1 | = {{id name="HRockwell"/}}**Rockwell** = | ||
2 | |||
3 | == {{id name="HDF1"/}}**DF1** == | ||
4 | |||
5 | MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5 | ||
6 | |||
7 | **HMI Settings** | ||
8 | |||
9 | |=Item|=Recommended |=Note | ||
10 | |=Protocol|Rockwell DF1| | ||
11 | |=Connection|RS232| | ||
12 | |=Baud rate|19200| | ||
13 | |=Stop bits|1| | ||
14 | |=Data bits|8| | ||
15 | |=Parity|None| | ||
16 | |=PLC Station No.|1| | ||
17 | |=HMI Station No.|0| | ||
18 | |||
19 | **PLC Settings** | ||
20 | |||
21 | DF1 Full Duplex protocol and CRC error check | ||
22 | |||
23 | **Address List** | ||
24 | |||
25 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note | ||
26 | |(% rowspan="5" %)Bit|I|I ddd.dd|0.0~~255.15|Only able to communicate with file number I1 | ||
27 | |O|O ddd.dd|0.0~~255.15|Only able to communicate with file number O0 | ||
28 | |B|B nnhh.dd|0.0~~ffff.15|Only able to communicate with file number B3 | ||
29 | |S|S ddd.dd|0.0~~255.15|Only able to communicate with file number S2 | ||
30 | |N|N nnhh.dd|0.0~~ffff.15|Only able to communicate with file number N7 | ||
31 | |(% rowspan="6" %)Word|S|S ddd|0~~255|Only able to communicate with file number S2 | ||
32 | |TS|TS nnhh|0~~ffff|Only able to communicate with file number T4 (Timer Preset Value) | ||
33 | |TP|TP nnhh|0~~ffff|Only able to communicate with file number T4 (Timer Accumulator Value) | ||
34 | |CS|CS nnhh|0~~ffff|Only able to communicate with file number C5 (Counter Preset Value) | ||
35 | |CP|CP nnhh|0~~ffff|Only able to communicate with file number C5 (Counter Accumulator Value) | ||
36 | |N|N nnhh|0~~ffff|Only able to communicate with file number N7 | ||
37 | |||
38 | **Cable Wiring** | ||
39 | |||
40 | {{id name="IAB.gif"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c884ca361be80135.gif||alt="AB.gif" height="247" width="400"]] | ||
41 | |||
42 | == {{id name="HDF1Advanced"/}}**DF1 Advanced** == | ||
43 | |||
44 | MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05; PLC-5 | ||
45 | |||
46 | **HMI Settings** | ||
47 | |||
48 | |=Item|=Recommended |=Note | ||
49 | |=Protocol|Rockwell DF1 Advanced| | ||
50 | |=Connection|RS232| | ||
51 | |=Baud rate|19200| | ||
52 | |=Stop bits|1| | ||
53 | |=Data bits|8| | ||
54 | |=Parity|None| | ||
55 | |=PLC Station No.|1| | ||
56 | |=HMI Station No.|0| | ||
57 | |||
58 | **PLC Settings** | ||
59 | |||
60 | DF1 Full Duplex protocol and CRC error check | ||
61 | |||
62 | **Address List** | ||
63 | |||
64 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note | ||
65 | |(% rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1 | ||
66 | |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0 | ||
67 | |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2 | ||
68 | |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3 | ||
69 | |BN|BNddddd.dd|0.0~~99255.15|((( | ||
70 | Bit data file B0~~B99 | ||
71 | |||
72 | First two digits is for file number | ||
73 | |||
74 | For example, BN13001.00 represents file number B13, address 001, the 0th bit. | ||
75 | ))) | ||
76 | |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7 | ||
77 | |NN|NNddddd.dd|0.0~~99255.15|((( | ||
78 | Integer data file bit format N0~~N99 | ||
79 | |||
80 | First two digits is for file number | ||
81 | |||
82 | For example, NN13001.00 represents file number N13, address 001, the 0th bit. | ||
83 | ))) | ||
84 | |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2 | ||
85 | |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value) | ||
86 | |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value) | ||
87 | |TNS|TNSddddd|0~~99255|((( | ||
88 | Timer Preset Value | ||
89 | |||
90 | First two digits is for file number | ||
91 | |||
92 | For example, TNS99255 represents file number T99, address 255. | ||
93 | ))) | ||
94 | |TNP|TNPddddd|0~~99255|((( | ||
95 | Timer Accumulator Value | ||
96 | |||
97 | First two digits is for file number | ||
98 | |||
99 | For example, TNP99255 represents file number T99, address 255. | ||
100 | ))) | ||
101 | |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value) | ||
102 | |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value) | ||
103 | |CNS|CNSddddd|0~~99255|((( | ||
104 | Counter Preset Value | ||
105 | |||
106 | First two digits is for file number | ||
107 | |||
108 | For example, CNS99255 represents file number C99, address 255. | ||
109 | ))) | ||
110 | |CNP|CNPddddd|0~~99255|((( | ||
111 | Counter Accumulator Value | ||
112 | |||
113 | First two digits is for file number | ||
114 | |||
115 | For example, CNP99255 represents file number C99, address 255. | ||
116 | ))) | ||
117 | |N7|N7ddd|0~~255|Only able to communicate with file number N7 | ||
118 | |NN|NNddd|0~~99255|((( | ||
119 | Integer data file | ||
120 | |||
121 | First two digits is for file number | ||
122 | |||
123 | For example, NN99255 represents file number N99, address 255. | ||
124 | ))) | ||
125 | |(% rowspan="3" %)Double Word|F8|F8ddd|0~~255|Only able to communicate with file number F8 | ||
126 | |FN|FNddddd|0~~99255|((( | ||
127 | Floating point data file | ||
128 | |||
129 | First two digits is for file number | ||
130 | |||
131 | For example, FN99255 represents file number F99, address 255. | ||
132 | ))) | ||
133 | |LN|LNddddd|0~~99255|Long | ||
134 | |||
135 | **Cable Wiring** | ||
136 | |||
137 | {{id name="IAB.gif-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c884ca361be80135.gif||alt="AB.gif" height="247" width="400"]] | ||
138 | |||
139 | == {{id name="HMicroLogix"/}}**MicroLogix** == | ||
140 | |||
141 | MicroLogix 1000/1100/1200/1400/1500; SLC 5/03 5/04 5/05 PLC-5 | ||
142 | |||
143 | **HMI Settings** | ||
144 | |||
145 | |**Item**|**Settings**|**Note** | ||
146 | |Protocol|Allen-Bradlley MicroLogix| | ||
147 | |Connection|RS232| | ||
148 | |Baud rate|19200| | ||
149 | |Data bit|8| | ||
150 | |Parity|None| | ||
151 | |Stop bit|1| | ||
152 | |PLC station No.|1| | ||
153 | |||
154 | **Address List** | ||
155 | |||
156 | |**Type**|**Device registers**|**Format**|**Range**|**Note** | ||
157 | |(% rowspan="5" %)Bit|I|I d.d|0.0~~255.15| | ||
158 | |O|O d.d|0.0~~255.15| | ||
159 | |B|B nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
160 | |S|S d.d|0.0~~255.15| | ||
161 | |N|N nnhh.dd|0.0~~ffff.15|nn: block number (hex) | ||
162 | |(% rowspan="9" %)Word|S|S d|0~~255| | ||
163 | |TS|TS nnhh|0~~ffff|(% rowspan="8" %)nn: block number (hex) | ||
164 | |TP|TP nnhh|0~~ffff | ||
165 | |CS|CS nnhh|0~~ffff | ||
166 | |CP|CP nnhh|0~~ffff | ||
167 | |N|N nnhh|0~~ffff | ||
168 | |C|C nnhh|0~~ffff | ||
169 | |T|T nnhh|0~~ffff | ||
170 | |R|R nnhh|0~~ffff | ||
171 | |||
172 | **Cable Wiring** | ||
173 | |||
174 | {{id name="I12.PLCProtocol_html_58205bdf82c06d4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_32d8ab10ec374ea6.png||alt="12.PLC Protocol_html_58205bdf82c06d4.png" height="307" width="500"]] | ||
175 | |||
176 | == {{id name="HEtherNet2FIP28CompactLogixSeries29"/}}**EtherNet/IP(CompactLogix Series)** == | ||
177 | |||
178 | Allen-Brandly Compact Logix Free Tag | ||
179 | |||
180 | **HMI Settings** | ||
181 | |||
182 | |**Items**|**Settings**|**Note** | ||
183 | |Protocol|EtherNet/IP(CompactLogix Series)| | ||
184 | |Connection|Ethernet| | ||
185 | |Port No.|44818| | ||
186 | |||
187 | **PLC Setting** | ||
188 | |||
189 | Create new tags | ||
190 | |||
191 | {{id name="I12.PLCProtocol_html_a748a27dcf7f1124.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_75d3f4097ac67d8e.png||alt="12.PLC Protocol_html_a748a27dcf7f1124.png" height="411" width="700"]] | ||
192 | |||
193 | Export tags to CSV file. ([Tools] » [Export] » [Tags and Logic Comments]) | ||
194 | |||
195 | {{id name="I12.PLCProtocol_html_151379170bb8ff3e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_39bb299de26a0af0.png||alt="12.PLC Protocol_html_151379170bb8ff3e.png" height="352" width="700"]] | ||
196 | |||
197 | Import labels, please open [Communication] window and click [Import label]; | ||
198 | |||
199 | Select csv file, all tags will be displayed as belows; | ||
200 | |||
201 | {{id name="I12.PLCProtocol_html_af192e54dee96f38.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_4216defdc24cba39.png||alt="12.PLC Protocol_html_af192e54dee96f38.png" height="586" width="700"]] | ||
202 | |||
203 | **✎Note:** | ||
204 | |||
205 | Because in different region, the separation symbol is different, we suggest you check this before you want to import your tags. To open csv file as text format. | ||
206 | |||
207 | {{id name="I12.PLCProtocol_html_33df1d63ebe53726.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_24f4d658173f88a9.png||alt="12.PLC Protocol_html_33df1d63ebe53726.png" height="206" width="700"]] | ||
208 | |||
209 | The directory of changing system settings: [Control Panel] -> [Date, Time, Language,and Regional Options] -> [Change the format of numbers, dates, and times]->[Customize]-> [List separator]. Please select [,] and export CSV file after setting. | ||
210 | |||
211 | **Communication settings in HMI** | ||
212 | |||
213 | Enable HMI Ethernet in [Project Settings]; | ||
214 | |||
215 | {{id name="I12.PLCProtocol_html_43b671f18153910d.png-5"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_a98ee09dac36eba3.png||alt="12.PLC Protocol_html_43b671f18153910d.png" height="106" width="400"]] | ||
216 | |||
217 | Set PLC IP in [Device IP] settings; | ||
218 | |||
219 | {{id name="I12.PLCProtocol_html_27870d373581892e.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_10385ddd81c8baff.png||alt="12.PLC Protocol_html_27870d373581892e.png" height="206" width="600"]] | ||
220 | |||
221 | **Cable Wiring** | ||
222 | |||
223 | {{id name="I12.PLCProtocol_html_2297240b57346b2a.png-3"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ac8ece9a26719fda.png||alt="12.PLC Protocol_html_2297240b57346b2a.png" height="170" width="400"]] | ||
224 | |||
225 | == {{id name="HMicroLogix1200"/}}**MicroLogix 1200** == | ||
226 | |||
227 | The operational address is determined by the connection of Allen-Bradley PLC to HMI. For extension modules or other special conditions, refer to allen-Bradley PLC instruction manual. The following is an example of allen-bradley MicroLogix1200. | ||
228 | |||
229 | * **Bit address I:** The address ranges from 0.0 to 255.15. The value of the data before the decimal point ranges from 0 to 255 (decimal). The value from 0 to 15 after the decimal point is the sub address (decimal). | ||
230 | * **Bit address B:** The address ranges from 000.0 to fff.15. The first f from left to right represents the block number (hexadecimal); The second and third f from left to right represent the word address (hexadecimal). The value 0 to 15 after the decimal point reprensents the sub address (decimal). | ||
231 | * **Word address S:** The word address ranges from 0 to 255 (decimal). | ||
232 | * **Word address TS:** The address ranges from 000.0 to ffff. The first and second f from left to right represents the block number (hexadecimal); The third and fourth f from left to right represent the word address (hexadecimal). | ||
233 | |||
234 | **✎Note: **Register address TP, CS, CP, N, F and TS address edit are same. D indicates decimal, and F indicates hexadecimal. Different PLC models may support different registers. See the following table. | ||
235 | |||
236 | |**PLC bit address type**|**Address format**|**Address range** | ||
237 | |I|dd.dd|I 0.0 ~~ 255.15 | ||
238 | |O|dd.dd|O 0.0 ~~ 255.15 | ||
239 | |B|fff.dd|B 000.0 ~~ fff.15 | ||
240 | |S|dd.dd|S 0.0 ~~ 255.15 | ||
241 | |N|ffff.dd|N 000.0 ~~ fff.15 | ||
242 | |**PLC word address type**|**Address format**|**Address range** | ||
243 | |S|ddd|S0 ~~ 255 | ||
244 | |TS|ffff|TS0 ~~ FFFF | ||
245 | |TP|ffff|TP0 ~~ FFFF | ||
246 | |CS|ffff|CS0 ~~ FFFF | ||
247 | |CP|ffff|CP0 ~~ FFFF | ||
248 | |N|ffff|N0 ~~ FFFF | ||
249 | |F|ffff|F0 ~~ FFFF | ||
250 | |||
251 | == **Ethernet/IP DF1** == | ||
252 | |||
253 | Supported Series: Rockwell MicroLogix 1100, 1400, SLC5/05 Ethernet port. MicroLogix1000,1200,1500,SLC 5/03, 5/04 with 1761-NET-ENI | ||
254 | |||
255 | |**Items**|**Settings**|**Note** | ||
256 | |Protocol|Rockwell Ethernet/IP DF1| | ||
257 | |Connection|Ethernet| | ||
258 | |Port No.|44818| | ||
259 | |PLC station No.|1| | ||
260 | |||
261 | **Address List** | ||
262 | |||
263 | |=**Type**|=**Device registers**|=**Format**|=**Range**|=Note | ||
264 | |(% rowspan="7" %)Bit|I1|I1ddd.dd|0.0~~255.15|Only able to communicate with file number I1 | ||
265 | |O0|O0ddd.dd|0.0~~255.15|Only able to communicate with file number O0 | ||
266 | |S2|S2ddd.dd|0.0~~255.15|Only able to communicate with file number S2 | ||
267 | |B3|B3ddd.dd|0.0~~255.15|Only able to communicate with file number B3 | ||
268 | |BN|BNddddd.dd|0.0~~99255.15|((( | ||
269 | Bit data file B0~~B99 | ||
270 | |||
271 | First two digits is for file number | ||
272 | |||
273 | For example, BN13001.00 represents file number B13, address 001, the 0th bit. | ||
274 | ))) | ||
275 | |N7|N7ddd.dd|0.0~~255.15|Only able to communicate with file number N7 | ||
276 | |NN|NNddddd.dd|0.0~~99255.15|((( | ||
277 | Integer data file bit format N0~~N99 | ||
278 | |||
279 | First two digits is for file number | ||
280 | |||
281 | For example, NN13001.00 represents file number N13, address 001, the 0th bit. | ||
282 | ))) | ||
283 | |(% rowspan="11" %)Word|S2|S2ddd|0~~255|Only able to communicate with file number S2 | ||
284 | |T4S|T4Sddd|0~~255|Only able to communicate with file number T4 (Timer Preset Value) | ||
285 | |T4P|T4Pddd|0~~255|Only able to communicate with file number T4 (Timer Accumulator Value) | ||
286 | |TNS|TNSddddd|0~~99255|((( | ||
287 | Timer Preset Value | ||
288 | |||
289 | First two digits is for file number | ||
290 | |||
291 | For example, TNS99255 represents file number T99, address 255. | ||
292 | ))) | ||
293 | |TNP|TNPddddd|0~~99255|((( | ||
294 | Timer Accumulator Value | ||
295 | |||
296 | First two digits is for file number | ||
297 | |||
298 | For example, TNP99255 represents file number T99, address 255. | ||
299 | ))) | ||
300 | |C5S|C5Sddd|0~~255|Only able to communicate with file number C5 (Counter Preset Value) | ||
301 | |C5P|C5Pddd|0~~255|Only able to communicate with file number C5 (Counter Accumulator Value) | ||
302 | |CNS|CNSddddd|0~~99255|((( | ||
303 | Counter Preset Value | ||
304 | |||
305 | First two digits is for file number | ||
306 | |||
307 | For example, CNS99255 represents file number C99, address 255. | ||
308 | ))) | ||
309 | |CNP|CNPddddd|0~~99255|((( | ||
310 | Counter Accumulator Value | ||
311 | |||
312 | First two digits is for file number | ||
313 | |||
314 | For example, CNP99255 represents file number C99, address 255. | ||
315 | ))) | ||
316 | |N7|N7ddd|0~~255|Only able to communicate with file number N7 | ||
317 | |NN|NNddd|0~~99255|((( | ||
318 | Integer data file | ||
319 | |||
320 | First two digits is for file number | ||
321 | |||
322 | For example, NN99255 represents file number N99, address 255. | ||
323 | ))) | ||
324 | |(% rowspan="3" %)Double Word|F8|F8ddd|0~~255|Only able to communicate with file number F8 | ||
325 | |FN|FNddddd|0~~99255|((( | ||
326 | Floating point data file | ||
327 | |||
328 | First two digits is for file number | ||
329 | |||
330 | For example, FN99255 represents file number F99, address 255. | ||
331 | ))) | ||
332 | |LN|LNddddd|0~~99255|Long | ||
333 | |||
334 | **PLC Setting:** | ||
335 | |||
336 | 1.Open the RSLinx Classic Lite software and click [Configure Drivers...] in [Communications].[[image:1.png]] | ||
337 | |||
338 | 2.Click the drop-down menu and select EtherNet/IP driver[[image:2.png]] | ||
339 | |||
340 | 3.Click Add New and a pop-up window will pop up. Name the driver and click [OK] in the pop-up window.[[image:3.png]] | ||
341 | |||
342 | 4.The configuration driver window pops up., click on the correct network adapter option (such as the ASIX USB to Fast Ethernet Family Adapter option in this picture), and click OK | ||
343 | |||
344 | [[image:4.png]] | ||
345 | |||
346 | 5.Click the [Close] button.[[image:5.png]] | ||
347 | |||
348 | 6.Click the [RSWho] button.[[image:6.png]] | ||
349 | |||
350 | 7.Pop up the RS Who window, indicating that the driver has been added successfully.[[image:7.png]] | ||
351 | |||
352 | 8.Open the RSLogix 500Pro software and select [System Comms...] in the [Comms] option.[[image:8.jpg]] | ||
353 | |||
354 | 9.Select the driver you have created. All device nodes in the same LAN as the computer will be scanned. Select the PLC to be connected and click [OK]. | ||
355 | |||
356 | [[image:9.png]] | ||
357 | |||
358 | 10.Click Comms [Go Online].[[image:10.png]] | ||
359 | |||
360 | 11.Click [YES] in the pop-up window.[[image:11.png]] | ||
361 | |||
362 | 12.Enter online mode.[[image:14.jpg]] | ||
363 | |||
364 | **Cable Wiring** | ||
365 | |||
366 | (% style="text-align:center" %) | ||
367 | [[image:Ethernet.png]] | ||
368 | |||
369 | |||
370 | == **Rockwell EtherNet/IP(CompactLogix Series)** == | ||
371 | |||
372 | Supported Series: Rockwell CompactLogix Series Ethernet | ||
373 | |||
374 | |**Items**|**Settings**|**Note** | ||
375 | |Protocol|Rockwell EtherNet/IP (CompactLogix Series)| | ||
376 | |Connection|Ethernet| | ||
377 | |Port No.|44818| | ||
378 | |PLC station No.|1| | ||
379 | |||
380 | **Support Variable Type** | ||
381 | |||
382 | |PLC data type|Bit/Word|PIStudio data format|Memo | ||
383 | |BOOL|Boolean|Bit object| | ||
384 | |BitArray| | | | ||
385 | |SINT| | |-128-127 | ||
386 | |USINT| | |0~~255 | ||
387 | |INT|Integer|16-bit signed, ASCll|-32768~~32767 | ||
388 | |UINT| | |0~~65535 | ||
389 | |DINT|Double integer|32-bit signed|-2^31~~(2^31-1) | ||
390 | |UDINT| | |0~~4294967295 | ||
391 | |REAL|Single Precision Float|32-bit floating| | ||
392 | |LINT|Long integer|64-bit signed| | ||
393 | |ULINT|Long integer|64-bit unsigned| | ||
394 | |LREAL|Double Precision Float|64-bit double| | ||
395 | |STRING| | |Enable Read DWord | ||
396 | |||
397 | **PLC Setting:** | ||
398 | |||
399 | 1.Open the RSLinx Classic Lite software and click [Configure Drivers...] in [Communications]. | ||
400 | |||
401 | [[image:1726907484077-900.png]] | ||
402 | |||
403 | 2.Click the drop-down menu and select EtherNet/IP driver | ||
404 | |||
405 | [[image:1726907484081-522.png]] | ||
406 | |||
407 | 3.Click Add New and a pop-up window will pop up. Name the driver and click [OK] in the pop-up window. | ||
408 | |||
409 | [[image:1726907484084-295.png]] | ||
410 | |||
411 | 4.The configuration driver window pops up., click on the correct network adapter option (such as the ASIX USB to Fast Ethernet Family Adapter option in this picture), and click [OK]. | ||
412 | |||
413 | [[image:1726907484085-985.png]] | ||
414 | |||
415 | 5.Click the [Close] button | ||
416 | |||
417 | [[image:1726907484087-419.png]] | ||
418 | |||
419 | 6.Open Stuido5000 and create a new project or open an existing project. | ||
420 | |||
421 | To create a new project: click [New Project]. | ||
422 | |||
423 | (% style="text-align:center" %) | ||
424 | [[image:1726907578613-886.png]] | ||
425 | |||
426 | 7.Click the [1769-L16ER-BB1B]→ Edit Project Name → Select the file storage location → [Next] | ||
427 | |||
428 | (% style="text-align:center" %) | ||
429 | [[image:1726907578645-890.png]] | ||
430 | |||
431 | 8. Select the software version →Select [Expansion I/O] number→ Security Authority → Click [Finish]. | ||
432 | |||
433 | The software version must be the same as the PLC firmware version, and the Security Authority protection should be selected according to personal needs. | ||
434 | |||
435 | (% style="text-align:center" %) | ||
436 | [[image:1726907578647-323.png]] | ||
437 | |||
438 | **~ Create a new tag** | ||
439 | |||
440 | 1.Click the drop-down menu on the left of [Controller ABcs]→ Right-click [Controller Tags] → Click [New tag]. | ||
441 | |||
442 | [[image:1726907578648-590.png]] | ||
443 | |||
444 | 2.Input tag name → Select tag type → Create | ||
445 | |||
446 | (% style="text-align:center" %) | ||
447 | [[image:1726907578652-543.png]] | ||
448 | |||
449 | Establishing communication | ||
450 | |||
451 | 1.Click [Communications]→Click[Who Active]. | ||
452 | |||
453 | (% style="text-align:center" %) | ||
454 | [[image:6.jpg]] | ||
455 | |||
456 | 2.Select the drive → Select the corresponding PLC →Click [Go Online]. | ||
457 | |||
458 | The driver is a new created driver from step 1.2 | ||
459 | |||
460 | (% style="text-align:center" %) | ||
461 | [[image:1726908219964-183.png]] | ||
462 | |||
463 | 3.Click [Download] | ||
464 | |||
465 | (% style="text-align:center" %) | ||
466 | [[image:1726908219966-477.png]] | ||
467 | |||
468 | 4.Click [Download]→ [YES]. | ||
469 | |||
470 | (% style="text-align:center" %) | ||
471 | [[image:1726908219968-250.png]] | ||
472 | |||
473 | |||
474 | (% style="text-align:center" %) | ||
475 | [[image:1726908219970-794.png]] | ||
476 | |||
477 | |||
478 | **Export Tags** | ||
479 | |||
480 | 1.Click the drop-down menu on the left of [Controller ABcs]→Right-click [Controller Tags]→ Click [Export Tags]. | ||
481 | |||
482 | (% style="text-align:center" %) | ||
483 | [[image:11.jpg]] | ||
484 | |||
485 | 2.Edit the tag file name → Select the file storage location → [Export]. | ||
486 | |||
487 | (% style="text-align:center" %) | ||
488 | [[image:1726908448582-442.png]] | ||
489 | |||
490 | **HMI Setting:** | ||
491 | |||
492 | ① [Project]→[Communication]→[Setting] | ||
493 | |||
494 | [[image:1726909065716-860.png]] | ||
495 | |||
496 | ② Choose protocol: | ||
497 | |||
498 | Device type [Rockwell]→[Rockwell EtherNet/IP(CompactLogix Series)]→[OK] | ||
499 | |||
500 | (% style="text-align:center" %) | ||
501 | [[image:1726909065723-657.png]] | ||
502 | |||
503 | ③[Setting]→[PLC IP Address]→[OK]→[Labels manage]. | ||
504 | |||
505 | (% style="text-align:center" %) | ||
506 | [[image:1726909065724-657.png]] | ||
507 | |||
508 | ④Tags import: | ||
509 | |||
510 | [Import Tags From File]→Choose the .CSV file→[Open]→[Save]→[OK] | ||
511 | |||
512 | (% style="text-align:center" %) | ||
513 | [[image:1726909065726-124.png]] | ||
514 | |||
515 | **Project making** | ||
516 | |||
517 | ①Using PIStudio to program a HMI project depending on the requirements. | ||
518 | |||
519 | (% style="text-align:center" %) | ||
520 | [[image:1726909065727-501.png]] | ||
521 | |||
522 | ②After programming[Compile], you can download the project into HMI when compilation complete. | ||