Stone Wu 11.1 1 = 1 Safety =
Stone Wu 10.1 2
Stone Wu 7.1 3 Before installation, operation, maintenance, or inspection of this product, thoroughly read through and understand this manual and all of the associated manuals. Also, take care to handle the module properly and safely.
4
5 = 2 Design =
6
7 Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure.
8
9 1. An emergency stop circuit, a protection circuit, an interlock circuit for opposite movements, and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits).
10 1. Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that couldnot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
11 1. Note that when an error occurs in a relay or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
12
13 = 3 Installation =
14
Stone Wu 11.1 15 (% class="wikigeneratedid" id="H2.1PDFDownloadLink:" %)
16 PDF Download Link:
17
18 (((
19 **[[Download>>doc:PLC Editor.1 User Manual.WebHome||anchor="#HDownload"]]**
20 )))
21
Stone Wu 7.1 22 Use the product within the generic environment specifications described in this manual. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas, flammable gas, vibration or impacts, or expose it to high temperature, condensation (extreme humidity), or rain, and strong wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
23
24 When drilling screw holes or wiring, make sure that cutting and wiring debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions.
25
26 Connect the expansion module, expansion board, and cable securely to their designated connectors. Loose connections may cause malfunctions.
27
28 * To prevent temperature rise, do not install at the bottom, top and vertical. Be sure to install to wall horizontally as shown below.
29 * Please leave more than 50mm space between PLC CPU and other equipment or structures. Try to avoid high-voltage cables, high-voltage devices, and power equipment.
30
Leo Wei 1.1 31 (((
Stone Wu 10.1 32
Leo Wei 1.1 33 )))
34
35 (% style="text-align:center" %)
Stone Wu 7.1 36 [[image:1635751024117-385.png||height="476" width="700" class="img-thumbnail"]]
Leo Wei 1.1 37
Stone Wu 8.1 38 == Precautions ==
Leo Wei 1.1 39
Stone Wu 8.1 40 **Design precautions**
41
Leo Wei 1.1 42 (% style="text-align:center" %)
Stone Wu 7.1 43 [[image:1635751094666-258.png||height="263" width="700" class="img-thumbnail"]]
Leo Wei 1.1 44
Stone Wu 8.1 45 (% class="wikigeneratedid" id="H2InstallationPrecautions" %)
46 **Installation Precautions**
Leo Wei 1.1 47
48 (% style="text-align:center" %)
Stone Wu 7.1 49 [[image:1635751143212-115.png||height="392" width="700" class="img-thumbnail"]]
Leo Wei 1.1 50
Stone Wu 8.1 51 (% class="wikigeneratedid" id="H3WiringPrecautions" %)
52 **Wiring precautions**
Leo Wei 1.1 53
54 (% style="text-align:center" %)
Stone Wu 7.1 55 [[image:1635751294875-245.png||height="486" width="700" class="img-thumbnail"]]
Leo Wei 1.1 56
Stone Wu 8.1 57 (% class="wikigeneratedid" id="H4MaintenancePrecautions" %)
58 **Maintenance precautions**
Leo Wei 1.1 59
60 (% style="text-align:center" %)
61 [[image:1635751348860-366.png||height="324" width="700"]]
62
Stone Wu 8.1 63 == Specification ==
Leo Wei 1.1 64
65 (% style="text-align:center" %)
Stone Wu 7.1 66 [[image:1635751436113-174.png||height="433" width="800" class="img-thumbnail"]]
Leo Wei 1.1 67
68 (% style="text-align:center" %)
Stone Wu 7.1 69 [[image:1635751481409-482.png||height="156" width="700" class="img-thumbnail"]]
Leo Wei 1.1 70
Stone Wu 8.1 71 == Communication interface ==
Leo Wei 1.1 72
73 (% style="text-align:center" %)
Stone Wu 7.1 74 [[image:1635751612052-705.png||height="785" width="700" class="img-thumbnail"]]
Leo Wei 1.1 75
Stone Wu 8.1 76 == Model ==
Leo Wei 1.1 77
78 (% style="text-align:center" %)
Stone Wu 7.1 79 [[image:1635751705584-811.png||height="168" width="700" class="img-thumbnail"]]
Leo Wei 1.1 80
Stone Wu 8.1 81 == Electrical specification ==
Leo Wei 1.1 82
83 (% style="text-align:center" %)
Stone Wu 7.1 84 [[image:1635751765966-857.png||height="465" width="700" class="img-thumbnail"]]
Leo Wei 1.1 85
Stone Wu 8.1 86 == Enverornmental specifications ==
Leo Wei 1.1 87
88 (% style="text-align:center" %)
Stone Wu 7.1 89 [[image:1635751830638-427.png||height="524" width="700" class="img-thumbnail"]]
Leo Wei 1.1 90
Stone Wu 8.1 91 == Input specifications ==
Leo Wei 1.1 92
93 (% style="text-align:center" %)
Stone Wu 7.1 94 [[image:1635751918026-513.png||height="564" width="700" class="img-thumbnail"]]
Leo Wei 1.1 95
Stone Wu 8.1 96 == Output specification ==
Leo Wei 1.1 97
98 (% style="text-align:center" %)
Stone Wu 7.1 99 [[image:1635751973234-515.png||height="720" width="700" class="img-thumbnail"]]
Leo Wei 1.1 100
101 (% style="text-align:center" %)
Stone Wu 7.1 102 [[image:1635752082517-830.png||height="781" width="700" class="img-thumbnail"]]
Leo Wei 1.1 103
Stone Wu 8.1 104 == Terminal ==
Leo Wei 1.1 105
106 (% style="text-align:center" %)
Stone Wu 7.1 107 [[image:1635752127349-858.png||height="294" width="700" class="img-thumbnail"]]
Leo Wei 1.1 108
Stone Wu 8.1 109 == Installation ==
Leo Wei 1.1 110
111 (% style="text-align:center" %)
Stone Wu 7.1 112 [[image:1635752155991-330.png||height="738" width="700" class="img-thumbnail"]]
Leo Wei 1.1 113
Stone Wu 8.1 114 == Battery installation ==
Leo Wei 1.1 115
116 (% style="text-align:center" %)
Stone Wu 7.1 117 [[image:1635752211153-721.png||height="252" width="700" class="img-thumbnail"]]
Leo Wei 1.1 118
Stone Wu 8.1 119 == Terminal for LX3V ==
Leo Wei 1.1 120
121 (% style="text-align:center" %)
Stone Wu 7.1 122 [[image:1635752274494-360.png||height="53" width="700" class="img-thumbnail"]]
Leo Wei 1.1 123
124 (% style="text-align:center" %)
Stone Wu 7.1 125 [[image:1635752304121-875.png||height="290" width="700" class="img-thumbnail"]]
Leo Wei 1.1 126
127 (% style="text-align:center" %)
Stone Wu 7.1 128 [[image:1635752328465-309.png||height="510" width="700" class="img-thumbnail"]]
Leo Wei 1.1 129
130 (% style="text-align:center" %)
Stone Wu 7.1 131 [[image:1635752362200-650.png||height="327" width="700" class="img-thumbnail"]]
Leo Wei 1.1 132
133 (% style="text-align:center" %)
Stone Wu 7.1 134 [[image:1635752393636-867.png||height="226" width="700" class="img-thumbnail"]]
Leo Wei 1.1 135
136 (% style="text-align:center" %)
Stone Wu 7.1 137 [[image:1635752414702-735.png||height="132" width="700" class="img-thumbnail"]]
Leo Wei 1.1 138
139 (% style="text-align:center" %)
Stone Wu 7.1 140 [[image:1635752425894-292.png||height="403" width="700" class="img-thumbnail"]]
Leo Wei 1.1 141
Stone Wu 37.1 142 = 4 Wiring =
Stone Wu 7.1 143
144 1. PLC signal input and output could not be passed on the same cable;
145 1. Signal input cable and output cable could not be in the same pipe with another power cable, could not be bundled together;
146 1. If the above precautions are followed, the input / output wiring will have almost no noise even with a length of 50 to 100 m. However, it is recommended that the wiring length should be within 20m;
147
148 (% class="table-bordered" %)
149 |(% style="width:74px" %)(((
150 (% style="text-align:center" %)
Leo Wei 11.2 151 [[image:Safety Precautions_html_912af9cfcc757eac.jpg||height="64" width="59"]]
Stone Wu 7.1 152
153 Warning
154 )))|(% style="width:1001px" %)(((
155 (% style="text-align:center" %)
Leo Wei 11.2 156 [[image:Safety Precautions_html_e02060a6a61850ed.jpg||height="192" width="552"]]
Stone Wu 7.1 157
158 It is very dangerous to switch the forward and reverse contactor at the same time. For such loads, the interlock must be set on the outside of the PLC besides the PLC internal program settings, as shown in the above picture.
159 )))
160 |(% style="width:74px" %)(((
Leo Wei 11.2 161 [[image:Safety Precautions_html_5f2ba223cca70793.jpg||height="54" width="60"]]
Stone Wu 7.1 162
163 Caution
164 )))|(% style="width:1001px" %)(((
165 Do not wire terminals externally. It may damage the product.
166 )))
167
168 1. Before installation, wiring and other operations, cut off all phases of the power supply externally. Failure to do so may cause electric shock;
169 1. After installation, wiring and other work, the terminal cover must be installed in order to avoid electric shock, before the power operation;
170 1. Connect the AC power supply wiring to the dedicated terminals described in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out;
171 1. Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product;
172 1. Perform grounding to the grounding terminal on the main unit and extension units. Do not use common grounding with heavy electrical systems;
173 1. When there is less than 10ms instantaneous power failure, PLC will continue to work;
Stone Wu 37.1 174 1. When the power is cut off or the voltage is low for a long time, the PLC will stop working and the output will turn off. However, once the power is restored, the operation will restart automatically.
Stone Wu 7.1 175
Stone Wu 39.1 176 == PLC naming ==
Stone Wu 37.1 177
178 (% style="text-align:center" %)
179 [[image:PLC Editor.LX3V programing manual.2\.PLC Installation Manual.WebHome@1635494139870-975.png||height="313" width="700" class="img-thumbnail"]]
180
Stone Wu 40.1 181 == LX3V series PLC ==
Stone Wu 37.1 182
183 **LX3V-2416MT-A wiring demo**
184
185 (% style="text-align:center" %)
186 [[image:PLC Editor.LX3V programing manual.2\.PLC Installation Manual.WebHome@1622440579389-255.png||height="681" width="900" class="img-thumbnail"]]
187
188 **LX3V-2416MT-D wiring demo**
189
190 (% style="text-align:center" %)
191 [[image:PLC Editor.LX3V programing manual.2\.PLC Installation Manual.WebHome@1635491295476-484.png||height="649" width="900" class="img-thumbnail"]]
192
193 (% class="box infomessage" %)
194 (((
195 **✎Note:**
196
197 1. AC power type,the L and N terminal is power supply terminal,the COM and 24V+ is transducer supply output.
198 1. DC power type, the 24V+ and 24V- terminal is DC24v power supply terminal.
199 )))
200
Stone Wu 39.1 201 == Communication interface ==
Stone Wu 37.1 202
203 (% style="text-align:center" %)
204 [[image:PLC Editor.LX3V programing manual.2\.PLC Installation Manual.WebHome@1622441093094-862.png||height="721" width="700" class="img-thumbnail"]]
205
206 (% class="wikigeneratedid" id="H" %)
207 (((
Stone Wu 40.1 208 == (% style="color:inherit; font-family:inherit; font-size:26px" %)LX3V expansion module(%%) ==
Stone Wu 37.1 209
Stone Wu 41.1 210 (% class="wikigeneratedid" %)
Stone Wu 37.1 211 === LX3V-4AD ===
212 )))
213
214 (% style="text-align:center" %)
215 [[image:PLC Editor.LX3V programing manual.2\.PLC Installation Manual.WebHome@1622440720013-275.png||height="292" width="850" class="img-thumbnail"]]
216
217 === (% id="cke_bm_981S" style="display:none" %) [[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11088\wps1.jpg]](%%)LX3V-4DA ===
218
219 (% style="text-align:center" %)
220 [[image:PLC Editor.LX3V programing manual.2\.PLC Installation Manual.WebHome@1622440784787-538.png||height="261" width="850" class="img-thumbnail"]]
221
222 === LX3V-4PT ===
223
224 (% style="text-align:center" %)
225 [[image:PLC Editor.LX3V programing manual.2\.PLC Installation Manual.WebHome@1622440838446-556.png||height="299" width="850" class="img-thumbnail"]]
226
227 === (% style="color:inherit; font-family:inherit" %)LX3V-4PT (%%) ===
228
229 (% style="text-align:center" %)
230 [[image:PLC Editor.LX3V programing manual.2\.PLC Installation Manual.WebHome@1622440911145-424.png]]
231
Stone Wu 7.1 232 = 1.5 Startup and maintenance =
233
234 (((
235 (% class="table-bordered" %)
236 |(((
Leo Wei 11.2 237 [[image:Safety Precautions_html_662a1f3d56163ec3.jpg||height="39" width="35"]] Warning
Stone Wu 7.1 238 )))
239 |(((
240 ✎ Do not touch any terminal while the PLC's power is on. Doing so may cause electric shock or malfunctions;
241
242 ✎ Before cleaning or retightening terminals, cut off all phases of the power supply externally. Failure to do so may cause electric shock;
243
244 ✎ Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual and the associated manuals and ensure the safety of the operation. An operation error may damage the machinery or cause accidents.
245 )))
246 )))
247
248 (((
249 (% class="table-bordered" %)
250 |(((
Leo Wei 11.2 251 [[image:Safety Precautions_html_5f2ba223cca70793.jpg||height="32" width="35"]] Caution
Stone Wu 7.1 252 )))
253 |(((
254 ✎ Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions.
255
256 //For repair, contact WECON Technology Co.,//
257
258 ✎ Turn off the power to the PLC before connecting or disconnecting any extension cable. Failure to do so may cause equipment failures or malfunctions.
259 )))
260 )))
261
262 = 1.6 Maintenance and repair =
263
264 1. Periodic inspection: PLC is equipped with shorter life expectancy consumables;
265 1. For relay output, if it has high frequency of abnormal work or it drives large capacity load, please pay attention to its impact on PLC service life.
266 1. Check with other equipment, please note the following points
267 1. Is there any abnormal temperature rise due to other heating bodies or direct sunlight?
268 1. Is dust or conductive dust invading the machine?
269 1. Is there any wiring and terminal loosening and other anomalies
Leo Wei 1.1 270