Wiki source code of R Series

Version 66.1 by Mora Zhou on 2024/12/05 14:29

Hide last authors
Mora Zhou 62.1 1 == **Product description** ==
Mora Zhou 2.1 2
Mora Zhou 43.2 3 |**Series**|(% style="width:132px" %)**Model**|(% style="width:552px" %)**Description**
4 |(% rowspan="3" %)**R Series**|(% style="width:132px" %)RE-00|(% style="width:552px" %)1 network port, single serial port
5 |(% style="width:132px" %)RE-4G|(% style="width:552px" %)1 network port, single serial port, support 4G.
6 |(% style="width:132px" %)RH-WF|(% style="width:552px" %)(((
Mora Zhou 2.1 7 2 network ports, 1 HDMI interface, single serial port, 2 RS485 terminals, support WiFi
8
Mora Zhou 43.1 9 2 optocoupler isolated input (DI), 2 relay output (DO)
Mora Zhou 2.1 10 )))
11
Mora Zhou 62.1 12 === **Product appearance** ===
Mora Zhou 2.1 13
Joe 51.1 14 ==== **RE-00/RE-4G** ====
Mora Zhou 2.1 15
Mora Zhou 61.1 16 (% style="text-align:center" %)
Mora Zhou 43.2 17 [[image:1723447082795-273.png]]
Mora Zhou 2.1 18
19 RE-00/RE-4G Appearance
20
Mora Zhou 61.1 21 (% style="text-align:center" %)
Mora Zhou 43.2 22 [[image:1723447096815-592.png]]
Mora Zhou 2.1 23
24 RE-00/RE-4G Installation Dimensions
25
Joe 51.1 26 ==== **RH-WF** ====
Mora Zhou 2.1 27
Mora Zhou 61.1 28 (% style="text-align:center" %)
Mora Zhou 2.1 29 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_2faa2eeb.gif||alt="Shape1" height="316" width="464"]]
30
31 (((
32 **WiFi antenna**
33 )))
34
35 RH-WF
36
Mora Zhou 61.1 37 (% style="text-align:center" %)
Mora Zhou 2.1 38 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_99c3a18c.png||height="259" width="638"]]
39
Mora Zhou 43.2 40 Installation size
Mora Zhou 2.1 41
42
Mora Zhou 62.1 43 === **Product specifications** ===
Mora Zhou 2.1 44
45 (((
Mora Zhou 61.1 46 (% style="width:1075px" %)
Mora Zhou 43.2 47 |=(% colspan="3" %)**Model/Specifications**|=**RE-00**|=**RE-4G**|=**RH-WF**
Mora Zhou 2.1 48 |(% colspan="3" %)**Item**|(% colspan="3" %)**Parameters**
49 |(% colspan="3" %)CPU|(% colspan="2" %)Cortex-A35 4-Core 1.2GHz|Cortex A55 4-Core 1.8GHz
50 |(% rowspan="3" %)Memory|(% colspan="2" %)Flash|(% colspan="2" %)128MB|8GB
51 |(% colspan="2" %)RAM|(% colspan="2" %)DDRII 64MB|2GB
52 |(% colspan="2" %)SD Card|(% colspan="2" %)N/A|TF card
53 |(% rowspan="8" %)(((
54 I/O
55
56 Interface
57 )))|(% colspan="2" %)USB HOST|(% colspan="2" %)1, no isolation|(((
58 USB 2.0*1 No isolation
59
60 USB 3.0*1 No isolation
61 )))
62 |(% colspan="2" %)USB DEVICE|(% colspan="2" %)1, no isolation|Type-C*1
63 |(% colspan="2" %)Serial port|(% colspan="2" %)COM1: RS232, RS422/RS485|(((
64 COM1: RS232, RS422/RS485 (2 in 1)
65
66 1 expansion serial port (terminal line)
67
68 [COM2: RS485]
69 )))
70 |(% colspan="2" %)Ethernet port|(% colspan="2" %)1|10/100M Interface*2
71 |(% colspan="2" %)WIFI module|(% colspan="2" %)N/A|Yes
72 |(% colspan="2" %)4G module|N/A|4G|N/A
73 |(% colspan="2" %)HDMI|(% colspan="2" %)N/A|HDMI 2.0*1
74 |(% colspan="2" %)I/O|(% colspan="2" %)N/A|2-channel relay output, 2-channel isolated input with optocoupler
75 |(% rowspan="2" %)Power supply|(% colspan="2" %)Input power supply|(% colspan="3" %)24V DC (12-28V DC)
76 |(% colspan="2" %)Power consumption|(% colspan="3" %)<10W
77 |(% rowspan="4" %)Specifications|(% colspan="2" %)Shell material|(% colspan="2" %)Cold rolled sheet|Engineering-plastics PC+AB5 (Flame retardant level)
78 |(% colspan="2" %)Dimensions (W*H*D)|(% colspan="2" %)101.0*73.2*26.8mm|125.0*93.7*51.0 mm
79 |(% colspan="2" %)Wall mounting hole dimensions|(% colspan="2" %)110.0*15.6 mm|/(Fastener mounting)
80 |(% colspan="2" %)Weight|(% colspan="2" %)0.26Kg|253g
81 |(% rowspan="4" %)(((
82 Operation
83
84 Environment
85 )))|(% colspan="2" %)Vibration resistance|(% colspan="3" %)Compile with IEC61131-2 standard
86 |(% colspan="2" %)Storage temperature|(% colspan="3" %)-20℃-70℃
87 |(% colspan="2" %)Working temperature|(% colspan="3" %)-10℃-60℃
88 |(% colspan="2" %)Ambient humidity|(% colspan="3" %)10-90% RH (No condensation)
89 |(% colspan="3" %)CE certification|(% colspan="3" %)Yes
90 |(% colspan="3" %)FCC certification|(% colspan="3" %)FCC Class A Certification
Mora Zhou 61.1 91 |(% colspan="3" style="width:401px" %)Positioning function|(% colspan="2" style="width:401px" %)N/A  /  Base station positioning|(% style="width:401px" %)N/A
Mora Zhou 2.1 92 |(% rowspan="7" %)(((
93 Software
94
95 function
96 )))|(% colspan="2" rowspan="4" %)(((
97 Internet of Things Services
98
99 (Optional)
100 )))|(% colspan="2" %)100 real-time data tags|300 real-time data tags
101 |(% colspan="2" %)20 alarm data tags|200 alarm data tags
102 |(% colspan="2" %)50 historical data tags|100 historical data tags
103 |(% colspan="3" %)Days of historical data saved: 60 days/1 million
104 |(% colspan="2" %)Pass through|(% colspan="3" %)Yes
105 |(% colspan="2" %)VPN Pass trough|(% colspan="3" %)Yes
106 |(% colspan="2" %)API interface|(% colspan="3" %)Yes
107
Mora Zhou 62.1 108 === **Interface Description** ===
Mora Zhou 2.1 109 )))
110
Mora Zhou 46.1 111 ==== **Appearance component description** ====
Mora Zhou 2.1 112
Mora Zhou 43.2 113 **RE-00/RE-4G**
Mora Zhou 2.1 114
Mora Zhou 61.1 115 (% style="text-align:center" %)
Mora Zhou 43.2 116 [[image:1723448311561-814.png]]
Mora Zhou 2.1 117
118 RE-00/RE-4G Component Description
119
120
121 |**1**|Indicator lamp|**2**|Micro-USB|**3**|Ethernet port|**4**|COM port
122 |**5**|Power supply|**6**|4G antenna (Optional)|**7**|Fixed fastener|**8**|SIM card (Optional)
123
Mora Zhou 44.1 124 **RH-WF**
Mora Zhou 2.1 125
Mora Zhou 64.1 126 (% style="text-align:center" %)
Mora Zhou 43.2 127 [[image:1723448356737-113.png]]
Mora Zhou 2.1 128
129 RH-WF Component Description
130
131 |**1**|Indicator lamp|**2**|USB-A|**3**|Network Port 1|**4**|Network Port 2
132 |**5**|HDMI|**6**|TYPE-C|**7**|COM port|**8**|I/O interface and RS485 terminal
Mora Zhou 41.2 133 |**9**|Power supply|**10**|WIFI antenna|**11**|Fixed fastener| |
Mora Zhou 2.1 134
Mora Zhou 46.1 135 ==== **Interface Description** ====
Mora Zhou 2.1 136
Mora Zhou 45.1 137 **RE-00/RE-4G**
Mora Zhou 2.1 138
139 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_d215ad34.png||height="276" width="616"]]
140
141
142 **RH-WF**
143
Mora Zhou 45.1 144 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_d48f58ee.png||height="240" width="488"]]
Mora Zhou 2.1 145
Mora Zhou 46.1 146 ==== **Interface Definition** ====
Mora Zhou 2.1 147
Mora Zhou 46.1 148 **RE-00/RE-4G COM1 interface definition**
Mora Zhou 2.1 149
150 |**Pin**|**Definition**|**Pin**|**Definition**
151 |1|RS422 TX+/RS485 A+|2|RS232 RXD
152 |3|RS232 TXD|5|GND
153 |6|RS422 TX-/RS485 B-|8|RS422 RX-
Mora Zhou 41.2 154 |9|RS422 RX+| |
Mora Zhou 2.1 155
Joe 47.1 156 **RH-WF**
Mora Zhou 2.1 157
158 |(% colspan="2" %)**Pin**|**Definition**
159 |(% rowspan="7" %)[[image:Wecon V-BOX R Series User Manual 240611 V1.2_ef6a7104.gif||height="205" width="93"]]|S/S|(((
160 Input mode selection terminal.
161
Mora Zhou 41.2 162 Connecting to 24V+ indicates that it supports** NPN** input;
Mora Zhou 2.1 163
164 Connecting to 24V- indicates that it supports **PNP** input.
165 )))
166 |Xn|Switch quantity input terminal
167 |Yn|Switch quantity signal output terminal, relay output
168 |COM|Output common port
169 |485+|RS485+
170 |485-|RS485-
171 |GND|Ground
172
Mora Zhou 62.1 173 == **Applications** ==
Mora Zhou 2.1 174
Joe 59.2 175 === Basic application ===
176
Mora Zhou 43.2 177 R series products, which can easily realize advanced requirements such as real-time display on industrial sites.
Mora Zhou 2.1 178
Mora Zhou 63.1 179 (% style="text-align:center" %)
Mora Zhou 42.1 180 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_ab54a2bc.png||height="304" width="631"]]
Mora Zhou 2.1 181
182 ① Large-screen display, connect computer/TV Display the project screen;
183
184 ② Network port device, connect to network device such as slave computers, and download projects online through configuration software;
185
186 ③ Serial port device, connect to the serial port device of the slave computer, and the project can also be downloaded online through the configuration software.
187
Joe 59.2 188
189 === RH-WF and WS21 ===
190
Joe 59.4 191 RH-WF supports local HDMI interface to connect to in-site screen like a TV screen to display the project. WS21, a touching screen, can be connected with RH-WF via HDMI interface. The project an be operated manually in WS21 screen.
Joe 59.2 192
Joe 59.3 193 (% style="text-align:center" %)
194 [[image:图片1.png]]
195
196 (% style="text-align:center" %)
197 [[image:图片2.png]]
198
199 HDMI Port is for displaying the project. And USB Port is for touching.
200
Joe 60.1 201 [[WS21 parameter>>https://ftp.we-con.com.cn/Download/WIKI/%E9%9B%9C%E9%A0%85/Wecon%20WS21%20Monitor.pdf]]
Joe 59.3 202
Joe 60.1 203 [[Demo video>>https://ftp.we-con.com.cn/Download/WIKI/%E9%9B%9C%E9%A0%85/RH1.mp4]]
204
Mora Zhou 62.1 205 == **Operation Instructions** ==
Mora Zhou 2.1 206
Mora Zhou 62.1 207 === **Project Download-PIStudio** ===
Mora Zhou 2.1 208
209 **(1) New project**
210
211 PIStudio→[Home]→[New Project]→[Project Properties], and set the project name and [HMI model] in step by step: RE, RH series, select the detailed HMI model → [Screen style]: use the default do not set→[Done].
212
Mora Zhou 65.1 213 (% style="text-align:center" %)
Mora Zhou 2.1 214 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_8971673d.png||height="340" width="638"]]
215
216 **(2) Enable cloud server**
217
218 **Configuration of V-NET IoT System**
219
220 **It needs to check "Enable Cloud" function in order to view "Remote Monitoring" screen in V-NET, and configure the functions of tags, data recording on the cloud, and alarm recording on the cloud.**
221
222 Upload to the cloud: All configured tag information, historical information, and alarm information will be pushed to V-NET.
223
224
Mora Zhou 65.1 225 (% style="text-align:center" %)
Mora Zhou 2.1 226 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_19762229.png||height="360" width="638"]]
227
228 **(3) Project compile/download**
229
Mora Zhou 41.2 230 After the project is completed, click **[Project Compile]**→After prompting that the compilation is completed, click** [Download Project]**→device detected, **[PC port]**. Ethernet or USB download→[PC→HMI]→pop up a prompt, click **[OK]** → complete the configuration project download, it will take effect after restart.
Mora Zhou 2.1 231
Mora Zhou 65.1 232 (% style="text-align:center" %)
Mora Zhou 2.1 233 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_38834748.png||height="340" width="634"]]
234
Mora Zhou 65.1 235 (% style="text-align:center" %)
Mora Zhou 2.1 236 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_31fafd4e.png||height="287" width="348"]]
237
238 **Note: “Flash light" in the picture is the flashing light of the detection device; "Test network" in the figure refers to the network status of the test device.**
239
Mora Zhou 62.1 240 === **Check V-NET IoT System** ===
Mora Zhou 2.1 241
Mora Zhou 62.1 242 ==== **V-NET login** ====
Mora Zhou 2.1 243
244 (1) New users must register first, and after the registration is successful, the user can use it.
245
246 ● A successfully registered account is an administrator account, which can bind the device and support other operations.
247
248 ● Users need to remember the registered account and password, and can log in simultaneously on the PC/APP.
249
Mora Zhou 65.1 250 (% style="text-align:center" %)
Mora Zhou 2.1 251 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_7103ee91.png||height="274" width="453"]]
252
253 (2) Enter the account and password, and then click the **[Log in] **button.
254
255 (3) After admin account logs in to the platform, it will jump to the homepage by default, as shown in the figure below.
256
Mora Zhou 65.1 257 (% style="text-align:center" %)
Mora Zhou 2.1 258 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_59ff7f12.png||height="357" width="598"]]
259
Mora Zhou 62.1 260 ==== **Adding devices** ====
Mora Zhou 2.1 261
Mora Zhou 41.2 262 (1) After successfully logging in, enter the** [Device Management]** interface, and add the device information to be accessed through the “+” button in the bar.
Mora Zhou 2.1 263
Mora Zhou 65.1 264 (% style="text-align:center" %)
Mora Zhou 2.1 265 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_45c9855a.png||height="409" width="638"]]
266
267 (2) After the **[Add Device]** window pops up, enter the device machine code and password, etc., and add the device. Other instructions are as follows:   
268
269 ① **Device machine code:** Each device has a unique and independent machine code for remote monitoring device identification.     
270
271 Obtain machine code:
272
273 ● HMI PIStudio-**[Tool]**-**[Download project]**-Machine code.
274
275 ● Scan the QR code of the device to obtain the machine code.
276
277 ② **Device password:** Refers to the cloud access password, the default is 888888. The initial binding device password: see [[Cloud Configuration>>path:mk:@MSITStore:E:%5C%5CA%E6%97%A5%E5%B8%B8%E5%B7%A5%E4%BD%9C%E6%96%87%E4%BB%B6%5C%5C2023-06-15PI%E5%B8%AE%E5%8A%A9%E6%89%8B%E5%86%8C%5C%5C%E4%B8%AD%E6%80%A7%E7%89%8820231016%EF%BC%88%E6%A0%87%E5%87%86%EF%BC%89%5C%5Chelp20231020.chm::/levi%E2%85%A1/5/5.9.htm]].
278
279 ③ **Device alias:** Refers to the name recognition of the device in the menu bar of V-NET.
280
281 (3) Binding device is successful, click OK, prompt: Bind device successful!
282
Mora Zhou 62.1 283 ==== **V-NET check** ====
Mora Zhou 2.1 284
285 **(1) Remote monitoring**
286
287 The remote monitoring module can display the current screen in real time, and realize the operation of the project on the web page, realize the remote monitoring of the device and the control of the screen.
288
Mora Zhou 65.1 289 (% style="text-align:center" %)
Mora Zhou 2.1 290 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a262a004.png||height="362" width="638"]]
291
292 **(2) Data viewing**
293
294 Data view has six modules, including Communication port, Collection point, Alarm configuration, Alarm record, Historical configuration, Historical data record.
295
Mora Zhou 65.1 296 (% style="text-align:center" %)
Mora Zhou 2.1 297 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_6ce8af63.png||height="357" width="638"]]
298
299 **The specific parameter is as follows:**
300
301 ① **Communication port:** The communication port information, connection mode and protocol name configured on HMI. It can only be viewed, and cannot be added or modified. The information comes from what is set on HMI.
302
303 ② **Collection point**: Data monitoring module. The collection point is the tag, and its read-write, write-only, and read-only permissions also come from the tags set in PIStudio. (**Note: Tags cannot be added or removed here.**)
304
305 ③ **Alarm message:** For the alarm record of the device, tags cannot be added. Operations such as confirming the alarm record and exporting data can be performed.
306
307 ④ **Historical information:** The historical data of the device cannot add tag, supports curve and list viewing, and supports export historical data and other operations.
308
309 **(3) Cloud configuration**
310
311 The cloud SCADA platform is mainly used to display the monitoring/operation interface of the bound device in the V-NET.
312
Mora Zhou 65.1 313 (% style="text-align:center" %)
Mora Zhou 2.1 314 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_8ecdd915.png||height="332" width="638"]]
315
316 The main functions of Cloud SCADA interface in device management are as follows:
317
318 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_3c59fa4c.png||height="21" width="19"]] Refresh the current Cloud SCADA project.
319
320 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_56dc36ee.png||height="20" width="19"]] Browse the current Cloud SCADA project in full screen (Press “Esc” exit).
321
322 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_23075dbb.png||height="19" width="19"]] Switch the bound Cloud SCADA projects (The cloud SCADA projects bound in current device and cross-device).
323
324 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_1ced925.png||height="19" width="19"]] Edit the current cloud SCADA (jump to the Cloud SCADA edit page)
325
326
327 **(4) Basic information**
328
329 Include: "Basic information, status push, register information, version information" for the device.
330
Mora Zhou 65.1 331 (% style="text-align:center" %)
Mora Zhou 2.1 332 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_b1d4b150.png||height="330" width="638"]]
333
334 ●**Device name:** Mainly used to distinguish various devices.
335
336 ●**Online status**: Use the refresh function to refresh the online status of the device.
337
338 ●**Machine code:** Each device has a unique and independent machine code.
339
340 ●**Map Information:** The latitude and longitude information of the device, click “Location” to view the geographical location and modify the location information.
341
342 ●**Located with:**
343
344 ① Use device base station positioning.        
345
346 ②Use manual positioning.
347
Mora Zhou 43.3 348 **Note: After modifying the basic information of the device, you need to click Save below to save successfully. If the save is not successful, please click Force Sync.**
Mora Zhou 2.1 349
Mora Zhou 62.1 350 == **Pass-through of device** ==
Mora Zhou 2.1 351
Mora Zhou 43.3 352 **Note: The pass-through operation steps of V-NET/V-IEC are for reference only.**
Mora Zhou 2.1 353
354 Pass-through function: The pass-through function allows applications on the computer to increase maintenance value through RE devices, remote pass-through devices, download projects, etc.
355
Mora Zhou 66.1 356 (% style="text-align:center" %)
Mora Zhou 2.1 357 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_1c4453d8.png||height="338" width="638"]]
358
359 Device status description table is as follows:
360
Mora Zhou 43.3 361 |(% style="width:82px" %)**Color**|(% style="width:248px" %)**Color Value (HEX)**|**Status**|**Description**
362 |(% style="width:82px" %)[[image:1723449592784-532.png]]|(% style="width:248px" %)#18E600|Online|Pass-through available
363 |(% style="width:82px" %)[[image:1723449624928-809.png]]|(% style="width:248px" %)#B5C1D8|Offline|Pass-through is not allowed
364 |(% style="width:82px" %)[[image:1723449706265-533.png]]|(% style="width:248px" %)#1C9BFD|Pass-through connecting|In pass-through
365 |(% style="width:82px" %)[[image:1723449737329-134.png||height="28" width="31"]]|(% style="width:248px" %)#005CFF|VPN connecting|In pass-through
366 |(% style="width:82px" %)[[image:1723449765210-888.png]]|(% style="width:248px" %)#FD8B09|VPN pass-through is reconnecting|Pass-through reconnecting due to network and other reasons
367 |(% style="width:82px" %)[[image:1723449785743-305.png||height="28" width="32"]]|(% style="width:248px" %)#2C405E|VPN pass-through is ending|The end of pass-through due to [End pass-through]
368 |(% style="width:82px" %)[[image:1723449827434-119.png]]|(% style="width:248px" %)#109A00|Download is ready.|Download channel is ready. (Download can be executed.)
369 |(% style="width:82px" %)[[image:1723449809049-353.png]]|(% style="width:248px" %)#009577|Download|In download
Mora Zhou 2.1 370
371 **Pass-through precautions:**
372
373 ● The web cannot use the pass-through function for the time being, and it needs to be in the PC client to change the location.
374
375 ● When the device is offline, “Start pass-through” cannot be clicked.
376
377 ● When the device firmware version is too low, “Start pass-through” cannot be clicked.
378
379 ● The current user does not have pass-through rights on this device or this device is shared by others, and “Start pass-through” cannot be clicked.
380
381 ● When the current user has a device in pass-through, “Start pass-through” cannot be clicked.
382
383
Mora Zhou 62.1 384 === **Device pass-through download (RE)** ===
Mora Zhou 2.1 385
386 The pass-through function allows applications on the computer to download projects to RE device remotely pass-through through Ethernet.
387
388 **Steps:**
389
390 ① Click [[image:Wecon V-BOX R Series User Manual 240611 V1.2_f1b46bca.png||height="16" width="17"]] to enter the pass-through interface.
391
392 ② Select the device that needs pass-through, and ensure that the device is online.
393
394 ③ Click "Browse" to automatically detect the installed download tools on this machine. The table shows the versions and locations of all installed download tools. (HMI software should be installed in the computer to ensure that HMIEditor and download tools exist at the same time).
395
396 ④ Select any HMI download tool configuration in the table, and confirm the selected HMIEditor software through the folder location and corresponding version information.
397
398 ⑤ Pass-through is ready → [Start pass-through].
399
400 ●Click "Start pass-through" to conduct pass-through according to the specified download tools and selected devices.
401
Mora Zhou 43.4 402 ●Click [End pass-through] to end pass-through.
Mora Zhou 2.1 403
404 ⑥ After pass-through is successful, pop up the download tool box, select [PC->HMI], select the compiled .wmt3 file, and download the program.
405
Mora Zhou 66.1 406 (% style="text-align:center" %)
Mora Zhou 2.1 407 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_221b5f45.png||height="338" width="638"]]
408
Mora Zhou 62.1 409 === **Common serial port pass-through (PLC)** ===
Mora Zhou 2.1 410
411 Based on the normal communication between RE device and PLC or other device, PLC is connected according to the generated virtual serial port, allowing the PLC software on the computer to communicate and connect with the PLC, and completing the functions of uploading/downloading PLC programs and monitoring PLC programs.
412
413 **Steps:**
414
Mora Zhou 41.2 415 ① Virtual serial port settings: Click** [Settings]** →**[Virtual Serial Port]**→**[Enable Virtual Serial Port] **→**[Select Serial Port]**. Pay attention to the serial port, please do not reuse it. (When the COM port is changed, if a PLC or other software is connecting to the original COM port, it will be disconnected.)
Mora Zhou 2.1 416
Mora Zhou 66.1 417 (% style="text-align:center" %)
Mora Zhou 2.1 418 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_54a850e2.png||height="136" width="639"]]
419
420 ② Remote download configuration: Click [PLC pass-through ][[image:Wecon V-BOX R Series User Manual 240611 V1.2_cfc415e2.png||height="14" width="15"]] →Select the device that requires pass-through→[New/Edit]→[New Template] Configure pass-through parameters: [Name], [Communication Port], [Connection Method], [Baud Rate], [Stop Bit], [Data Bit], [Check Bit], the configured parameters need to be consistent with the PLC serial port parameters →[OK]→Prompt "Add successfully!"→[OK].
421
Mora Zhou 66.1 422 (% style="text-align:center" %)
Mora Zhou 2.1 423 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_353545eb.png||height="339" width="638"]]
424
425 ③ Pass-through steps: On the pass-through interface, click [Start pass-through]→after successful pass-through, it will prompt "pass-through succeeded"→[OK].
426
Mora Zhou 66.1 427 (% style="text-align:center" %)
Mora Zhou 2.1 428 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_5b5ad7dd.png||height="339" width="638"]]
429
430 ④ After the pass-through is successful, the indicator light of the corresponding RE device on the PC will turn blue, and the [current status] will become pass-through, indicating that the device is in the "pass-through" status.
431
432 ✎**Note:** Do not click [End pass-through], otherwise you will exit the pass-through function.
433
434
435
Mora Zhou 43.4 436 ⑤End pass-through: When the PLC software completes the remote operation, select [End pass-through]→Prompt "End pass-through successfully"→[OK], at this time the device will automatically restart. After the restart is completed, the working status before pass-through will be restored.
Mora Zhou 2.1 437
Mora Zhou 66.1 438 (% style="text-align:center" %)
Mora Zhou 2.1 439 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_c6ec3cf0.png||height="337" width="638"]]
440
Mora Zhou 44.1 441 **Pass-through Precautions:**
Mora Zhou 2.1 442
443 ① In the process of PLC software remote access, the pass-through serial port of the RE device needs to maintain a normal communication state, and the network state needs to remain stable.
444
445 ② When the device is in the pass-through, COM indicator light will be in the off status. When the device ends the pass-through, it will automatically restart.
446
447 ③ The parameters of the PLC connection need to be consistent with the parameters generated by the virtual serial port.
448
449 ④ It is necessary to ensure that the PLC serial port of pass-through can support the upload/download function, otherwise the remote pass-through function cannot be realized.
450
Mora Zhou 62.1 451 === **VPN pass-through (PLC)** ===
Mora Zhou 2.1 452
453 **VPN pass-through:** The pass-through function allows the application program on the computer to directly control the PLC device through the RE device, upload/download PLC programs, monitor PLC programs or other configuration information, etc.
454
455 **Steps:**
456
Mora Zhou 44.1 457 ① Click [VPN pass-through] [[image:1723450415577-521.png]]→Select the device that requires pass-through →[Local pass-through IP]→[Automatic acquisition/manual setting]→[Manual setting] 192.168.40.23 (Manual IP setting needs to ensure that it is on the same network segment as the RE device and device IP)→[Start pass-through]→Prompt "Pass-through succeeded"→[OK].
Mora Zhou 2.1 458
Mora Zhou 66.1 459 (% style="text-align:center" %)
460 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a4500d0f.png]]
Mora Zhou 2.1 461
462 ② After pass-through is successful, the indicator light of the corresponding RE device on the PC will turn yellow, and [current status] will become in the VPN pass-through, indicating that the device is in the "pass-through" status. (**Note:** You cannot click [End pass-through], otherwise you will exit the pass-through.)
463
464 ③ After the pass-through is successful, a virtual network card will be generated. You can check whether the IP is generated through the network card of the computer, as shown below.
465
Mora Zhou 66.1 466 (% style="text-align:center" %)
Mora Zhou 2.1 467 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_a53a8121.png||height="336" width="638"]]
468
469 ④ When PLC software completes the remote operation, select [End pass-through]→Prompt "End VPN pass through successfully"→[OK], at this time the device will automatically restart, and after the restart is completed, the working status before pass-through will be restored.
470
Mora Zhou 66.1 471 (% style="text-align:center" %)
Mora Zhou 2.1 472 [[image:Wecon V-BOX R Series User Manual 240611 V1.2_40416c98.png||height="336" width="638"]]
473
474 **Pass-through precautions:**
475
476 ① The Ethernet port IP of RE device, the IP used by the VPN pass-through, and the IP of the PLC must be kept in the same network segment without conflict.
477
478 ② The IP connected to the PLC needs to be consistent with the IP of the PLC itself.
479
480 ③ When the device ends the pass-through function, RE device will automatically restart.
481
482 ④ If the VPN pass-through is unsuccessful, please refer to the "Frequently Asked Questions of Wecon VPN pass-through Tools" for troubleshooting.
483
484 The file path is as follows:
485
Joe 47.1 486 [[https:~~/~~/www.we-con.com.cn/uploads/image/20210811/611392100b634.pdf>>https://www.we-con.com.cn/uploads/image/20210811/611392100b634.pdf]]
487
Mora Zhou 62.1 488 == Resumable upload ==
Joe 47.1 489
490 3000ig/8000ig HMI and RE/RH,E/H V-BOX can support  a function for resumable upload. The function is to save lost data when the device is offline and upload lost data to Cloud when the device is online again.
491
492 The following table shows the maximum number of the resumable data and the biggest file size of the resumable data:
493
494 |= |=RE/RH|=3000ig/8000ig HMI|=E/H V-BOX
495 |=data|100,000|100,000|2,000
496 |=file size|2M|2M|N/A
497
498 (% class="box infomessage" %)
499 (((
Joe 50.1 500 Note:
Joe 47.1 501
Joe 50.1 502 1.The function don't configure by manual.
503
Joe 47.1 504 2.When the device is online again, There is a keep-alive interval for about 30s. So data will be lost during the time.
505 )))
506
Mora Zhou 62.1 507 == Remote Background ==
Joe 53.1 508
509 R series box doesn’t have the actual screen, so a new remote page is designed for background setting if user want to change some background parameters.
510
511 (% class="box infomessage" %)
512 (((
513 Note: HMI of V3.0 version also supports this function.
514 )))
515
516 === Enter remote background ===
517
518
519 Keep R series/HMI and pc in the same Lan. Input "IP:9091" in pc webpage.
520
521 (% style="text-align:center" %)
522 [[image:TYyajNRreA.png]]
523
524 There will be a User login screen and input Account and Password.
525
526 (% style="text-align:center" %)
527 [[image:zt10uj9hHA.png]]
528
529 (% class="box infomessage" %)
530 (((
531 Note: The default Account is "admin". The default Password is "888888".
532 )))
533
534 === Modify account and password ===
535
536 Project Settings → Security→ LAN Monitoring Security→ OK → Compile and Download the project
537
538 (% style="text-align:center" %)
539 [[image:rDTHQo0uzs.png]]
540
Mora Zhou 62.1 541 == Centralized Monitor ==
Joe 56.1 542
Joe 57.1 543 In HMI V3.0 version, there will be a Device management tool for centralized monitoring Local and Cloud device. When HMIs and PC are in the same LAN, they can be selected for centralized monitor.
Joe 56.1 544
Joe 57.1 545 (% class="box infomessage" %)
546 (((
Joe 59.1 547 Note: Centralized Monitor can not be accomplished by connection that HMIs are connected to PC with USB.
Joe 57.1 548 )))
549
Joe 56.1 550 === Local Device ===
551
Joe 58.1 552 Download → choose monitored HMIs
Joe 56.1 553
554 (% style="text-align:center" %)
555 [[image:1yeIHMWarO.png]]
556
557 === Cloud Device ===
558
559 Cloud Linker →log in → select the server in configuration→ log in V-net Client account
560
561 (% style="text-align:center" %)
562 [[image:DTQ10E5Cv6.png]]
563
564 (% style="text-align:center" %)
565 [[image:IPJDUDCzD4.png]]
566
Joe 58.1 567 After logging in the account, select monitored HMIs.
Joe 56.1 568
569 (% style="text-align:center" %)
570 [[image:y6AlyJtG24.png]]
571
Joe 57.1 572 In Centralized monitor screen, selected HMI project will be display here. What's more, these projects can be operated in the screen.
Joe 56.1 573
574 (% style="text-align:center" %)