1 | = {{id name="HSchneider"/}}**Schneider** = | ||
2 | |||
3 | == {{id name="HSchneiderMODBUSRTU"/}}**MODBUS RTU** == | ||
4 | |||
5 | **HMI Setting** | ||
6 | |||
7 | |=**Parameters**|=**Recommended**|=**Notes** | ||
8 | |=**Protocol**|Schneider MODBUS RTU| | ||
9 | |=Connection|RS485| | ||
10 | |=**Baud rate**|19200| | ||
11 | |=**Data bit**|8| | ||
12 | |=**Parity**|Even| | ||
13 | |=**Stop bit**|1| | ||
14 | |=**PLC station No.**|1| | ||
15 | |||
16 | **PLC Setting** | ||
17 | |||
18 | |=**Communication mode**|Modbus RTU protocol | ||
19 | |||
20 | **Device Address** | ||
21 | |||
22 | |=**Bit/Word**|=**Device type**|=**Format**|=**Range**|=**Memo** | ||
23 | |B|IX|DDDDDo|0 ~~ 655357|Input bit (read only) | ||
24 | |B|QX|DDDDDo|0 ~~ 655357|Write multiple coils | ||
25 | |B|MX|DDDDDDo|0 ~~ 9999997|Output register bit (octal) | ||
26 | |W|MW|DDDDDD|0 ~~ 999999|Output register | ||
27 | |DW|MD|DDDDDD|0 ~~ 999999|Output register | ||
28 | |||
29 | **Wiring Diagram** | ||
30 | |||
31 | **RS-485 2W **(RJ45 Connector): The following is the view from the soldering point of a connector. | ||
32 | |||
33 | {{id name="Iimage-20220817154212-1.jpeg"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c74587d16cc7ee2.jpg||alt="image-20220817154212-1.jpeg" height="315" width="554"]] | ||
34 | |||
35 | == **TM218 series** == | ||
36 | |||
37 | |||
38 | **HMI Setting** | ||
39 | |||
40 | |=**Parameters**|=**Recommended**|=**Notes** | ||
41 | |=**Protocol**|Schneider Modicon MODBUS RTU| | ||
42 | |=Connection|RS485| | ||
43 | |=**Baud rate**|19200| | ||
44 | |=**Data bit**|8| | ||
45 | |=**Parity**|Even| | ||
46 | |=**Stop bit**|1| | ||
47 | |=**PLC station No.**|1 | ||
48 | |||
49 | **Device Address** | ||
50 | |||
51 | |=**Bit/Word**|=**Device type**|=**Format**|=**Range** | ||
52 | |B|IX|IX dddd.d|0 to 65535 | ||
53 | |B|QX|QX dddd.d|0 to 65535 | ||
54 | |B|MX|MX dddd.dd|0 to 999999 | ||
55 | |W|MW|MW dddd|0 to 999999 | ||
56 | |||
57 | **Configure the communication protocol** | ||
58 | |||
59 | (% style="text-align:center" %) | ||
60 | [[image:11.png]] | ||
61 | |||
62 | (% style="text-align:center" %) | ||
63 | [[image:12.png]] | ||
64 | |||
65 | **PLC Setting:** | ||
66 | |||
67 | Open SoMachine Central, create a new project or open the project that has been created. | ||
68 | |||
69 | Create new project: [Create a new project]→[Empty Project]→[OK]→[Open Configuration] | ||
70 | |||
71 | (% style="text-align:center" %) | ||
72 | [[image:2.png]] | ||
73 | |||
74 | (% style="text-align:center" %) | ||
75 | [[image:3.png]] | ||
76 | |||
77 | Into the [Open Configuration]. | ||
78 | |||
79 | [Untitled]→[Add Device]→[Logic Controller]→[M218]→[TM218LDA16DRN] | ||
80 | |||
81 | (% style="text-align:center" %) | ||
82 | [[image:4.png]] | ||
83 | |||
84 | PLC Default Parameters: | ||
85 | |||
86 | In the Devices tree [MyController]→[Serial Line 2]→[Modbus_Manager] | ||
87 | |||
88 | Modbus: | ||
89 | |||
90 | [Transmission Mode] RTU→[Addressing] Slave | ||
91 | |||
92 | Serial Line Settings: | ||
93 | |||
94 | [Baud rate] 19200, [Data bits] 8, [Stop bits] 1, [Parity] EVEN, [Physical Medium] RS485 | ||
95 | |||
96 | (% style="text-align:center" %) | ||
97 | [[image:5.png]] | ||
98 | |||
99 | **Cable Wiring** | ||
100 | |||