... ... @@ -21,13 +21,13 @@
21 21  The input and output of PLC is the main function of use, and I/O point problems are often caused by improper use or process\individual device problems; Including how the customer uses it, whether the mount is in compliance, etc. are all causes that lead to I/O failures .
22 22  
23 23  (% class="table-bordered" %)
24 -|**Number**|**Failure**|**Troubleshooting**|**Solution**
25 -|1|(((
24 +|**Number**|(% style="width:124px" %)**Failure**|(% style="width:747px" %)**Troubleshooting**|**Solution**
25 +|1|(% style="width:124px" %)(((
26 26  X point failure
27 -)))|1. Use PLC software to detect X points that cannot be lit;
27 +)))|(% style="width:747px" %)1. Use PLC software to detect X points that cannot be lit;
28 28  2. Connect PLC S/S to 24V, change multimeter to 20mA gear. The red test lead is on the X point of the fault, and the black test lead is on a Y point (the COMx corresponding to Y is connected to the COM terminal of the 24V voltage);
29 29  3.Use PLC software to control the on-off of the Y point(connected in step2) to check whether there is current on the multimeter. The high-speed input current is about 6.8mA, and the low-speed input current is about 4.7mA.|If no voltage is detected, the motherboard needs to be replaced for confirmation.
30 -|2|Y point failure|1. All COMx of PLC are connected to COM;
30 +|2|(% style="width:124px" %)Y point failure|(% style="width:747px" %)1. All COMx of PLC are connected to COM;
31 31  2. Power on the PLC, use the buzzer of the multimeter, pen one test lead on COM, and the other on the Y that needs to be detected, and observe whether the buzzer sounds when the lamp board Y is not lit. ;|The normal situation is that the buzzer will beep when Y is turned on, and there will be no buzzer when it is turned off, or the Y point needs to be replaced.
32 32  
33 33  = **3. Communication failure** =