Changes for page 07 Communication

Last modified by Devin Chen on 2024/08/19 14:28

From version 18.1
edited by Devin Chen
on 2024/08/19 14:14
Change comment: Rollback to version 16.1
To version 7.3
edited by Stone Wu
on 2022/07/28 11:28
Change comment: Renamed from xwiki:PLC Editor.LX3V programing manual.8\.1\. Communication.WebHome

Summary

Details

Page properties
Parent
... ... @@ -1,1 +1,1 @@
1 -PLC Editor.WebHome
1 +PLC Editor.LX3V programing manual.WebHome
Author
... ... @@ -1,1 +1,1 @@
1 -XWiki.DevinChen
1 +XWiki.Stone
Content
... ... @@ -1,4 +1,4 @@
1 -= **PLC COM2 Modbus RTU** =
1 += **1 PLC COM2 Modbus RTU** =
2 2  
3 3  == **Protocol Setting (D8126)** ==
4 4  
... ... @@ -6,7 +6,6 @@
6 6  |=WECON PLC Protocol|Using WECON PLC Protocol|01H
7 7  |=MODBUS RTU Master|PLC is slave device|02H
8 8  |=MODBUS ASCII Master|PLC is slave device|03H
9 -|=User-defined Protocol|Using User-defined Protocol|10H
10 10  |=MODBUS RTU Slave|PLC is master device|20H
11 11  |=MODBUS ASCII Slave|PLC is master device|30H
12 12  
... ... @@ -57,8 +57,8 @@
57 57  |S0 ~~ S999|0xE000 ~~ 0xE3E7|57344 ~~ 58343
58 58  |T0 ~~ T256|0xF000 ~~ 0xF100|61440 ~~ 61696
59 59  |C0 ~~ C255|0xF400 ~~ 0xF4FF|62464 ~~ 62719
60 -|X0 ~~ X377|0xF800 ~~ 0xF8FF|63488 ~~ 63743
61 -|Y0 ~~ Y377|0xFC00 ~~ 0xFCFF|64512 ~~ 64767
59 +|X0 ~~ X255|0xF800 ~~ 0xF9FE|63488 ~~ 63998
60 +|Y0 ~~ Y255|0xFC00 ~~ 0xFDFE|64512 ~~ 65022
62 62  |(% colspan="3" %)** PLC Word Address**
63 63  |(% rowspan="2" %)PLC Address|(% colspan="2" %)MODBUS Address
64 64  |Hex|Decimal
... ... @@ -67,7 +67,7 @@
67 67  |C0 ~~ C199|0xF400 ~~ 0xF4C7|62464 ~~ 62663
68 68  |C200 ~~ C255|0xF700 ~~ 0xF7FF|63232 ~~ 63487
69 69  
70 -== **MODBUS function code introduction** ==
69 +== **MODBUS function fode introduction** ==
71 71  
72 72  **Function code 0x01(01): read coil (bit address)**
73 73  
... ... @@ -190,13 +190,13 @@
190 190  
191 191  [[image:1641782240401-942.png||height="161" width="754"]]
192 192  
193 -= (% style="color:inherit; font-family:inherit" %)**N:N network**(%%) =
192 += (% style="color:inherit; font-family:inherit" %)**2 N:N network**(%%) =
194 194  
195 195  **LX3VP COM2 N:N Application**
196 196  
197 197  == **LX3VP COM2 N:N Connection** ==
198 198  
199 -PLC built-in N:N connection protocol provides an effective way to exchange data among multiple PLC (Max. 8 devices). Technically, it only requires the twisted pair RS485 cable to connect with each PLC COM2 (in parallel).
198 +PLC built-in N:N connection protocol provides a effective way to exchange data among multiple PLC (Max. 8 devices). Technically, it only requires the twisted pair RS485 cable to connect with each PLC COM2 (in parallel).
200 200  
201 201  (% style="text-align:center" %)
202 202  [[image:9.Communication example_html_8c43baa1ae891689.jpg||height="142" width="500" class="img-thumbnail"]]
... ... @@ -263,7 +263,7 @@
263 263  )))
264 264  |M8191|Processing sending data
265 265  
266 -== **Communications format** ==
265 +== **Communications format:** ==
267 267  
268 268  (% border="1" %)
269 269  |=**Item**|=(% style="width: 115px;" %)**Parameters**|=(% style="width: 239px;" %)**b15(RS2)**|=**b14-b8**|=**b7**|=**b6**|=**b5**|=**b4**|=**b3**|=**b2**|=**b1**|=**b0**
... ... @@ -283,20 +283,6 @@
283 283  |(% rowspan="2" %)**Data bit**|(% style="width:115px" %)7 bit|(% style="width:239px" %)-|-|-|-|-|-|-|-|0
284 284  |(% style="width:115px" %)8 bit|(% style="width:239px" %)-|-|-|-|-|-|-|-|1
285 285  
286 -== **Communication error code (D8211~~D8218)** ==
287 -
288 -|=(% style="width: 195px;" %)**Error code**|=(% style="width: 881px;" %)**Description**
289 -|(% style="width:195px" %)1|(% style="width:881px" %)The monitoring period has elapsed, and the slave station has not responded to requests from the master station yet.
290 -|(% style="width:195px" %)2|(% style="width:881px" %)The other slave stations have responded to requests sent by the master station.
291 -|(% style="width:195px" %)3|(% style="width:881px" %)The count values in the parameter data do not match those responded by the slave stations.
292 -|(% style="width:195px" %)4|(% style="width:881px" %)The response messages from the slave stations are incorrect.
293 -|(% style="width:195px" %)17|(% style="width:881px" %)The monitoring period has elapsed,the master station has not sent a request to the next slave station yet.
294 -|(% style="width:195px" %)20|(% style="width:881px" %)The messages from the master station are incorrect.
295 -|(% style="width:195px" %)33|(% style="width:881px" %)The slave station is unresponsive.
296 -|(% style="width:195px" %)34|(% style="width:881px" %)The other slave stations have responded to requests sent by the master station.
297 -|(% style="width:195px" %)35|(% style="width:881px" %)The count values in the parameter data do not match those responded by the slave stations.
298 -|(% style="width:195px" %)49|(% style="width:881px" %)The slave station received requests from the master station before receiving the parameters.
299 -
300 300  == **Program example** ==
301 301  
302 302  LX3VP COM2 port communication parameters: 9600, 1, 8, NONE. Register block mode: 3
... ... @@ -319,7 +319,7 @@
319 319  * In LX3VP series PLC, only one kind of N:N configuration available. Second mode would be disabled when LX3VP built-in N:N protocol configured.
320 320  )))
321 321  
322 -= (% style="color:inherit; font-family:inherit" %)**RS485-BD and ETH-BD communiaction**(%%) =
307 += (% style="color:inherit; font-family:inherit" %)**3 RS485-BD and ETH-BD communiaction**(%%) =
323 323  
324 324  Please kindly check the link as below.
325 325