1 -= **1 PLC COM2 Modbus RTU** =
1 += **PLC COM2 Modbus RTU** =
2 2  
3 3  == **Protocol Setting (D8126)** ==
4 4  
... ... @@ -6,6 +6,7 @@
6 6  |=WECON PLC Protocol|Using WECON PLC Protocol|01H
7 7  |=MODBUS RTU Master|PLC is slave device|02H
8 8  |=MODBUS ASCII Master|PLC is slave device|03H
9 +|=User-defined Protocol|Using User-defined Protocol|10H
9 9  |=MODBUS RTU Slave|PLC is master device|20H
10 10  |=MODBUS ASCII Slave|PLC is master device|30H
11 11  
... ... @@ -56,8 +56,8 @@
56 56  |S0 ~~ S999|0xE000 ~~ 0xE3E7|57344 ~~ 58343
57 57  |T0 ~~ T256|0xF000 ~~ 0xF100|61440 ~~ 61696
58 58  |C0 ~~ C255|0xF400 ~~ 0xF4FF|62464 ~~ 62719
59 -|X0 ~~ X255|0xF800 ~~ 0xF9FE|63488 ~~ 63998
60 -|Y0 ~~ Y255|0xFC00 ~~ 0xFDFE|64512 ~~ 65022
60 +|X0 ~~ X377|0xF800 ~~ 0xF8FF|63488 ~~ 63743
61 +|Y0 ~~ Y377|0xFC00 ~~ 0xFCFF|64512 ~~ 64767
61 61  |(% colspan="3" %)** PLC Word Address**
62 62  |(% rowspan="2" %)PLC Address|(% colspan="2" %)MODBUS Address
63 63  |Hex|Decimal
... ... @@ -148,8 +148,6 @@
148 148  
149 149  **Read bit address from device**
150 150  
151 -(When reading the bit address, the return value of 256 means that the coil is turned ON, and the return value of 0 means that the coil is turned OFF.)
152 -
153 153  (% style="text-align:center" %)
154 154  [[image:1641781999957-637.png||height="390" width="750" class="img-thumbnail"]]
155 155  
... ... @@ -189,13 +189,13 @@
189 189  
190 190  [[image:1641782240401-942.png||height="161" width="754"]]
191 191  
192 -= (% style="color:inherit; font-family:inherit" %)**2 N:N network**(%%) =
191 += (% style="color:inherit; font-family:inherit" %)**N:N network**(%%) =
193 193  
194 194  **LX3VP COM2 N:N Application**
195 195  
196 196  == **LX3VP COM2 N:N Connection** ==
197 197  
198 -PLC built-in N:N connection protocol provides a effective way to exchange data among multiple PLC (Max. 8 devices). Technically, it only requires the twisted pair RS485 cable to connect with each PLC COM2 (in parallel).
197 +PLC built-in N:N connection protocol provides an effective way to exchange data among multiple PLC (Max. 8 devices). Technically, it only requires the twisted pair RS485 cable to connect with each PLC COM2 (in parallel).
199 199  
200 200  (% style="text-align:center" %)
201 201  [[image:9.Communication example_html_8c43baa1ae891689.jpg||height="142" width="500" class="img-thumbnail"]]
... ... @@ -262,7 +262,7 @@
262 262  )))
263 263  |M8191|Processing sending data
264 264  
265 -== **Communications format:** ==
264 +== **Communications format** ==
266 266  
267 267  (% border="1" %)
268 268  |=**Item**|=(% style="width: 115px;" %)**Parameters**|=(% style="width: 239px;" %)**b15(RS2)**|=**b14-b8**|=**b7**|=**b6**|=**b5**|=**b4**|=**b3**|=**b2**|=**b1**|=**b0**
... ... @@ -282,6 +282,20 @@
282 282  |(% rowspan="2" %)**Data bit**|(% style="width:115px" %)7 bit|(% style="width:239px" %)-|-|-|-|-|-|-|-|0
283 283  |(% style="width:115px" %)8 bit|(% style="width:239px" %)-|-|-|-|-|-|-|-|1
284 284  
284 +== **Communication error code (D8211~~D8218)** ==
285 +
286 +|=(% style="width: 195px;" %)**Error code**|=(% style="width: 881px;" %)**Description**
287 +|(% style="width:195px" %)1|(% style="width:881px" %)The monitoring period has elapsed, and the slave station has not responded to requests from the master station yet.
288 +|(% style="width:195px" %)2|(% style="width:881px" %)The other slave stations have responded to requests sent by the master station.
289 +|(% style="width:195px" %)3|(% style="width:881px" %)The count values in the parameter data do not match those responded by the slave stations.
290 +|(% style="width:195px" %)4|(% style="width:881px" %)The response messages from the slave stations are incorrect.
291 +|(% style="width:195px" %)17|(% style="width:881px" %)The monitoring period has elapsed,the master station has not sent a request to the next slave station yet.
292 +|(% style="width:195px" %)20|(% style="width:881px" %)The messages from the master station are incorrect.
293 +|(% style="width:195px" %)33|(% style="width:881px" %)The slave station is unresponsive.
294 +|(% style="width:195px" %)34|(% style="width:881px" %)The other slave stations have responded to requests sent by the master station.
295 +|(% style="width:195px" %)35|(% style="width:881px" %)The count values in the parameter data do not match those responded by the slave stations.
296 +|(% style="width:195px" %)49|(% style="width:881px" %)The slave station received requests from the master station before receiving the parameters.
297 +
285 285  == **Program example** ==
286 286  
287 287  LX3VP COM2 port communication parameters: 9600, 1, 8, NONE. Register block mode: 3
... ... @@ -304,7 +304,7 @@
304 304  * In LX3VP series PLC, only one kind of N:N configuration available. Second mode would be disabled when LX3VP built-in N:N protocol configured.
305 305  )))
306 306  
307 -= (% style="color:inherit; font-family:inherit" %)**3 RS485-BD and ETH-BD communiaction**(%%) =
320 += (% style="color:inherit; font-family:inherit" %)**RS485-BD and ETH-BD communiaction**(%%) =
308 308  
309 309  Please kindly check the link as below.
310 310