... ... @@ -55,3 +55,6 @@
55 55  2. Control variables to determine whether it is a module problem or a host problem;
56 56  3. If the communication is abnormal due to the host, replace the upper board and the CORE board respectively to confirm;
57 57  4. If it is the module that causes the communication abnormality, it needs to be analyzed and checked separately;
58 +|=6|RUN and ERR flash in same frequency|1. Unstable power supply
59 +2. Firmware issue|1. Measure the power input and ensure that the power supply is stable.
60 +2. Replace the core board(middle board) and check.