1 += {{id name="HWECON"/}}WECON =
2 +
3 +== {{id name="HLX3Series"/}}**LX3 Series** ==
4 +
5 +Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM
6 +
7 +**HMI Settings**
8 +
9 +|=**Item**|=**Settings**|=**Note**
10 +|=Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM|
11 +|=Connection|RS422/RS485|
12 +|=Baud rate|9600|
13 +|=Data bit|7|
14 +|=Parity|EVEN|
15 +|=Stop bit|1|
16 +|=PLC station No.|1|
17 +
18 +**Address List**
19 +
20 +|=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note**
21 +|=Bit|=X|X|Xo|0~~303237|
22 +|=Y|Y|Y o|0~~303237|
23 +|=M|M|M d|0~~99999|
24 +|=T|T|T d|0~~99999|
25 +|=C|C|C d|0~~99999|
26 +|=S|S|S d|0~~99999|
27 +|=Word|=X|X|Xo|0~~303237|
28 +|=Y|Y|Y o|0~~303237|
29 +|=M|M|M d|0~~99999|
30 +|=T|T|T d|0~~99999|
31 +|=C|C|C d|0~~199|
32 +|=D|D|D d|0~~7999|
33 +|=S|S|S d|0~~99999|
34 +|=SD|SD|SD d|8000~~9999|
35 +
36 +**Cable Wiring**
37 +
38 +* **RS485**
39 +
40 +{{id name="I12.PLCProtocol_html_1897d92be6948d58.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6d16b5adff76549.png||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]]
41 +
42 +* **RS422**
43 +
44 +{{id name="I12.PLCProtocol_html_5c7fca9a70da2ee8.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_59ce051d2c5e70e0.png||alt="12.PLC Protocol_html_5c7fca9a70da2ee8.png" height="247" width="389"]]
45 +
46 +**✎Note:**
47 +
48 +* HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) .
49 +* If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual.
50 +
51 +[[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]]
52 +
53 +{{id name="HHMIsettings"/}}**HMI settings**
54 +
55 +**Download PIStudio Software**
56 +
57 +Please visit the link below to get the latest version PIstudio for HMI programming:
58 +
59 +* [[Download link>>url:https://docs.we-con.com.cn/bin/view/PIStudio/Download/3%20Software/]]
60 +
61 +**Create a new HMI project connect with PLC**
62 +
63 +Check the link below for the video to show you how to get started with a new project
64 +
65 +* [[Video>>url:https://youtu.be/0FpmDZe_8U8]]
66 +
67 +For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]]
68 +
69 +**General**
70 +
71 +HMI could communicate with PLC and support many PLC protocols.  It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example.
72 +
73 +**Protocol settings**
74 +
75 +The communication between two devices requires a protocol. The following contents show the steps of protocol settings.
76 +
77 +Please select the protocol, when creating a new project.
78 +
79 +1. Select the COM port for communication;
80 +1. PLC type: It means PLC brand, like WECON;
81 +1. PLC model: It shows the model of PLC, such as LX3V;
82 +
83 +{{id name="Iimage-20220819093729-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_271ccf1461ff2285.png||alt="image-20220819093729-1.png" height="236" width="464"]]
84 +
85 +If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure.
86 +
87 +{{id name="Iimage-20220819093729-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_9089051384ca99de.png||alt="image-20220819093729-2.png" height="138" width="702"]]
88 +
89 +The steps to change the protocol for project are as follows.
90 +
91 +1. Click [Setting] to open the [Communication device] window;
92 +1. Select communication port, such as COM1;
93 +1. Select Serial port for communication, such as RS422;
94 +1. Select device type (device brand), such as WECON;
95 +1. Select the protocol for communication, such as WECON LX3V;
96 +
97 +{{id name="Iimage-20220819093729-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_33df6370c17ebfa9.png||alt="image-20220819093729-3.png" height="674" width="875"]]
98 +
99 +**Parameter settings**
100 +
101 +The parameters settings are in [Communication] window, shown as following below.
102 +
103 +1. Click [Setting] to open the [COM port setting] window;
104 +1. Set the parameters such as [connection], [Baud rate] and so on;
105 +
106 +{{id name="Iimage-20220819093729-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_891cd58628495097.png||alt="image-20220819093729-4.png" height="636" width="818"]]
107 +
108 +1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value.
109 +
110 +{{id name="Iimage-20220819093729-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_b80c1a7329ce3f5f.png||alt="image-20220819093729-5.png" height="296" width="349"]]
111 +
112 +**Set PLC address in HMI screen**
113 +
114 +1. Place the objects to HMI screen;
115 +1. Double-click the object to open the setting window;
116 +1. Click “Edit” to open the address setting windows;
117 +1. Connection: select the serial port in HMI;
118 +1. Address type: All the PLC address types will be display in this list, such as M;
119 +1. Address No.: Please input the number of this address, such as 0;
120 +
121 +{{id name="Iimage-20220819093729-6.jpeg"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c233137c112020bf.jpg||alt="image-20220819093729-6.jpeg" height="817" width="1593"]]
122 +
123 +**HMI Compilation Download**
124 +
125 +{{id name="Iimage-20220902171247-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_49085bc4fc23af93.png||alt="image-20220902171247-1.png" height="1078" width="1262"]]
126 +
127 +**Communication cable**
128 +
129 +In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition.
130 +
131 +{{id name="Iimage-20220819093729-7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e18a02a8b5c24f4a.png||alt="image-20220819093729-7.png" height="256" width="414"]]
132 +
133 +**HMI communication PLC use Modbus **
134 +
135 +* HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>url:https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]]
136 +* PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>url:https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]]
137 +
138 +{{id name="HPLCsettings"/}}**PLC settings**
139 +
140 +**Download PLC Software**
141 +
142 +Please visit below link to get the latest version PLC Editor for HMI programming
143 +
144 +* LX3V:[[Download link>>url:https://docs.we-con.com.cn/bin/view/PLC%20Editor/10%20Hardware%20/Software/]]
145 +* LX5V:[[Download link>>url:https://docs.we-con.com.cn/bin/view/PLC%20Editor2/Download/03%20Software/]]
146 +
147 +**Start a new PLC project**
148 +
149 +Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list.
150 +
151 +{{id name="Iimage-20220819101447-3.jpeg"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d5d194db9d1d33d0.jpg||alt="image-20220819101447-3.jpeg" height="411" width="726"]]
152 +
153 +**Add a new instruction **
154 +
155 +Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol.
156 +
157 +{{id name="Iimage-20220819105530-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6e59dd6d3eba4d.png||alt="image-20220819105530-1.png" height="387" width="698"]]
158 +
159 +You could also select the ladder symbol from the menu bar directly.
160 +
161 +{{id name="Iimage-20220819093729-12.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_db5a3ad72966c00e.png||alt="image-20220819093729-12.png" height="1040" width="1920"]]
162 +
163 +**Add comment to PLC program**
164 +
165 +{{id name="Iimage-20220819105630-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_50fcec6a5d6ac220.png||alt="image-20220819105630-3.png" height="413" width="698"]]
166 +
167 +**Add the statement to PLC program**
168 +
169 +Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit.
170 +
171 +{{id name="Iimage-20220819105644-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d44e5ea0b00e2e14.png||alt="image-20220819105644-4.png" height="345" width="698"]]
172 +
173 +**Compile **
174 +
175 +You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error.
176 +
177 +{{id name="Iimage-20220819093729-15.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e2d51171f234946a.png||alt="image-20220819093729-15.png" height="356" width="1912"]]
178 +
179 +**Download setting **
180 +
181 +Click on “Transfer Setup” to select download mode.
182 +
183 +{{id name="Iimage-20220820150853-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_98b1686a16c575ea.png||alt="image-20220820150853-1.png" height="713" width="1509"]] **Download PLC program to PLC**
184 +
185 +Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK”
186 +
187 +{{id name="Iimage-20220819093729-17.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_575b66f5b3d8cac5.png||alt="image-20220819093729-17.png" height="808" width="1920"]]
188 +
189 +**Upload PLC program from PLC**
190 +
191 +Read the PLC program from PLC to computer.
192 +
193 +{{id name="Iimage-20220819093729-18.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_66ea9f304121cf6d.png||alt="image-20220819093729-18.png" height="762" width="1920"]]
194 +
195 +**Device monitor**
196 +
197 +Monitor the value of certain address in PLC, double click “Current value” to change the value in this address.
198 +
199 +{{id name="Iimage-20220819093730-19.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ee6125099c14cb2b.png||alt="image-20220819093730-19.png" height="781" width="1920"]]
200 +
201 +**Online monitor**
202 +
203 +Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd.
204 +
205 +{{id name="Iimage-20220819093730-20.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_21923412853b2626.png||alt="image-20220819093730-20.png" height="564" width="1607"]]
206 +
207 +**Monitor edit**
208 +
209 +In this mode, you could edit the PLC program during PLC is running. 
210 +
211 +{{id name="Iimage-20220819105928-9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_9c0519bed3567723.png||alt="image-20220819105928-9.png" height="229" width="669"]]
212 +
213 +== {{id name="HLX5VA0Series"/}}**LX5V Series** ==
214 +
215 +This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
216 +
217 +**Software configuration of PLC**
218 +
219 +PLC programming software
220 +
221 +{{id name="Iimage-20220810164710-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7599c2849074f02b.png||alt="image-20220810164710-1.png" height="326" width="424"]]
222 +
223 +**New PLC project**
224 +
225 +Click "New Project" and select the PLC model.
226 +
227 +{{id name="Iimage-20220810172412-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d6bc182897bb2201.png||alt="image-20220810172412-1.png" height="898" width="1672"]]
228 +
229 +**Set Serial port parameters**
230 +
231 +Follow the steps below to configure Serial port parameters.
232 +
233 +* Baud rate:115200
234 +* Data bit:8
235 +* Stop bit:1
236 +* Parity:No verification
237 +
238 +{{id name="Iimage-20220810165759-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6b7effc40ae03777.png||alt="image-20220810165759-3.png" height="1029" width="1920"]]
239 +
240 +**Registers list**
241 +
242 +{{id name="Iimage-20220811102219-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_eb0d8d9280761af1.png||alt="image-20220811102219-3.png" height="658" width="1226"]]
243 +
244 +**HMI software configuration**
245 +
246 +HMI programming software
247 +
248 +{{id name="Iimage-20220810171237-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d127b46be5bf7497.png||alt="image-20220810171237-4.png" height="419" width="673"]]
249 +
250 +**New HMI project**
251 +
252 +Click New Project and select the HMI model.
253 +
254 +{{id name="Iimage-20220810172010-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e73d0d6216dbf983.png||alt="image-20220810172010-5.png" height="912" width="1697"]]
255 +
256 +Set communication port parameters
257 +
258 +Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port.
259 +
260 +* Baud rate:115200
261 +* Data bit:8
262 +* Stop bit:1
263 +* Parity:No verification
264 +
265 +{{id name="Iimage-20220811104012-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dac87f79e1471c71.png||alt="image-20220811104012-1.png" height="965" width="1383"]]
266 +
267 +**hardware connection**
268 +
269 +Hardware wiring diagram
270 +
271 +This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows:
272 +
273 +{{id name="Iimage-20220811103005-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dab0150e5cf17042.png||alt="image-20220811103005-4.png" height="150" width="681"]]
274 +
275 +{{id name="Iimage-20220811103227-7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d72bd5e65a0f052c.png||alt="image-20220811103227-7.png" height="209" width="342"]]
276 +
277 +The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC.
278 +
279 +== {{id name="HLX5V-NEthernet"/}}**LX5V-N Ethernet** ==
280 +
281 +{{id name="cke_bm_147709S"/}} This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring.
282 +
283 +**Software configuration of PLC**
284 +
285 +**PLC programming software**
286 +
287 +{{id name="Iimage-20220810164710-1.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7599c2849074f02b.png||alt="image-20220810164710-1.png" height="326" width="424"]]
288 +
289 +**New PLC project**
290 +
291 +Click New Project and select the PLC model.
292 +
293 +{{id name="Iimage-20220811115454-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ff2c1cc959b53fdd.png||alt="image-20220811115454-1.png" height="930" width="1699"]]
294 +
295 +**Set Ethernet port parameters**
296 +
297 +Follow the steps below to configure Ethernet parameters
298 +
299 +* PLC IP address:192.168.39.200
300 +* default gateway:192.168.39.1
301 +* subnet mask:255.255.255.0
302 +
303 +{{id name="Iimage-20220811140530-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_60404ed3c7204071.png||alt="image-20220811140530-2.png" height="1031" width="1920"]]
304 +
305 +**Registers list**
306 +
307 +{{id name="Iimage-20220811102219-3.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_eb0d8d9280761af1.png||alt="image-20220811102219-3.png" height="658" width="1226"]]
308 +
309 +**HMI software configuration**
310 +
311 +HMI programming software
312 +
313 +{{id name="Iimage-20220810171237-4.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d127b46be5bf7497.png||alt="image-20220810171237-4.png" height="419" width="673"]]
314 +
315 +**New HMI project**
316 +
317 +Click New Project and select the HMI model.
318 +
319 +{{id name="Iimage-20220810172010-5.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e73d0d6216dbf983.png||alt="image-20220810172010-5.png" height="912" width="1697"]]
320 +
321 +**Set communication port parameters**
322 +
323 +Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network.
324 +
325 +* HMI IP address:192.168.39.201
326 +* Default gateway:192.168.39.1
327 +* Subnet mask:255.255.255.0
328 +
329 +{{id name="Iimage-20220811170753-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_94717717b08e9074.png||alt="image-20220811170753-2.png" height="1008" width="1920"]]
330 +
331 +Next, click Communication Settings to configure the IP of the HMI communication object.
332 +
333 +{{id name="Iimage-20220811163047-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_291564bcc9db7b1b.png||alt="image-20220811163047-1.png" height="1030" width="1920"]]
334 +
335 +**Hardware connection**
336 +
337 +This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows:
338 +
339 +{{id name="Iimage-20220811170248-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dcab5cd2ecf22982.png||alt="image-20220811170248-1.png" height="199" width="779"]]
340 +
341 +The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC.