Stone Wu 11.1 1 = 1 Safety =
Stone Wu 10.1 2
Stone Wu 7.1 3 Before installation, operation, maintenance, or inspection of this product, thoroughly read through and understand this manual and all of the associated manuals. Also, take care to handle the module properly and safely.
4
5 = 2 Design =
6
7 Make sure to have the following safety circuits outside of the PLC to ensure safe system operation even during external power supply problems or PLC failure.
8
9 1. An emergency stop circuit, a protection circuit, an interlock circuit for opposite movements, and an interlock circuit (to prevent damage to the equipment at the upper and lower positioning limits).
10 1. Note that when the PLC CPU detects an error, such as a watchdog timer error, during self-diagnosis, all outputs are turned off. Also, when an error that couldnot be detected by the PLC CPU occurs in an input/output control block, output control may be disabled. External circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
11 1. Note that when an error occurs in a relay or transistor output device, the output could be held either on or off. For output signals that may lead to serious accidents, external circuits and mechanisms should be designed to ensure safe machinery operation in such a case.
12
13 = 3 Installation =
14
15 Use the product within the generic environment specifications described in this manual. Never use the product in areas with excessive dust, oily smoke, conductive dusts, corrosive gas, flammable gas, vibration or impacts, or expose it to high temperature, condensation (extreme humidity), or rain, and strong wind. If the product is used in such conditions, electric shock, fire, malfunctions, deterioration or damage may occur.
16
17 When drilling screw holes or wiring, make sure that cutting and wiring debris does not enter the ventilation slits. Failure to do so may cause fire, equipment failures or malfunctions.
18
19 Connect the expansion module, expansion board, and cable securely to their designated connectors. Loose connections may cause malfunctions.
20
21 * To prevent temperature rise, do not install at the bottom, top and vertical. Be sure to install to wall horizontally as shown below.
22 * Please leave more than 50mm space between PLC CPU and other equipment or structures. Try to avoid high-voltage cables, high-voltage devices, and power equipment.
23
Leo Wei 1.1 24 (((
Stone Wu 10.1 25
Leo Wei 1.1 26 )))
27
28 (% style="text-align:center" %)
Stone Wu 7.1 29 [[image:1635751024117-385.png||height="476" width="700" class="img-thumbnail"]]
Leo Wei 1.1 30
Stone Wu 8.1 31 == Precautions ==
Leo Wei 1.1 32
Stone Wu 8.1 33 **Design precautions**
34
Leo Wei 1.1 35 (% style="text-align:center" %)
Stone Wu 7.1 36 [[image:1635751094666-258.png||height="263" width="700" class="img-thumbnail"]]
Leo Wei 1.1 37
Stone Wu 8.1 38 (% class="wikigeneratedid" id="H2InstallationPrecautions" %)
39 **Installation Precautions**
Leo Wei 1.1 40
41 (% style="text-align:center" %)
Stone Wu 7.1 42 [[image:1635751143212-115.png||height="392" width="700" class="img-thumbnail"]]
Leo Wei 1.1 43
Stone Wu 8.1 44 (% class="wikigeneratedid" id="H3WiringPrecautions" %)
45 **Wiring precautions**
Leo Wei 1.1 46
47 (% style="text-align:center" %)
Stone Wu 7.1 48 [[image:1635751294875-245.png||height="486" width="700" class="img-thumbnail"]]
Leo Wei 1.1 49
Stone Wu 8.1 50 (% class="wikigeneratedid" id="H4MaintenancePrecautions" %)
51 **Maintenance precautions**
Leo Wei 1.1 52
53 (% style="text-align:center" %)
54 [[image:1635751348860-366.png||height="324" width="700"]]
55
Stone Wu 8.1 56 == Specification ==
Leo Wei 1.1 57
58 (% style="text-align:center" %)
Stone Wu 7.1 59 [[image:1635751436113-174.png||height="433" width="800" class="img-thumbnail"]]
Leo Wei 1.1 60
61 (% style="text-align:center" %)
Stone Wu 7.1 62 [[image:1635751481409-482.png||height="156" width="700" class="img-thumbnail"]]
Leo Wei 1.1 63
Stone Wu 8.1 64 == Communication interface ==
Leo Wei 1.1 65
66 (% style="text-align:center" %)
Stone Wu 7.1 67 [[image:1635751612052-705.png||height="785" width="700" class="img-thumbnail"]]
Leo Wei 1.1 68
Stone Wu 8.1 69 == Model ==
Leo Wei 1.1 70
71 (% style="text-align:center" %)
Stone Wu 7.1 72 [[image:1635751705584-811.png||height="168" width="700" class="img-thumbnail"]]
Leo Wei 1.1 73
Stone Wu 8.1 74 == Electrical specification ==
Leo Wei 1.1 75
76 (% style="text-align:center" %)
Stone Wu 7.1 77 [[image:1635751765966-857.png||height="465" width="700" class="img-thumbnail"]]
Leo Wei 1.1 78
Stone Wu 8.1 79 == Enverornmental specifications ==
Leo Wei 1.1 80
81 (% style="text-align:center" %)
Stone Wu 7.1 82 [[image:1635751830638-427.png||height="524" width="700" class="img-thumbnail"]]
Leo Wei 1.1 83
Stone Wu 8.1 84 == Input specifications ==
Leo Wei 1.1 85
86 (% style="text-align:center" %)
Stone Wu 7.1 87 [[image:1635751918026-513.png||height="564" width="700" class="img-thumbnail"]]
Leo Wei 1.1 88
Stone Wu 8.1 89 == Output specification ==
Leo Wei 1.1 90
91 (% style="text-align:center" %)
Stone Wu 7.1 92 [[image:1635751973234-515.png||height="720" width="700" class="img-thumbnail"]]
Leo Wei 1.1 93
94 (% style="text-align:center" %)
Stone Wu 7.1 95 [[image:1635752082517-830.png||height="781" width="700" class="img-thumbnail"]]
Leo Wei 1.1 96
Stone Wu 8.1 97 == Terminal ==
Leo Wei 1.1 98
99 (% style="text-align:center" %)
Stone Wu 7.1 100 [[image:1635752127349-858.png||height="294" width="700" class="img-thumbnail"]]
Leo Wei 1.1 101
Stone Wu 8.1 102 == Installation ==
Leo Wei 1.1 103
104 (% style="text-align:center" %)
Stone Wu 7.1 105 [[image:1635752155991-330.png||height="738" width="700" class="img-thumbnail"]]
Leo Wei 1.1 106
Stone Wu 8.1 107 == Battery installation ==
Leo Wei 1.1 108
109 (% style="text-align:center" %)
Stone Wu 7.1 110 [[image:1635752211153-721.png||height="252" width="700" class="img-thumbnail"]]
Leo Wei 1.1 111
Stone Wu 8.1 112 == Terminal for LX3V ==
Leo Wei 1.1 113
114 (% style="text-align:center" %)
Stone Wu 7.1 115 [[image:1635752274494-360.png||height="53" width="700" class="img-thumbnail"]]
Leo Wei 1.1 116
117 (% style="text-align:center" %)
Stone Wu 7.1 118 [[image:1635752304121-875.png||height="290" width="700" class="img-thumbnail"]]
Leo Wei 1.1 119
120 (% style="text-align:center" %)
Stone Wu 7.1 121 [[image:1635752328465-309.png||height="510" width="700" class="img-thumbnail"]]
Leo Wei 1.1 122
123 (% style="text-align:center" %)
Stone Wu 7.1 124 [[image:1635752362200-650.png||height="327" width="700" class="img-thumbnail"]]
Leo Wei 1.1 125
126 (% style="text-align:center" %)
Stone Wu 7.1 127 [[image:1635752393636-867.png||height="226" width="700" class="img-thumbnail"]]
Leo Wei 1.1 128
129 (% style="text-align:center" %)
Stone Wu 7.1 130 [[image:1635752414702-735.png||height="132" width="700" class="img-thumbnail"]]
Leo Wei 1.1 131
132 (% style="text-align:center" %)
Stone Wu 7.1 133 [[image:1635752425894-292.png||height="403" width="700" class="img-thumbnail"]]
Leo Wei 1.1 134
Stone Wu 37.1 135 = 4 Wiring =
Stone Wu 7.1 136
137 1. PLC signal input and output could not be passed on the same cable;
138 1. Signal input cable and output cable could not be in the same pipe with another power cable, could not be bundled together;
139 1. If the above precautions are followed, the input / output wiring will have almost no noise even with a length of 50 to 100 m. However, it is recommended that the wiring length should be within 20m;
140
141 (% class="table-bordered" %)
142 |(% style="width:74px" %)(((
143 (% style="text-align:center" %)
Leo Wei 11.2 144 [[image:Safety Precautions_html_912af9cfcc757eac.jpg||height="64" width="59"]]
Stone Wu 7.1 145
146 Warning
147 )))|(% style="width:1001px" %)(((
148 (% style="text-align:center" %)
Leo Wei 11.2 149 [[image:Safety Precautions_html_e02060a6a61850ed.jpg||height="192" width="552"]]
Stone Wu 7.1 150
151 It is very dangerous to switch the forward and reverse contactor at the same time. For such loads, the interlock must be set on the outside of the PLC besides the PLC internal program settings, as shown in the above picture.
152 )))
153 |(% style="width:74px" %)(((
Leo Wei 11.2 154 [[image:Safety Precautions_html_5f2ba223cca70793.jpg||height="54" width="60"]]
Stone Wu 7.1 155
156 Caution
157 )))|(% style="width:1001px" %)(((
158 Do not wire terminals externally. It may damage the product.
159 )))
160
161 1. Before installation, wiring and other operations, cut off all phases of the power supply externally. Failure to do so may cause electric shock;
162 1. After installation, wiring and other work, the terminal cover must be installed in order to avoid electric shock, before the power operation;
163 1. Connect the AC power supply wiring to the dedicated terminals described in this manual. If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn out;
164 1. Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension units. Doing so may cause damage to the product;
165 1. Perform grounding to the grounding terminal on the main unit and extension units. Do not use common grounding with heavy electrical systems;
166 1. When there is less than 10ms instantaneous power failure, PLC will continue to work;
Stone Wu 37.1 167 1. When the power is cut off or the voltage is low for a long time, the PLC will stop working and the output will turn off. However, once the power is restored, the operation will restart automatically.
Stone Wu 7.1 168
Stone Wu 39.1 169 == PLC naming ==
Stone Wu 37.1 170
171 (% style="text-align:center" %)
Stone Wu 50.1 172 [[image:1635494139870-975.png||height="313" width="700" class="img-thumbnail"]]
Stone Wu 37.1 173
Stone Wu 40.1 174 == LX3V series PLC ==
Stone Wu 37.1 175
176 **LX3V-2416MT-A wiring demo**
177
178 (% style="text-align:center" %)
Stone Wu 50.1 179 [[image:1622440579389-255.png||height="681" width="900" class="img-thumbnail"]]
Stone Wu 37.1 180
181 **LX3V-2416MT-D wiring demo**
182
183 (% style="text-align:center" %)
Stone Wu 50.1 184 [[image:1635491295476-484.png||height="649" width="900" class="img-thumbnail"]]
Stone Wu 37.1 185
186 (% class="box infomessage" %)
187 (((
188 **✎Note:**
189
190 1. AC power type,the L and N terminal is power supply terminal,the COM and 24V+ is transducer supply output.
191 1. DC power type, the 24V+ and 24V- terminal is DC24v power supply terminal.
192 )))
193
Stone Wu 39.1 194 == Communication interface ==
Stone Wu 37.1 195
196 (% style="text-align:center" %)
Stone Wu 50.1 197 [[image:1622441093094-862.png||height="721" width="700" class="img-thumbnail"]]
Stone Wu 37.1 198
199 (% class="wikigeneratedid" id="H" %)
200 (((
Stone Wu 47.1 201 == (% style="color:inherit; font-family:inherit; font-size:26px" %)Expansion module(%%) ==
Stone Wu 37.1 202
203 === LX3V-4AD ===
204 )))
205
206 (% style="text-align:center" %)
Stone Wu 50.1 207 [[image:1622440720013-275.png||height="292" width="850" class="img-thumbnail"]]
Stone Wu 37.1 208
Stone Wu 46.1 209 === (% id="cke_bm_981S" style="display:none" %)[[image:file:///C:\Users\Administrator\AppData\Local\Temp\ksohtml11088\wps1.jpg]](%%)LX3V-4DA ===
Stone Wu 37.1 210
211 (% style="text-align:center" %)
Stone Wu 50.1 212 [[image:1622440784787-538.png||height="261" width="850" class="img-thumbnail"]]
Stone Wu 37.1 213
214 === LX3V-4PT ===
215
216 (% style="text-align:center" %)
Stone Wu 50.1 217 [[image:1622440838446-556.png||height="299" width="850" class="img-thumbnail"]]
Stone Wu 37.1 218
Stone Wu 45.1 219 === (% style="color:inherit; font-family:inherit" %)LX3V-4TC (%%) ===
Stone Wu 37.1 220
221 (% style="text-align:center" %)
Stone Wu 50.1 222 [[image:1622440911145-424.png]]
Stone Wu 37.1 223
Stone Wu 53.1 224 = 5 Startup and maintenance =
Stone Wu 7.1 225
226 (((
227 (% class="table-bordered" %)
Stone Wu 48.1 228 (% class="warning" %)|(((
Leo Wei 11.2 229 [[image:Safety Precautions_html_662a1f3d56163ec3.jpg||height="39" width="35"]] Warning
Stone Wu 7.1 230 )))
231 |(((
Stone Wu 48.1 232 * Do not touch any terminal while the PLC's power is on. Doing so may cause electric shock or malfunctions;
233 * Before cleaning or retightening terminals, cut off all phases of the power supply externally. Failure to do so may cause electric shock;
234 * Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual and the associated manuals and ensure the safety of the operation. An operation error may damage the machinery or cause accidents.
Stone Wu 7.1 235 )))
236 )))
237
238 (((
239 (% class="table-bordered" %)
Stone Wu 48.1 240 (% class="warning" %)|(((
Leo Wei 11.2 241 [[image:Safety Precautions_html_5f2ba223cca70793.jpg||height="32" width="35"]] Caution
Stone Wu 7.1 242 )))
243 |(((
Stone Wu 48.1 244 * Do not disassemble or modify the PLC. Doing so may cause fire, equipment failures, or malfunctions.
245 * //For repair, contact WECON Technology Co.,//
246 * Turn off the power to the PLC before connecting or disconnecting any extension cable. Failure to do so may cause equipment failures or malfunctions.
Stone Wu 7.1 247 )))
248 )))
249
Stone Wu 52.1 250 = 6 Maintenance and repair =
Stone Wu 7.1 251
252 1. Periodic inspection: PLC is equipped with shorter life expectancy consumables;
253 1. For relay output, if it has high frequency of abnormal work or it drives large capacity load, please pay attention to its impact on PLC service life.
254 1. Check with other equipment, please note the following points