Hide last authors
author | version | line-number | content |
---|---|---|---|
![]() |
2.1 | 1 | = {{id name="HWECON"/}}WECON = |
2 | |||
3 | == {{id name="HLX3Series"/}}**LX3 Series** == | ||
4 | |||
5 | Supported series: WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM | ||
6 | |||
7 | **HMI Settings** | ||
8 | |||
9 | |=**Item**|=**Settings**|=**Note** | ||
10 | |=Protocol|WECON LX2V/ LX2E/ LX3V/LX3VP/LX3VE/LX3VM| | ||
11 | |=Connection|RS422/RS485| | ||
12 | |=Baud rate|9600| | ||
13 | |=Data bit|7| | ||
14 | |=Parity|EVEN| | ||
15 | |=Stop bit|1| | ||
16 | |=PLC station No.|1| | ||
17 | |||
18 | **Address List** | ||
19 | |||
20 | |=**Type**|=**Device registers**|=**HMI registers**|=**Format**|=**Range**|=**Note** | ||
21 | |=Bit|=X|X|Xo|0~~303237| | ||
22 | |=Y|Y|Y o|0~~303237| | ||
23 | |=M|M|M d|0~~99999| | ||
24 | |=T|T|T d|0~~99999| | ||
25 | |=C|C|C d|0~~99999| | ||
26 | |=S|S|S d|0~~99999| | ||
27 | |=Word|=X|X|Xo|0~~303237| | ||
28 | |=Y|Y|Y o|0~~303237| | ||
29 | |=M|M|M d|0~~99999| | ||
30 | |=T|T|T d|0~~99999| | ||
31 | |=C|C|C d|0~~199| | ||
32 | |=D|D|D d|0~~7999| | ||
33 | |=S|S|S d|0~~99999| | ||
34 | |=SD|SD|SD d|8000~~9999| | ||
35 | |||
36 | **Cable Wiring** | ||
37 | |||
38 | * **RS485** | ||
39 | |||
40 | {{id name="I12.PLCProtocol_html_1897d92be6948d58.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c6d16b5adff76549.png||alt="12.PLC Protocol_html_1897d92be6948d58.png" height="223" width="393"]] | ||
41 | |||
42 | * **RS422** | ||
43 | |||
44 | {{id name="I12.PLCProtocol_html_5c7fca9a70da2ee8.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_59ce051d2c5e70e0.png||alt="12.PLC Protocol_html_5c7fca9a70da2ee8.png" height="247" width="389"]] | ||
45 | |||
46 | **✎Note:** | ||
47 | |||
48 | * HMI COM3 is available in PI8000 series and COM3 is in COM2(hardware PIN 7 and PIN 8) . | ||
49 | * If PLC <= 20 points,such as LX3V-1208/LX3V-0806 PLC,PLC RS485A and RS485B mean PLC COM2 RS485+ and RS485- .PLC COM2 can support modbus. Please refer to PLC COM2 setting manual. | ||
50 | |||
51 | [[https:~~/~~/drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing>>url:https://drive.google.com/drive/folders/13rgso7oUlatZQN_SNEcJCcN4toEdDPoP?usp=sharing]] | ||
52 | |||
![]() |
38.3 | 53 | **{{id name="HHMIsettings"/}}HMI settings** |
![]() |
2.1 | 54 | |
55 | **Download PIStudio Software** | ||
56 | |||
57 | Please visit the link below to get the latest version PIstudio for HMI programming: | ||
58 | |||
59 | * [[Download link>>url:https://docs.we-con.com.cn/bin/view/PIStudio/Download/3%20Software/]] | ||
60 | |||
61 | **Create a new HMI project connect with PLC** | ||
62 | |||
63 | Check the link below for the video to show you how to get started with a new project | ||
64 | |||
65 | * [[Video>>url:https://youtu.be/0FpmDZe_8U8]] | ||
66 | |||
67 | For more videos, please visit our Youtube channel: [[http:~~/~~/www.youtube.com/user/Wecon2004/videos>>url:http://www.youtube.com/user/Wecon2004/videos]] | ||
68 | |||
69 | **General** | ||
70 | |||
71 | HMI could communicate with PLC and support many PLC protocols. It is easy to operate and set communication parameters. This demo shows how to make a communication with PLC device, use WECON LX3V Series PLC as an example. | ||
72 | |||
73 | **Protocol settings** | ||
74 | |||
75 | The communication between two devices requires a protocol. The following contents show the steps of protocol settings. | ||
76 | |||
77 | Please select the protocol, when creating a new project. | ||
78 | |||
79 | 1. Select the COM port for communication; | ||
80 | 1. PLC type: It means PLC brand, like WECON; | ||
81 | 1. PLC model: It shows the model of PLC, such as LX3V; | ||
82 | |||
83 | {{id name="Iimage-20220819093729-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_271ccf1461ff2285.png||alt="image-20220819093729-1.png" height="236" width="464"]] | ||
84 | |||
85 | If you want to change the protocol for existing project, please click [Program] → [Communication] to open the [Communication] windows, shown as the following figure. | ||
86 | |||
87 | {{id name="Iimage-20220819093729-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_9089051384ca99de.png||alt="image-20220819093729-2.png" height="138" width="702"]] | ||
88 | |||
89 | The steps to change the protocol for project are as follows. | ||
90 | |||
91 | 1. Click [Setting] to open the [Communication device] window; | ||
92 | 1. Select communication port, such as COM1; | ||
93 | 1. Select Serial port for communication, such as RS422; | ||
94 | 1. Select device type (device brand), such as WECON; | ||
95 | 1. Select the protocol for communication, such as WECON LX3V; | ||
96 | |||
97 | {{id name="Iimage-20220819093729-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_33df6370c17ebfa9.png||alt="image-20220819093729-3.png" height="674" width="875"]] | ||
98 | |||
99 | **Parameter settings** | ||
100 | |||
101 | The parameters settings are in [Communication] window, shown as following below. | ||
102 | |||
103 | 1. Click [Setting] to open the [COM port setting] window; | ||
104 | 1. Set the parameters such as [connection], [Baud rate] and so on; | ||
105 | |||
106 | {{id name="Iimage-20220819093729-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_891cd58628495097.png||alt="image-20220819093729-4.png" height="636" width="818"]] | ||
107 | |||
108 | 1. Click [Setting] to open [Timeout] setting window, you could set the parameters according your requirements, or just use the default value. | ||
109 | |||
110 | {{id name="Iimage-20220819093729-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_b80c1a7329ce3f5f.png||alt="image-20220819093729-5.png" height="296" width="349"]] | ||
111 | |||
112 | **Set PLC address in HMI screen** | ||
113 | |||
114 | 1. Place the objects to HMI screen; | ||
115 | 1. Double-click the object to open the setting window; | ||
116 | 1. Click “Edit” to open the address setting windows; | ||
117 | 1. Connection: select the serial port in HMI; | ||
118 | 1. Address type: All the PLC address types will be display in this list, such as M; | ||
119 | 1. Address No.: Please input the number of this address, such as 0; | ||
120 | |||
121 | {{id name="Iimage-20220819093729-6.jpeg"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_c233137c112020bf.jpg||alt="image-20220819093729-6.jpeg" height="817" width="1593"]] | ||
122 | |||
123 | **HMI Compilation Download** | ||
124 | |||
125 | {{id name="Iimage-20220902171247-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_49085bc4fc23af93.png||alt="image-20220902171247-1.png" height="1078" width="1262"]] | ||
126 | |||
127 | **Communication cable** | ||
128 | |||
129 | In order to ensure the stability of communication, please use the twisted-pair communication cable with good grounding. The following figure shows the pin out definition. | ||
130 | |||
131 | {{id name="Iimage-20220819093729-7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e18a02a8b5c24f4a.png||alt="image-20220819093729-7.png" height="256" width="414"]] | ||
132 | |||
133 | **HMI communication PLC use Modbus ** | ||
134 | |||
135 | * HMI setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/>>url:https://docs.we-con.com.cn/bin/view/PIStudio/12.PLC%20protocols/]] | ||
136 | * PLC setting: [[https:~~/~~/docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/>>url:https://docs.we-con.com.cn/bin/view/PLC%20Editor/8.1.%09Communication/]] | ||
137 | |||
![]() |
38.3 | 138 | **{{id name="HPLCsettings"/}}PLC settings** |
![]() |
2.1 | 139 | |
140 | **Download PLC Software** | ||
141 | |||
142 | Please visit below link to get the latest version PLC Editor for HMI programming | ||
143 | |||
144 | * LX3V:[[Download link>>url:https://docs.we-con.com.cn/bin/view/PLC%20Editor/10%20Hardware%20/Software/]] | ||
145 | * LX5V:[[Download link>>url:https://docs.we-con.com.cn/bin/view/PLC%20Editor2/Download/03%20Software/]] | ||
146 | |||
147 | **Start a new PLC project** | ||
148 | |||
149 | Start a new PLC project by clicking “New” on the left top corner of screen, select the PLC mode from the drop-down list. | ||
150 | |||
151 | {{id name="Iimage-20220819101447-3.jpeg"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d5d194db9d1d33d0.jpg||alt="image-20220819101447-3.jpeg" height="411" width="726"]] | ||
152 | |||
153 | **Add a new instruction ** | ||
154 | |||
155 | Double click on the ladder, select the ladder symbol (instruction) from the drop-down list, then enter the address for this symbol. | ||
156 | |||
157 | {{id name="Iimage-20220819105530-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6e59dd6d3eba4d.png||alt="image-20220819105530-1.png" height="387" width="698"]] | ||
158 | |||
159 | You could also select the ladder symbol from the menu bar directly. | ||
160 | |||
161 | {{id name="Iimage-20220819093729-12.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_db5a3ad72966c00e.png||alt="image-20220819093729-12.png" height="1040" width="1920"]] | ||
162 | |||
163 | **Add comment to PLC program** | ||
164 | |||
165 | {{id name="Iimage-20220819105630-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_50fcec6a5d6ac220.png||alt="image-20220819105630-3.png" height="413" width="698"]] | ||
166 | |||
167 | **Add the statement to PLC program** | ||
168 | |||
169 | Add the statement by single click on “Statement”, when finished, single click on “Statement” again to go back to Ladder edit. | ||
170 | |||
171 | {{id name="Iimage-20220819105644-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d44e5ea0b00e2e14.png||alt="image-20220819105644-4.png" height="345" width="698"]] | ||
172 | |||
173 | **Compile ** | ||
174 | |||
175 | You need to compile the PLC program before downloading or running Off-line simulator. The background color will be changed from purple to white when there is no error. | ||
176 | |||
177 | {{id name="Iimage-20220819093729-15.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e2d51171f234946a.png||alt="image-20220819093729-15.png" height="356" width="1912"]] | ||
178 | |||
179 | **Download setting ** | ||
180 | |||
181 | Click on “Transfer Setup” to select download mode. | ||
182 | |||
183 | {{id name="Iimage-20220820150853-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_98b1686a16c575ea.png||alt="image-20220820150853-1.png" height="713" width="1509"]] **Download PLC program to PLC** | ||
184 | |||
185 | Quick select the parameters and main program of PLC program, then download to PLC, “Yes”-”Yes”-”OK” | ||
186 | |||
187 | {{id name="Iimage-20220819093729-17.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_575b66f5b3d8cac5.png||alt="image-20220819093729-17.png" height="808" width="1920"]] | ||
188 | |||
189 | **Upload PLC program from PLC** | ||
190 | |||
191 | Read the PLC program from PLC to computer. | ||
192 | |||
193 | {{id name="Iimage-20220819093729-18.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_66ea9f304121cf6d.png||alt="image-20220819093729-18.png" height="762" width="1920"]] | ||
194 | |||
195 | **Device monitor** | ||
196 | |||
197 | Monitor the value of certain address in PLC, double click “Current value” to change the value in this address. | ||
198 | |||
199 | {{id name="Iimage-20220819093730-19.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ee6125099c14cb2b.png||alt="image-20220819093730-19.png" height="781" width="1920"]] | ||
200 | |||
201 | **Online monitor** | ||
202 | |||
203 | Monitor the each address in PLC by online monitor. Changing the state or value in PLC is also allowd. | ||
204 | |||
205 | {{id name="Iimage-20220819093730-20.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_21923412853b2626.png||alt="image-20220819093730-20.png" height="564" width="1607"]] | ||
206 | |||
207 | **Monitor edit** | ||
208 | |||
209 | In this mode, you could edit the PLC program during PLC is running. | ||
210 | |||
211 | {{id name="Iimage-20220819105928-9.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_9c0519bed3567723.png||alt="image-20220819105928-9.png" height="229" width="669"]] | ||
212 | |||
213 | == {{id name="HLX5VA0Series"/}}**LX5V Series** == | ||
214 | |||
215 | This example introduces the establishment of serial port communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring. | ||
216 | |||
217 | **Software configuration of PLC** | ||
218 | |||
219 | PLC programming software | ||
220 | |||
221 | {{id name="Iimage-20220810164710-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7599c2849074f02b.png||alt="image-20220810164710-1.png" height="326" width="424"]] | ||
222 | |||
223 | **New PLC project** | ||
224 | |||
225 | Click "New Project" and select the PLC model. | ||
226 | |||
227 | {{id name="Iimage-20220810172412-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d6bc182897bb2201.png||alt="image-20220810172412-1.png" height="898" width="1672"]] | ||
228 | |||
229 | **Set Serial port parameters** | ||
230 | |||
231 | Follow the steps below to configure Serial port parameters. | ||
232 | |||
233 | * Baud rate:115200 | ||
234 | * Data bit:8 | ||
235 | * Stop bit:1 | ||
236 | * Parity:No verification | ||
237 | |||
238 | {{id name="Iimage-20220810165759-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_6b7effc40ae03777.png||alt="image-20220810165759-3.png" height="1029" width="1920"]] | ||
239 | |||
240 | **Registers list** | ||
241 | |||
242 | {{id name="Iimage-20220811102219-3.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_eb0d8d9280761af1.png||alt="image-20220811102219-3.png" height="658" width="1226"]] | ||
243 | |||
244 | **HMI software configuration** | ||
245 | |||
246 | HMI programming software | ||
247 | |||
248 | {{id name="Iimage-20220810171237-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d127b46be5bf7497.png||alt="image-20220810171237-4.png" height="419" width="673"]] | ||
249 | |||
250 | **New HMI project** | ||
251 | |||
252 | Click New Project and select the HMI model. | ||
253 | |||
254 | {{id name="Iimage-20220810172010-5.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e73d0d6216dbf983.png||alt="image-20220810172010-5.png" height="912" width="1697"]] | ||
255 | |||
256 | Set communication port parameters | ||
257 | |||
258 | Click the communication configuration button on the left to find the communication protocol with LX5V. After selecting the protocol, configure the communication parameters of the COM port. | ||
259 | |||
260 | * Baud rate:115200 | ||
261 | * Data bit:8 | ||
262 | * Stop bit:1 | ||
263 | * Parity:No verification | ||
264 | |||
265 | {{id name="Iimage-20220811104012-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dac87f79e1471c71.png||alt="image-20220811104012-1.png" height="965" width="1383"]] | ||
266 | |||
267 | **hardware connection** | ||
268 | |||
269 | Hardware wiring diagram | ||
270 | |||
271 | This example introduces WeconHMI with LX5V PLC to establish communication through serial port. The connection diagram is as follows: | ||
272 | |||
273 | {{id name="Iimage-20220811103005-4.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dab0150e5cf17042.png||alt="image-20220811103005-4.png" height="150" width="681"]] | ||
274 | |||
275 | {{id name="Iimage-20220811103227-7.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d72bd5e65a0f052c.png||alt="image-20220811103227-7.png" height="209" width="342"]] | ||
276 | |||
277 | The above are all the steps for establishing serial port communication between Wecon HMI with LX5V PLC. | ||
278 | |||
279 | == {{id name="HLX5V-NEthernet"/}}**LX5V-N Ethernet** == | ||
280 | |||
281 | {{id name="cke_bm_147709S"/}} This example introduces the establishment of Ethernet communication between Wecon HMI and LX5V, including three parts: PLC software configuration, HMI software configuration, and hardware wiring. | ||
282 | |||
283 | **Software configuration of PLC** | ||
284 | |||
285 | **PLC programming software** | ||
286 | |||
287 | {{id name="Iimage-20220810164710-1.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_7599c2849074f02b.png||alt="image-20220810164710-1.png" height="326" width="424"]] | ||
288 | |||
289 | **New PLC project** | ||
290 | |||
291 | Click New Project and select the PLC model. | ||
292 | |||
293 | {{id name="Iimage-20220811115454-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_ff2c1cc959b53fdd.png||alt="image-20220811115454-1.png" height="930" width="1699"]] | ||
294 | |||
295 | **Set Ethernet port parameters** | ||
296 | |||
297 | Follow the steps below to configure Ethernet parameters | ||
298 | |||
299 | * PLC IP address:192.168.39.200 | ||
300 | * default gateway:192.168.39.1 | ||
301 | * subnet mask:255.255.255.0 | ||
302 | |||
303 | {{id name="Iimage-20220811140530-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_60404ed3c7204071.png||alt="image-20220811140530-2.png" height="1031" width="1920"]] | ||
304 | |||
305 | **Registers list** | ||
306 | |||
307 | {{id name="Iimage-20220811102219-3.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_eb0d8d9280761af1.png||alt="image-20220811102219-3.png" height="658" width="1226"]] | ||
308 | |||
309 | **HMI software configuration** | ||
310 | |||
311 | HMI programming software | ||
312 | |||
313 | {{id name="Iimage-20220810171237-4.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_d127b46be5bf7497.png||alt="image-20220810171237-4.png" height="419" width="673"]] | ||
314 | |||
315 | **New HMI project** | ||
316 | |||
317 | Click New Project and select the HMI model. | ||
318 | |||
319 | {{id name="Iimage-20220810172010-5.png-1"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_e73d0d6216dbf983.png||alt="image-20220810172010-5.png" height="912" width="1697"]] | ||
320 | |||
321 | **Set communication port parameters** | ||
322 | |||
323 | Click the project setting button on the left to configure the IP address of the HMI machine to ensure that the HMI and PLC IP remain in a local area network. | ||
324 | |||
325 | * HMI IP address:192.168.39.201 | ||
326 | * Default gateway:192.168.39.1 | ||
327 | * Subnet mask:255.255.255.0 | ||
328 | |||
329 | {{id name="Iimage-20220811170753-2.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_94717717b08e9074.png||alt="image-20220811170753-2.png" height="1008" width="1920"]] | ||
330 | |||
331 | Next, click Communication Settings to configure the IP of the HMI communication object. | ||
332 | |||
333 | {{id name="Iimage-20220811163047-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_291564bcc9db7b1b.png||alt="image-20220811163047-1.png" height="1030" width="1920"]] | ||
334 | |||
335 | **Hardware connection** | ||
336 | |||
337 | This example introduces WeconHMI with LX5V-N PLC to establish communication through ethernet. The connection diagram is as follows: | ||
338 | |||
339 | {{id name="Iimage-20220811170248-1.png"/}}[[image:xwiki_PIStudio_12.PLC+protocols_WebHome_dcab5cd2ecf22982.png||alt="image-20220811170248-1.png" height="199" width="779"]] | ||
340 | |||
341 | The above are all the steps for establishing ethernet communication between Wecon HMI with LX5V PLC. | ||
![]() |
38.3 | 342 | |
![]() |
42.1 | 343 | == **LX6V Ethernet** == |
344 | |||
![]() |
45.1 | 345 | **HMI Setting** |
346 | |||
347 | |=**Items**|=**Settings** | ||
![]() |
49.1 | 348 | |Protocol|WECON LX6V EtherNet/IP |
![]() |
45.1 | 349 | |Connection|Ethernet |
![]() |
46.1 | 350 | |Port No.|33818 |
351 | |Device No.|1 | ||
![]() |
45.1 | 352 | |HMI No.|0 |
353 | |||
![]() |
47.1 | 354 | **Tags support** |
355 | |||
356 | |=Data Type|=PIStudio Data Format | ||
357 | |=BOOL|Bit | ||
358 | |=BYTE|16-bit Unsigned/Binary/BCD/Hex | ||
359 | |=WORD|16-bit Unsigned/Binary/BCD/Hex | ||
360 | |=DWORD|32-bit Unsigned/Binary/BCD/Hex | ||
361 | |=LWORD|64-bit Signed/Binary/BCD/Hex | ||
362 | |=SINT|16-bit Signed/Binary/BCD/Hex | ||
363 | |=USINT|16-bit Unsigned/Binary/BCD/Hex | ||
364 | |=INT|16-bit Signed/Binary/BCD/Hex | ||
365 | |=UINT|16-bit Unsigned/Binary/BCD/Hex | ||
366 | |=DINT|32-bit Signed/Binary/BCD/Hex | ||
367 | |=UDINT|32-bit Unsigned/Binary/BCD/Hex | ||
368 | |=LINT|64-bit Signed/Binary/BCD/Hex | ||
369 | |=REAL|32-bit Float | ||
370 | |=LREAL|64-bit Float | ||
371 | |||
![]() |
43.1 | 372 | **PLC Setting** |
![]() |
42.1 | 373 | |
374 | PLC programmer software | ||
375 | |||
376 | (% style="text-align:center" %) | ||
377 | [[image:1726822663840-435.png]] | ||
378 | |||
379 | Create and Export the Freetags | ||
380 | |||
![]() |
43.1 | 381 | **①**[Program]→[Global variable]→[GVL]→Create the Freetags you need,notice the Category and Type of data |
382 | |||
383 | (% class="box infomessage" %) | ||
384 | ((( | ||
385 | **✎**Note: Only global variables can be exported normally | ||
386 | ))) | ||
387 | |||
388 | (% style="text-align:center" %) | ||
![]() |
48.1 | 389 | [[image:图片2.png||height="537" width="988"]] |
![]() |
43.1 | 390 | |
![]() |
48.1 | 391 | **②**[File]→[Export label] |
![]() |
43.1 | 392 | |
393 | (% style="text-align:center" %) | ||
![]() |
48.1 | 394 | [[image:图片3.png||height="535" width="987"]] |
![]() |
43.1 | 395 | |
![]() |
48.1 | 396 | **③**Set the Name and Type→[Save]→[OK] |
![]() |
43.1 | 397 | |
398 | (% style="text-align:center" %) | ||
![]() |
48.1 | 399 | [[image:图片4.png||height="529" width="974"]] |
![]() |
43.1 | 400 | |
401 | **HMI Setting ** | ||
![]() |
47.1 | 402 | |
![]() |
50.1 | 403 | Tags import |
![]() |
47.1 | 404 | |
405 | [Labels manage]→[Import Tags From File]→Choose the .CSV file you need→[Open]→[Save]→[OK] | ||
406 | |||
407 | (% style="text-align:center" %) | ||
![]() |
48.1 | 408 | [[image:图片1.png||height="530" width="978"]] |