|44818| |
378 |
|
-|PLC station No.|1| |
379 |
|
- |
380 |
|
-**Support Variable Type** |
381 |
|
- |
382 |
|
-|PLC data type|Bit/Word|PIStudio data format|Memo |
383 |
|
-|BOOL|Boolean|Bit object| |
384 |
|
-|BitArray| | | |
385 |
|
-|SINT| | |-128-127 |
386 |
|
-|USINT| | |0~~255 |
387 |
|
-|INT|Integer|16-bit signed, ASCll|-32768~~32767 |
388 |
|
-|UINT| | |0~~65535 |
389 |
|
-|DINT|Double integer|32-bit signed|-2^31~~(2^31-1) |
390 |
|
-|UDINT| | |0~~4294967295 |
391 |
|
-|REAL|Single Precision Float|32-bit floating| |
392 |
|
-|LINT|Long integer|64-bit signed| |
393 |
|
-|ULINT|Long integer|64-bit unsigned| |
394 |
|
-|LREAL|Double Precision Float|64-bit double| |
395 |
|
-|STRING| | |Enable Read DWord |
396 |
|
- |
397 |
397 |
|